SPEC 45409

1/C AL 2000V XLPE RHH/RHW-2 Power Cable SSRTM Type PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:AlumaFlex® Single Input Wire (SIW) Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation:Southwire’s Super Sunlight Resistant (SSRTM) Cross-linked Polyethylene (XLPE)

Applications and Features:

Southwire’s new Super Sunlight Resistant – SSR Type PV cables are leading the industry with features such as enhanced UV stability, color permanence and aged physical properties, providing you with the most reliable solutions for your PV wiring systems. The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, RoHS compliant, passes -40°C cold bend.

Specifications:

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 4703 Standard for Photovoltaic Wire
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • AA 8176 Stranded Aluminum Alloy Conductors
  • Sample Print Legend:

    SOUTHWIRE SSR™ E316464 (UL) PV WIRE XX AWG (XX.X mm2) COMPACT AL.— ALUMAFLEX® AA8176 2000V 90°C WET OR DRY (-40°C) SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V — RoHS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    6435766170.169850.3392454
    6435804170.212850.3833974
    6435831180.2981050.50978137
    6435871/01100.3361050.54699163
    6435902/01120.3761050.586125195
    6435943/01160.4221050.633158235
    6435974/01190.4741050.685199284
    6418212501220.5201200.760235342
    6418183001210.5691200.810282397
    6418153501350.6151200.856329452
    6418124001350.6591200.899376506
    6414925001340.7351200.978471614
    6414956001370.8121351.083565743
    6414997501610.9081351.178706902
    64193010001581.0601351.3309421166
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    643576612.71570.6740.8120.0515055
    643580413.12500.4240.5100.0486575
    643583114.15020.2110.2540.046100115
    6435871/014.46330.1680.2010.044120135
    6435902/014.77980.1330.1600.043135150
    6435943/015.110060.1050.1260.042155175
    6435974/015.512690.0840.1000.041180205
    64182125016.115000.0710.0860.041205230
    64181830016.518000.0590.0710.041230260
    64181535016.821000.0500.0620.040250280
    64181240017.224000.0440.0540.040270305
    64149250017.830000.0350.0440.039310350
    64149560018.736000.0290.0370.039340385
    64149975019.445000.0240.0310.038385435
    6419301000110.660000.0180.0250.037445500
    † Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    † Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Stock Code Colors

    SizeBlackRedWhite
    AWG/KcmilBlackRedWhite
    6 (7)643576643578643579
    4 (7)643580643581643582
    1 (8)643583643584643586
    1/0 (10)643587643588643589
    2/0 (12)643590643591643592
    3/0 (16)643594643595643596
    4/0 (19)643597643598643599
    250 (22)641821641822641823
    300 (21)641818641819641820
    350 (35)641815641816641817
    400 (35)641812641813641814
    500 (34)641492641494641493
    600 (37)641495641497641496
    750 (37)641499641501641500
    1000 (58)641930641931641932

    Revision: 1.000.003

    Updated On: July 3, 2024, 10:13 p.m. UTC