Search Results:

SPEC 85004

Multi-Conductor CU 600 V FR-XLPE PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • CSA CSA marking is available upon request
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE (XHHW-2) CDRS 90°C PVC JKT 600V TYPE TC-ER SUN. RES. DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    CSA Listed
    SOUTHWIRE #P 156205 CSA XX AWG X/C FR-XLPE CDRS 90C PVC JACKET, -40C, FT-4, SUN RES, DIR BUR, 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CInductive RectanceMin Bending RadiusAllowable Ampacity 75°CAllowable Ampacity 90°CJacket Color
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmp
    18 AWG
    62417718270.04525450.29110406.6698.0350.0361.1-14Black
    62030918470.04525450.33520616.6698.0350.0361.3-11Black
    62417618770.04525450.32935916.6698.0350.0361.3-10Black
    604208181270.04525450.533601536.6698.0350.0362.1-7Black
    14 AWG
    618791^14370.07030450.38638952.6313.1700.0581.52025Black
    TBA14570.07030450.449631222.6313.1700.0581.71620Black
    TBA14670.07030450.480761432.6313.1700.0581.91620Black
    61948114770.07030450.503891762.6313.1700.0582.01417Black
    619483^14970.07030600.5951152312.6313.1700.0582.31417Black
    664329^141270.07045600.7941533622.6313.1700.0583.21013Black
    12 AWG
    62030612270.08830450.392611121.6622.0020.0541.52530Black
    619487^12470.08830450.39640881.6622.0020.0541.52024Black
    619488^12370.08830450.416611181.6622.0020.0541.62530Black
    619489^12470.08830450.453811511.6622.0020.0541.82024Black
    61949212770.08830600.5711422531.6622.0020.0542.21721Black
    604283^121270.08830600.7422444091.6622.0020.0542.91215Black
    620307121270.08830600.7422444101.6622.0020.0542.91215Black
    10 AWG
    60401810270.11330450.440641221.0401.2530.0501.73540Black
    60428210270.11330450.440641341.0401.2530.0501.73540Black
    672864^10370.11330450.4671292031.0401.2530.0501.83540Black
    62076410370.11330450.471971701.0401.2530.0501.83540Black
    619088^10470.11330450.5101292081.0401.2530.0502.02832Black
    604410^@104190.11330600.5571292361.0401.2530.0502.22832Black
    604284^10470.11330600.5571292371.0401.2530.0502.22832Black
    619090^10570.11330600.5941612781.0401.2530.0502.32832Black
    66185910770.11330600.6402263541.0401.2530.0502.52428Black
    628428^10770.11330600.6432263561.0401.2530.0502.52428Black
    619498^10870.11330600.6962584041.0401.2530.0502.72428Black
    67308410970.11330600.7582914551.0401.2530.0503.02428Black
    606676^101270.11330800.8873886211.0401.2530.0503.51720Black
    8 AWG
    619504!8270.14145600.5981022090.6530.7860.0522.35055Black
    619507^8370.14145600.6351542890.6530.7860.0522.55055Black
    619508^8470.14145600.6942053550.6530.7860.0522.74044Black
    6 AWG
    619511!6270.17745600.6741632890.4110.4950.0512.76575Black
    619512^6370.17745600.7122453990.4110.4950.0512.86575Black
    619514^6470.17745600.7873275270.4110.4950.0513.15260Black
    4 AWG
    619517^4370.22545600.8053905770.2580.3100.0483.28595Black
    619518^4470.22545800.9325207650.2580.3100.0483.76876Black
    2 AWG
    6195242370.28245800.9816208900.1620.1950.0453.9115130Black
    6616762470.28245801.07682711420.1620.1950.0455.392104Black
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    ! UL listed TC rated (not TC-ER)
    @ Combination unilay stranded per ASTM B787
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. * Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.

    Revision: 1.000.009

    Updated On: Sept. 19, 2025, 4:13 p.m. UTC