SPEC 45257
CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN/THWN-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8 (cable size 8 & 6 AWG has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 AWG uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Polyvinyl Chloride (PVC)
Applications and Features:
Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in wet and dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
SOUTHWIRE® {UL} XX AWG (XX.X{mm2}) CU 4 CDRS TYPE TC-ER THHN OR THWN-2 CDRS GW 1 X X AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 557694◊ | 8 | 4 | 7 | 0.142 | 30 | 1 x 10 | 60 | 0.701 | 238 | 383 | BK |
| 553438◊ | 6 | 4 | 7 | 0.178 | 30 | 1 x 8 | 60 | 0.8 | 379 | 564 | BK |
| 601989◊ | 4 | 4 | 7 | 0.225 | 40 | 1 x 8 | 80 | 0.948 | 572 | 851 | BK |
| 601997◊ | 2 | 4 | 7 | 0.283 | 40 | 1 x 6 | 80 | 1.088 | 910 | 1226 | BK |
| 602003 | 1 | 4 | 19 | 0.322 | 50 | 1 x 6 | 80 | 1.233 | 1126 | 1528 | BK |
| 554568◊ | 1/0 | 4 | 19 | 0.362 | 50 | 1 x 6 | 80 | 1.319 | 1399 | 1829 | BK |
| 556720◊ | 2/0 | 4 | 19 | 0.405 | 50 | 1 x 6 | 80 | 1.425 | 1742 | 2218 | BK |
| 602029◊ | 3/0 | 4 | 19 | 0.456 | 50 | 1 x 4 | 80 | 1.546 | 2223 | 2765 | BK |
| 444745◊ | 4/0 | 4 | 19 | 0.512 | 50 | 1 x 4 | 80 | 1.652 | 2770 | 3284 | BK |
| 602045◊ | 250 | 4 | 37 | 0.558 | 60 | 1 x 4 | 110 | 1.871 | 3249 | 4043 | BK |
| 602060◊ | 350 | 4 | 37 | 0.661 | 60 | 1 x 3 | 110 | 2.11 | 4530 | 5408 | BK |
| TBA | 400 | 4 | 37 | 0.706 | 70 | 1 x 3 | 110 | 2.273 | 5152 | 5958 | BK |
| 552513◊ | 500 | 4 | 37 | 0.789 | 60 | 1 x 2 | 110 | 2.412 | 6444 | 7441 | BK |
| 593375 | 500 | 4 | 37 | 0.789 | 60 | 1 x 250 | 110 | 2.485 | 7017 | 8022 | BK |
| 604819 | 600 | 4 | 61 | 0.866 | 70 | 1 x 2 | 110 | 2.644 | 7691 | 8900 | BK |
| 456241 | 600 | 4 | 61 | 0.866 | 70 | 1 x 1/0 | 115 | 2.656 | 7813 | 9059 | BK |
| 604827 | 750 | 4 | 61 | 0.968 | 70 | 1 x 1 | 140 | 2.998 | 9616 | 11403 | BK |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 557694◊ | 8 | 4 | 2.8 | 528 | 0.653 | 0.81 | 0.052 | 40 | 44 |
| 553438◊ | 6 | 4 | 3.2 | 839 | 0.411 | 0.51 | 0.051 | 52 | 60 |
| 601989◊ | 4 | 4 | 3.8 | 1335 | 0.258 | 0.32 | 0.048 | 68 | 76 |
| 601997◊ | 2 | 4 | 5.4 | 2123 | 0.162 | 0.201 | 0.045 | 92 | 104 |
| 602003 | 1 | 4 | 6.2 | 2678 | 0.128 | 0.159 | 0.046 | 104 | 116 |
| 554568◊ | 1/0 | 4 | 6.6 | 3379 | 0.102 | 0.127 | 0.044 | 120 | 136 |
| 556720◊ | 2/0 | 4 | 7.1 | 4259 | 0.082 | 0.102 | 0.043 | 140 | 156 |
| 602029◊ | 3/0 | 4 | 7.7 | 5369 | 0.064 | 0.079 | 0.042 | 160 | 180 |
| 444745◊ | 4/0 | 4 | 8.3 | 6771 | 0.051 | 0.063 | 0.041 | 184 | 208 |
| 602045◊ | 250 | 4 | 9.4 | 8000 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 602060◊ | 350 | 4 | 12.7 | 11200 | 0.031 | 0.039 | 0.04 | 248 | 280 |
| TBA | 400 | 4 | 13.6 | 12800 | 0.027 | 0.035 | 0.04 | 268 | 304 |
| 552513◊ | 500 | 4 | 14.5 | 16000 | 0.021 | 0.027 | 0.039 | 304 | 344 |
| 593375 | 500 | 4 | 14.9 | 16000 | 0.021 | 0.027 | 0.039 | 304 | 344 |
| 604819 | 600 | 4 | 15.9 | 19200 | 0.018 | 0.024 | 0.039 | 336 | 380 |
| 456241 | 600 | 4 | 15.9 | 19200 | 0.018 | 0.024 | 0.039 | 336 | 380 |
| 604827 | 750 | 4 | 18 | 24000 | 0.014 | 0.019 | 0.038 | 380 | 428 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.007
Updated On: Sept. 19, 2025, 6:03 p.m. UTC