SPEC 44122

4/C CU 2000V EPDM/CPE Type G Industrial Grade Cable 90°C. MSHA Approved

Flexible Copper conductors, Ethylene Propylene Diene Monomer (EPDM) insulation, Single Layer Chlorinated Polyethylene (CPE) Jacket

...

Construction:

  1. Conductor:Bare, soft drawn, annealed, flexible, rope-lay stranded copper per ASTM B3/B172
  2. Separator Tape:Non-conducting tape applied between the conductor and insulation to facilitate stripping
  3. Insulation:Ethylene Propylene Diene Monomer (EPDM). Color coded black, white, blue, red for sizes #4/0 and smaller and black, white, red, orange for sizes over 250 kcmil
  4. Ground Conductors:Four insulated, bare, soft drawn, annealed, rope stranded, flexible lay copper per ASTM B3/B172
  5. Fillers:Jute fillers applied as needed to round the cable core
  6. Reinforcement Binder:Reinforcing binder with twine applied over the core
  7. Jacket:Black, flame resistant, thermosetting Chlorinated Polyethylene (CPE)

Applications and Features:

Southwire Type G cable is a heavy-duty industrial cable for use in flexible, portable, and extra-hard usage applications where equipment grounding is required per NEC Article 400. Suitable for continuous submersion in water – ideal for submersible pumps, marine application. Also suitable for use in light to medium-duty mining applications. Sunlight and oil resistant. Highly flexible and easy to work with in cold conditions. Not for use as permanent building wiring. Meets FT-5 Flame Test. cUL Listed.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • UL 1650 Standard for Portable Power Cable
  • MSHA Approved
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    2 AWG 4/C TYPE G PORTABLE POWER CABLE 90°C WET OR DRY 2000V OIL AND SUN RES (UL) P-136-35-MSHA AIWTM c(UL) FT1/FT5 (-40°C)
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over ConductorInsul. ThicknessGroundJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.No.inchmilNo. x AWGmilinchlb/1000ft
    56207884710.145604 x 121450.985629
    57147364650.186604 x 121451.130865
    571365441120.235604 x 101751.2221121
    562081241680.290604 x 92051.4791882
    562083142240.300804 x 81451.5912063
    5620841/042590.379804 x 71551.7552452
    5620852/043240.400804 x 61551.9303057
    5600663/044180.480804 x 51552.0483679
    5620864/045320.530804 x 41552.1754392
    57140725046080.605954 x 32702.5275609
    57026035048930.670954 x 22702.9728110
    570261500412210.858954 x 1/03253.23010201
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CInductive ReactanceMin Bending RadiusAllowable Ampacity In Air 60°CAllowable Ampacity In Air 75°CAllowable Ampacity In Air 90°C
    AWG/KcmilΩ/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    80.6790.8180.0523.9384652
    60.4350.5240.0515.6506270
    40.2740.3300.0486.1678191
    20.1720.2070.0457.390106122
    10.1370.1640.0467.9105125142
    1/00.1090.1310.0448.7121145164
    2/00.0870.1040.0439.6139166190
    3/00.0690.0830.04212.2161193219
    4/00.0550.0670.04113.0186222253
    2500.0470.0570.04115.1207248282
    3500.0330.0420.04017.8254305346
    5000.0230.0310.03919.3314376429
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.002

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC