SPEC 25077
CU 1000V LSZH Solononplus™ Insulation. RW90
Single Copper Conductors, LSZH Insulation Solononplus™, Sunlight Resistant, 1000V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Low Smoke Zero Halogen Solononplus™ (XLPO)
Applications and Features:
Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green Duraground™ also available.
Specifications:
Sample Print Legend:
SOUTHWIRE SOLONONplus{TM} LSZH XLPO 156205 {CSA} XXX KCMIL (XXX{mm2}) CU RW90 1000V VW-1 HAL-FREE TC PRI PRII GRI GRII -40°C SR FT4 ST-1
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Strand | Insul. Thickness | Insulation Color | Approx. OD | Approx. Weight | Min Bending Radius | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mil | inch | lb/1000ft | inch | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | ||
| TBA | 14 | 7 | 45 | BK | 0.161 | 22 | 0.6 | 2.631 | 3.265 | 0.058 | 25 |
| 456277 | 12 | 7 | 45 | BK | 0.185 | 36 | 0.7 | 1.662 | 2.063 | 0.054 | 30 |
| 456282 | 10 | 7 | 45 | BK | 0.209 | 51 | 0.8 | 1.04 | 1.291 | 0.05 | 40 |
| TBA | 8 | 7 | 45 | 0.232 | 66 | 0.9 | 0.653 | 0.81 | 0.052 | 55 | |
| TBA | 6 | 7 | 60 | 0.298 | 106 | 1.2 | 0.411 | 0.51 | 0.051 | 75 | |
| TBA | 4 | 7 | 60 | 0.345 | 159 | 1.4 | 0.258 | 0.32 | 0.048 | 95 | |
| TBA | 2 | 7 | 60 | 0.403 | 241 | 1.6 | 0.162 | 0.201 | 0.045 | 130 | |
| TBA | 1/0 | 19 | 80 | BK | 0.522 | 389 | 2.1 | 0.102 | 0.127 | 0.044 | 170 |
| TBA | 2/0 | 19 | 80 | BK | 0.565 | 480 | 2.3 | 0.082 | 0.102 | 0.043 | 195 |
| TBA | 3/0 | 19 | 80 | BK | 0.616 | 594 | 2.5 | 0.064 | 0.079 | 0.042 | 225 |
| TBA | 4/0 | 19 | 80 | BK | 0.672 | 737 | 2.7 | 0.051 | 0.063 | 0.041 | 260 |
| TBA | 250 | 37 | 90 | BK | 0.738 | 875 | 3 | 0.043 | 0.053 | 0.041 | 290 |
| TBA | 350 | 37 | 90 | BK | 0.841 | 1201 | 3.4 | 0.031 | 0.039 | 0.04 | 350 |
| 664475 | 500 | 37 | 90 | BK | 0.956 | 1716 | 3.8 | 0.021 | 0.027 | 0.039 | 430 |
| TBA | 750 | 61 | 90 | BK | 1.148 | 2485 | 5.7 | 0.014 | 0.019 | 0.038 | 535 |
| 664478 | 1000 | 61 | 90 | BK | 1.307 | 3348 | 6.5 | 0.011 | 0.016 | 0.037 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Weights and Measurements (Metric)
| Stock Number | Cond. Size | Strand | Insul. Thickness | Insulation Color | Approx. OD | Approx. Weight | Min Bending Radius | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity In Raceway 90°C |
|---|---|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | No. | mm | mm | kg/km | mm | Ω/km | Ω/km | Ω/km | Amp | ||
| TBA | 14 | 7 | 1.14 | BK | 4.09 | 33 | 15.24 | 8.63 | 10.71 | 0.1903 | 25 |
| 456277 | 12 | 7 | 1.14 | BK | 4.70 | 54 | 17.78 | 5.45 | 6.77 | 0.1772 | 30 |
| 456282 | 10 | 7 | 1.14 | BK | 5.31 | 76 | 20.32 | 3.41 | 4.24 | 0.1640 | 40 |
| TBA | 8 | 7 | 1.14 | 5.89 | 98 | 22.86 | 2.14 | 2.66 | 0.1706 | 55 | |
| TBA | 6 | 7 | 1.52 | 7.57 | 158 | 30.48 | 1.35 | 1.67 | 0.1673 | 75 | |
| TBA | 4 | 7 | 1.52 | 8.76 | 237 | 35.56 | 0.85 | 1.05 | 0.1575 | 95 | |
| TBA | 2 | 7 | 1.52 | 10.24 | 359 | 40.64 | 0.53 | 0.66 | 0.1476 | 130 | |
| TBA | 1/0 | 19 | 2.03 | BK | 13.26 | 579 | 53.34 | 0.33 | 0.42 | 0.1444 | 170 |
| TBA | 2/0 | 19 | 2.03 | BK | 14.35 | 714 | 58.42 | 0.27 | 0.33 | 0.1411 | 195 |
| TBA | 3/0 | 19 | 2.03 | BK | 15.65 | 884 | 63.50 | 0.21 | 0.26 | 0.1378 | 225 |
| TBA | 4/0 | 19 | 2.03 | BK | 17.07 | 1097 | 68.58 | 0.17 | 0.21 | 0.1345 | 260 |
| TBA | 250 | 37 | 2.29 | BK | 18.75 | 1302 | 76.20 | 0.14 | 0.17 | 0.1345 | 290 |
| TBA | 350 | 37 | 2.29 | BK | 21.36 | 1787 | 86.36 | 0.10 | 0.13 | 0.1312 | 350 |
| 664475 | 500 | 37 | 2.29 | BK | 24.28 | 2554 | 96.52 | 0.07 | 0.09 | 0.1280 | 430 |
| TBA | 750 | 61 | 2.29 | BK | 29.16 | 3698 | 144.78 | 0.05 | 0.06 | 0.1247 | 535 |
| 664478 | 1000 | 61 | 2.29 | BK | 33.20 | 4982 | 165.10 | 0.04 | 0.05 | 0.1214 | 615 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Revision: 1.000.005
Updated On: Oct. 15, 2026, 2:35 p.m. UTC


