SPEC 45254
CU 600/1000V XLPE Insulation Thermoplastic LSZH-TP XHHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free
Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket with 1 Bare CU Ground. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8 (cable size 8 & 6 has insulated green ground)
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE® {UL} XXX AWG CU 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG CU SOLONON® 90°C JACKET SUN RES OIL RES I FOR DIRECT BURIAL 600V
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | Jacket Color |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | |||
| 561568 | 8 | 3 | 7 | 0.141 | 45 | 1 x 10 GG | 60 | 0.710 | 186 | 340 | Black |
| 561567 | 6 | 3 | 7 | 0.177 | 45 | 1 x 8 GG | 60 | 0.795 | 297 | 480 | Black |
| 551378 | 2 | 3 | 7 | 0.282 | 45 | 1 x 6 | 80 | 0.980 | 702 | 979 | Black |
| TBA | 1 | 3 | 19 | 0.322 | 55 | 1 x 6 | 80 | 1.095 | 863 | 1172 | Black |
| TBA | 1/0 | 3 | 19 | 0.361 | 55 | 1 x 6 | 80 | 1.179 | 1067 | 1408 | Black |
| 561564 | 2/0 | 3 | 19 | 0.405 | 55 | 1 x 6 | 80 | 1.302 | 1326 | 1719 | Black |
| 565815 | 3/0 | 3 | 19 | 0.456 | 55 | 1 x 4 | 80 | 1.406 | 1699 | 2132 | Black |
| 959718 | 4/0 | 3 | 19 | 0.512 | 55 | 1 x 4 | 80 | 1.531 | 2109 | 2615 | Black |
| TBA | 250 | 3 | 37 | 0.558 | 65 | 1 x 4 | 80 | 1.648 | 2465 | 3029 | Black |
| TBA | 350 | 3 | 37 | 0.661 | 65 | 1 x 3 | 110 | 1.931 | 3435 | 4217 | Black |
| 564938 | 500 | 3 | 37 | 0.789 | 65 | 1 x 2 | 110 | 2.183 | 4884 | 5745 | Black |
| 552362 | 500 | 3 | 37 | 0.789 | 65 | 3 x 6 | 110 | 2.233 | 4923 | 5965 | Black |
| TBA | 750 | 3 | 61 | 0.968 | 80 | 1 x 1 | 110 | 2.658 | 7268 | 8547 | Black |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | ||
| 561568 | 8 | 3 | 2.8 | 396 | 0.653 | 0.786 | 0.052 | 50 | 55 |
| 561567 | 6 | 3 | 3.2 | 629 | 0.411 | 0.495 | 0.051 | 65 | 75 |
| 551378 | 2 | 3 | 3.9 | 1592 | 0.162 | 0.195 | 0.045 | 115 | 130 |
| TBA | 1 | 3 | 5.5 | 2008 | 0.128 | 0.154 | 0.046 | 130 | 145 |
| TBA | 1/0 | 3 | 5.9 | 2534 | 0.102 | 0.122 | 0.044 | 150 | 170 |
| 561564 | 2/0 | 3 | 6.5 | 3194 | 0.081 | 0.097 | 0.043 | 175 | 195 |
| 565815 | 3/0 | 3 | 7.0 | 4027 | 0.064 | 0.078 | 0.042 | 200 | 225 |
| 959718 | 4/0 | 3 | 7.7 | 5078 | 0.051 | 0.062 | 0.041 | 230 | 260 |
| TBA | 250 | 3 | 8.2 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| TBA | 350 | 3 | 9.7 | 8400 | 0.031 | 0.039 | 0.040 | 310 | 350 |
| 564938 | 500 | 3 | 13.1 | 12000 | 0.022 | 0.029 | 0.039 | 380 | 430 |
| 552362 | 500 | 3 | 13.4 | 12000 | 0.022 | 0.029 | 0.039 | 380 | 430 |
| TBA | 750 | 3 | 15.9 | 18000 | 0.014 | 0.022 | 0.038 | 475 | 535 |
*Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.006
Updated On: April 14, 2025, 10:03 p.m. UTC

