SPEC 60300
Armorlite® Type MC THHN/THWN Copper Conductor Feeder Cable
Copper THHN/THWN-2 Insulated Singles. Bare Copper Grounding Conductor. UL Listed 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor.

Construction:
- Conductor:Class B compressed copper per ASTM B3 and ASTM B8
- Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
- Ground:Bare stranded copper ground
- Filler:Fillers as needed
- Binder:Mylar tape
- Armor:Aluminum Interlocked Armor
Applications and Features:
Southwire Armorlite® Type MC Feeder Cable is suitable for use as follows:
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.
Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
- Feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
- Fished or embedded in plaster.
- Concealed or exposed installations.
- Environmental air-handling spaces per NEC 300.22 (C).
- Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
- Installation in cable tray and approved raceways.
- Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(E)
- Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
- Binder tape with print legend wrapped around assembly.
- Type THHN/THWN rated 90ºC Dry.
Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
- UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
- Federal Specification A-A59544 (formerly J-C-30B)
- NFPA 70 (National Electrical Code), Article 330
- Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
Specifications:
Sample Print Legend:
E96627 {UL} TYPE MC AWG XX THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
Table 1 – Weights and Measurements
| Stock Number | Cond. Size | Conductor Number | Diameter Over Conductor | Conductor Stranding | Insulation Thickness | Ground Size | Diameter Over Armor | Copper Weight | Overall Weight |
|---|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | inch | mils | No. x AWG | inch | lbs/1000ft | lbs/1000ft | |||
| 890347◊ | 1 | 3 | 0.322 | 19 | 60 | 1x6 GG | 1.275 | 864 | 1147 |
| 890348◊ | 1/0 | 3 | 0.361 | 19 | 60 | 1x6 | 1.241 | 1069 | 1349 |
| 890349◊ | 2/0 | 3 | 0.405 | 19 | 60 | 1x6 | 1.339 | 1326 | 1637 |
| 890394◊ | 3/0 | 3 | 0.456 | 19 | 60 | 1x4 | 1.447 | 1699 | 2039 |
| 890351◊ | 4/0 | 3 | 0.512 | 19 | 60 | 1x4 | 1.639 | 2109 | 2536 |
| 890352◊ | 250 | 3 | 0.558 | 37 | 70 | 1x4 | 1.817 | 2469 | 2975 |
| 555146◊ | 350 | 3 | 0.661 | 37 | 70 | 1x1/0 | 2.039 | 3603 | 4205 |
| 564192◊ | 350 | 3 | 0.661 | 37 | 70 | 1x3/0 | 2.242 | 3797 | 4433 |
| 890353◊ | 350 | 3 | 0.661 | 37 | 70 | 1x3 | 2.039 | 3438 | 4039 |
| 561375◊ | 500 | 3 | 0.789 | 37 | 70 | 1x250 | 2.322 | 5457 | 6178 |
| 890354◊ | 500 | 3 | 0.789 | 37 | 70 | 1x2 | 2.260 | 4884 | 5518 |
| 555147◊ | 750 | 3 | 0.968 | 61 | 80 | 1x4/0 | 2.590 | 7678 | 8472 |
| 890355◊ | 1 | 4 | 0.322 | 19 | 60 | 1x6 GG | 1.351 | 1125 | 1490 |
| 890356◊ | 1/0 | 4 | 0.361 | 19 | 60 | 1x6 | 1.371 | 1399 | 1760 |
| 890357◊ | 2/0 | 4 | 0.405 | 19 | 60 | 1x6 | 1.573 | 1742 | 2218 |
| 561032◊ | 3/0 | 4 | 0.456 | 19 | 60 | 1x3 | 1.694 | 2257 | 2783 |
| 890395◊ | 3/0 | 4 | 0.456 | 19 | 60 | 1x4 | 1.694 | 2223 | 2749 |
| 890359◊ | 4/0 | 4 | 0.512 | 19 | 60 | 1x4 | 1.795 | 2769 | 3322 |
| 552552◊ | 4/0 | 4 | 0.512 | 19 | 60 | 1x3 | 1.795 | 2803 | 3356 |
| 890360◊ | 250 | 4 | 0.558 | 37 | 70 | 1x4 | 1.954 | 3248 | 3885 |
| 581852◊ | 250 | 4 | 0.558 | 37 | 70 | 1x2 GG | 1.954 | 3325 | 3994 |
| 890361◊ | 350 | 4 | 0.661 | 37 | 70 | 1x3 | 2.251 | 4530 | 5323 |
| 568710◊ | 350 | 4 | 0.661 | 37 | 70 | 1x3/0 | 2.387 | 4889 | 5705 |
| 890362◊ | 500 | 4 | 0.789 | 37 | 70 | 1x2 | 2.499 | 6444 | 7289 |
| 564202◊ | 500 | 4 | 0.789 | 37 | 70 | 1x1/0 | 2.495 | 6566 | 7408 |
| 564196◊ | 500 | 4 | 0.789 | 37 | 70 | 1x250 | 2.633 | 7016 | 7806 |
| 552088◊ | 600 | 4 | 0.865 | 61 | 80 | 1x2 | 2.611 | 7691 | 8691 |
| 567671◊ | 600 | 4 | 0.865 | 61 | 80 | 1x3/0 | 2.798 | 8007 | 9041 |
| 550453◊ | 750 | 4 | 0.968 | 61 | 80 | 1x1/0 | 2.864 | 9684 | 10653 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Note: Conductor number = number of phase conductors. Does not include ground
Note: GG = Green insulated ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Note: GG = Green insulated ground
TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
Table 2 – Electrical and Engineering Data
| Cond. Size | Conductor Number | Min. Bend Radius | Max Pull Tension | DC Resistance at 25°C | AC Resistance at 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity Raceway 75°C | Allowable Ampacity Raceway 90°C |
|---|---|---|---|---|---|---|---|---|
| AWG/Kcmil | Inches | Lbs | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | |
| 1 | 3 | 8.9 | 2008 | 0.128 | 0.154 | 0.046 | 130 | 145 |
| 1/0 | 3 | 8.7 | 2534 | 0.102 | 0.122 | 0.044 | 150 | 170 |
| 2/0 | 3 | 9.4 | 3194 | 0.081 | 0.097 | 0.043 | 175 | 195 |
| 3/0 | 3 | 10.1 | 4027 | 0.064 | 0.078 | 0.042 | 200 | 225 |
| 4/0 | 3 | 11.5 | 5078 | 0.051 | 0.062 | 0.041 | 230 | 260 |
| 250 | 3 | 12.7 | 6000 | 0.043 | 0.053 | 0.041 | 255 | 290 |
| 350 | 3 | 14.3 | 8400 | 0.031 | 0.039 | 0.040 | 310 | 350 |
| 350 | 3 | 15.7 | 8400 | 0.031 | 0.039 | 0.040 | 310 | 350 |
| 350 | 3 | 14.3 | 8400 | 0.031 | 0.039 | 0.040 | 310 | 350 |
| 500 | 3 | 16.3 | 12000 | 0.022 | 0.029 | 0.039 | 380 | 430 |
| 500 | 3 | 15.8 | 12000 | 0.022 | 0.029 | 0.039 | 380 | 430 |
| 750 | 3 | 18.1 | 18000 | 0.014 | 0.022 | 0.038 | 475 | 535 |
| 1 | 4 | 9.5 | 2142 | 0.128 | 0.154 | 0.046 | 104 | 116 |
| 1/0 | 4 | 9.6 | 2703 | 0.102 | 0.122 | 0.044 | 120 | 136 |
| 2/0 | 4 | 11.0 | 3407 | 0.081 | 0.097 | 0.043 | 140 | 156 |
| 3/0 | 4 | 11.9 | 4295 | 0.064 | 0.078 | 0.042 | 160 | 180 |
| 3/0 | 4 | 11.9 | 4295 | 0.064 | 0.078 | 0.042 | 160 | 180 |
| 4/0 | 4 | 12.6 | 5416 | 0.051 | 0.062 | 0.041 | 184 | 208 |
| 4/0 | 4 | 12.6 | 5416 | 0.051 | 0.062 | 0.041 | 184 | 208 |
| 250 | 4 | 13.7 | 6400 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 250 | 4 | 13.7 | 6400 | 0.043 | 0.053 | 0.041 | 204 | 232 |
| 350 | 4 | 15.8 | 8960 | 0.031 | 0.039 | 0.040 | 248 | 280 |
| 350 | 4 | 16.7 | 8960 | 0.031 | 0.039 | 0.040 | 248 | 280 |
| 500 | 4 | 17.5 | 12800 | 0.022 | 0.029 | 0.039 | 304 | 344 |
| 500 | 4 | 17.5 | 12800 | 0.022 | 0.029 | 0.039 | 304 | 344 |
| 500 | 4 | 18.4 | 12800 | 0.022 | 0.029 | 0.039 | 304 | 344 |
| 600 | 4 | 18.3 | 15360 | 0.018 | 0.025 | 0.039 | 336 | 380 |
| 600 | 4 | 19.6 | 15360 | 0.018 | 0.025 | 0.039 | 336 | 380 |
| 750 | 4 | 20.0 | 19200 | 0.014 | 0.022 | 0.038 | 380 | 428 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
* Ampacities have been adjusted for more than Three Current-Carrying Conductors.
Revision: 1.000.004
Updated On: Dec. 31, 2024, 11:08 p.m. UTC


