SPEC 60215

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor Isolated Ground 120/208V Colors

Copper THHN/THWN Insulated Singles. Two Insulated Grounding Conductors. UL Listed 600 Volts Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Two insulated Green and Green/Yellow grounds. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable -Isolated Ground is suitable for use as follow:
  • Applications requiring redundant, dedicated or isolated grounding paths.
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multi- residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2)
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.

  • Southwire Armorlite® Type MC Cable - Isolated Ground meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • Sample Print Legend:

    E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    695965122BK/WE0.080Solid202x120.51479132
    556323122RD/WE0.080Solid202x120.51479132
    556325122BE/WE0.080Solid202x120.51479132
    695973123BK/RD/WE0.080Solid202x120.54999159
    560950123BK/BE/WE0.080Solid202x120.54999159
    695981124BK/RD/BE/WE0.080Solid202x120.586119187
    562419124BK/RD/BE/WE0.080Solid202x120.586119187
    587697126See Table0.080Solid202x120.624159238
    695999102BK/WE0.101Solid252x100.589123192
    555636102BE/WE0.101Solid252x100.589123192
    696005103BK/RD/WE0.101Solid252x100.633154233
    696013104BK/RD/BE/WE0.101Solid252x100.679185274
    551104122BK/WE0.09019202x120.53880138
    551106123BK/RD/WE0.09019202x120.565100159
    551296124BK/RD/BE/WE0.09019202x120.613120197
    551298102BK/WE0.11719252x100.626129206
    551302103BK/RD/WE0.11719252x100.674161250
    55518482BK/WE0.14319352x100.682167260
    55518984BK/RD/BE/WE0.14319352x100.869270433
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1223.61.6622.0020.054202530
    1223.61.6622.0020.054202530
    1223.61.6622.0020.054202530
    1233.81.6622.0020.054202530
    1233.81.6622.0020.054202530
    1244.11.6622.0020.054162024
    1244.11.6622.0020.054162024
    1264.41.6622.0020.054162024
    1024.11.0401.2530.050303540
    1024.11.0401.2530.050303540
    1034.41.0401.2530.050303540
    1044.81.0401.2530.050242832
    1223.81.6622.0020.054202530
    1234.01.6622.0020.054202530
    1244.31.6622.0020.054162024
    1024.41.0401.2530.050303540
    1034.71.0401.2530.050303540
    824.80.6530.7860.052405055
    846.10.6530.7860.052324044
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.003

    Updated On: Feb. 2, 2024, 1:31 p.m. UTC