SPEC 45257

CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Power Cable 600 Volt Four Conductor Copper, Polyvinyl Chloride (PVC) with nylon layer insulation THHN/THWN-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer Type THHN/THWN-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8 (cable size 8 & 6 AWG has insulated green ground)
  4. Filler:Paper filler (cable size 8 & 6 AWG uses Polypropylene filler)
  5. Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
  6. Overall Jacket:Polyvinyl Chloride (PVC)

Applications and Features:

Southwire’s 600 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C in wet and dry locations, 105°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE, 4-ORANGE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    SOUTHWIRE® {UL} XX AWG (XX.X{mm2}) CU 4 CDRS TYPE TC-ER THHN OR THWN-2 CDRS GW 1 X X AWG 90°C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE {YYYY}
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODCopper WeightApprox. WeightJacket Color
    AWG/KcmilNo. of StrandsinchmilNo. x AWGmilinchlb/1000ftlb/1000ft
    557694◊8470.142301 x 10600.701238383BK
    553438◊6470.178301 x 8600.8379564BK
    601989◊4470.225401 x 8800.948572851BK
    601997◊2470.283401 x 6801.0889101226BK
    60200314190.322501 x 6801.23311261528BK
    554568◊1/04190.362501 x 6801.31913991829BK
    556720◊2/04190.405501 x 6801.42517422218BK
    602029◊3/04190.456501 x 4801.54622232765BK
    444745◊4/04190.512501 x 4801.65227703284BK
    602045◊2504370.558601 x 41101.87132494043BK
    602060◊3504370.661601 x 31102.1145305408BK
    TBA4004370.706701 x 31102.27351525958BK
    552513◊5004370.789601 x 21102.41264447441BK
    5933755004370.789601 x 2501102.48570178022BK
    6048196004610.866701 x 21102.64476918900BK
    4562416004610.866701 x 1/01152.65678139059BK
    6048277504610.968701 x 11402.998961611403BK
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    557694◊842.85280.6530.810.0524044
    553438◊643.28390.4110.510.0515260
    601989◊443.813350.2580.320.0486876
    601997◊245.421230.1620.2010.04592104
    602003146.226780.1280.1590.046104116
    554568◊1/046.633790.1020.1270.044120136
    556720◊2/047.142590.0820.1020.043140156
    602029◊3/047.753690.0640.0790.042160180
    444745◊4/048.367710.0510.0630.041184208
    602045◊25049.480000.0430.0530.041204232
    602060◊350412.7112000.0310.0390.04248280
    TBA400413.6128000.0270.0350.04268304
    552513◊500414.5160000.0210.0270.039304344
    593375500414.9160000.0210.0270.039304344
    604819600415.9192000.0180.0240.039336380
    456241600415.9192000.0180.0240.039336380
    604827750418240000.0140.0190.038380428
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.