SPEC 48001

CU 600V LSZH XHHW-2 SOLONONplus®

SOLONONplus® 600Volt Single Conductor Copper Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Insulation Type XHHW-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:SOLONONplus® Cross Linked Polyolefin Low Smoke Zero Halogen (XLPO LSZH) Type XHHW-2

Applications and Features:

Southwire’s 600 Volt SOLONONplus® Type XHHW-2 cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, and aerially when supported by a messenger. These cables are ideal for use in establishments where low smoke and low acid emissions are desired for public safety and health and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

a. The conductors are available in tinned and flexible copper stranding upon request.
b. NEC compliant
c. The halogen content is less than 0.2% and Acid gas less than 2.0%
d. Passes UL VW-1 # 8 AWG and larger
e. 70,000 BTU/Hr. Vertical Flame Test
f. UL listed for CT use on 1/0 and Larger
g. UL listed FT4/IEEE 1202 and ST-1 (#8 and larger)
h. -40°C Cold impact and cold bend
i. Oil Resistant I and II
j. UV/Sunlight resistant black color
k. Color Available upon request

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B170 Oxygen Free Electrolytic Copper (available upon request)
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
  • UL 2885 Acid Gas, Acidity and conductivity of combusted materials and assessment of halogens
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • ICEA T-33-655/MIL-C-24643 Low Smoke Halogen Free (LSHF) Polymeric Jackets
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • ISO 9001 Quality management
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (#8 AWG and larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus{TM} E30117 {UL} AWG XX BARE OR TINNED CU LSZH XLPO TYPE XHHW-2 HF -40°C SR PRI PRII FT4 ST-1 600V {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand ClassStrand CountCond. CmilAlloyDiameter Over ConductorInsul. ThicknessJacket ColorApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°C
    AWG/kcmilNo. of Strandscmilinchmilinchlb/1000ftΩ/1000ftΩ/1000ft
    64959314SolidSolid4110Solid0.07030BK0.128182.6313.170
    64736114B741100.07030BK0.133182.6313.170
    59925412SolidSolid65300.08030BK0.144261.6622.002
    59926310SolidSolid103800.10130BK0.165391.0401.253
    64654210B7103800.11330BK0.177401.0401.253
    5993288B7165100.14145BK0.236670.6530.786
    67907006B7262400.17745BK0.2721000.4110.495
    5993376B7262400.17745BK0.2721000.4110.495
    5993464B7417400.22545BK0.3191520.2580.310
    6416913B7526200.25245BK0.3461880.2050.246
    5993552B7663600.28245BK0.3712330.1620.195
    6437521B19836900.32255BK0.4382990.1280.154
    6416931/0B191056000.36155BK0.4783710.1020.122
    5995092/0B191331000.40555BK0.5224610.0810.097
    5995194/0B192116000.51255BK0.6147140.0510.062
    641699250B372500000.55865BK0.6788490.0430.053
    649645300B373000000.61065BK0.74710120.0360.045
    641703600B616000000.86580BK1.03420000.0180.025
    59925612SolidSolid65300.08030BE0.144261.6622.002
    59926510SolidSolid103800.10130BE0.165391.0401.253
    64653110B7103800.11330BE0.177401.0401.253
    5993298B7165100.14145BE0.236670.6530.786
    5993386B7262400.17745BE0.2721000.4110.495
    5993474B7417400.22545BE0.3191520.2580.310
    5993562B7663600.28245BE0.3712330.1620.195
    59925812SolidSolid65300.08030BN0.144261.6622.002
    64652612B765300.08830BN0.151271.6622.002
    59928110SolidSolid103800.10130BN0.165391.0401.253
    5993338B7165100.14145BN0.236670.6530.786
    5993426B7262400.17745BN0.2721000.4110.495
    5993514B7417400.22545BN0.3191520.2580.310
    5993602B7663600.28245BN0.3712330.1620.195
    679131*250B372500000.55865BN0.6788490.0430.053
    59925212SolidSolid65300.08030GN0.144261.6622.002
    64652912B765300.08830GN0.151271.6622.002
    59926110SolidSolid103800.10130GN0.165391.0401.253
    64653310B7103800.11330GN0.177401.0401.253
    5993308B7165100.14145GN0.236670.6530.786
    5993396B7262400.17745GN0.2721000.4110.495
    5993484B7417400.22545GN0.3191520.2580.310
    5993572B7663600.28245GN0.3712330.1620.195
    6416941/0B191056000.36155GN0.4783710.1020.122
    679228*2/0B191331000.40555GN0.5224610.0810.097
    641702500B375000000.78965GN0.91916350.0220.029
    59925712SolidSolid65300.08030GY0.144261.6622.002
    64960112B765300.08830GY0.151271.6622.002
    59928010SolidSolid103800.10130GY0.165391.0401.253
    5993348B7165100.14145GY0.236670.6530.786
    5993436B7262400.17745GY0.2721000.4110.495
    5993524B7417400.22545GY0.3191520.2580.310
    5995052B7663600.28245GY0.3712330.1620.195
    59925912SolidSolid65300.08030OE0.144261.6622.002
    64652712B765300.08830OE0.151271.6622.002
    59928210SolidSolid103800.10130OE0.165391.0401.253
    5993358B7165100.14145OE0.236670.6530.786
    5993446B7262400.17745OE0.2721000.4110.495
    5993534B7417400.22545OE0.3191520.2580.310
    5995072B7663600.28245OE0.3712330.1620.195
    64391714B741100.07030RD0.133182.6313.170
    59925512SolidSolid65300.08030RD0.144261.6622.002
    677425*12B765300.08830RD0.151271.6622.002
    59926410SolidSolid103800.10130RD0.165391.0401.253
    64653010B7103800.11330RD0.177401.0401.253
    5993318B7165100.14145RD0.236670.6530.786
    5993406B7262400.17745RD0.2721000.4110.495
    5993494B7417400.22545RD0.3191520.2580.310
    5993582B7663600.28245RD0.3712330.1620.195
    59925312SolidSolid65300.08030WE0.144261.6622.002
    59926210SolidSolid103800.10130WE0.165391.0401.253
    64653210B7103800.11330WE0.177401.0401.253
    5993416B7262400.17745WE0.2721000.4110.495
    5993504B7417400.22545WE0.3191520.2580.310
    5993592B7663600.28245WE0.3712330.1620.195
    59926012SolidSolid65300.08030YW0.144261.6622.002
    64652812B765300.08830YW0.151271.6622.002
    59928310SolidSolid103800.10130YW0.165391.0401.253
    5993368B7165100.14145YW0.236670.6530.786
    5993456B7262400.17745YW0.2721000.4110.495
    5993544B7417400.22545YW0.3191520.2580.310
    5995082B7663600.28245YW0.3712330.1620.195
    64751612SolidSolid65300.08030PE0.144261.6622.002
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ # 6AWG Stock Number 679070 is Tinned Copper Conductor

    Table 3 - Stock Code Colors (Black in Table 1)

    SizeRedBlueWhiteBrownOrangeYellowGrayGreenPurple
    RedBlueWhiteBrownOrangeYellowGrayGreenPurple
    12 (Solid)599255599256599253599258599259599260599257599252647516
    10 (Solid)599264599265599262599281599282599283599280599261
    14 (19)643917
    12 (19)677425*646526646527646528646529
    10 (19)646530646531646532646533
    8 (19)599331599329599333599335599336599334599330
    6 (19)599340599338599341599342599344599345599343599339
    4 (19)599349599347599350599351599353599354599352599348
    2 (19)599358599356599359599360599507599508599505599357
    1/0 (19)641694
    2/0 (19)679228*
    250 (37)679131*
    500 (37)641702
    *Tinned Copper per ASTM B33