SPEC 60100

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor 120/208V Colors

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape with print legend wrapped around assembly.
  5. Armor:Aluminum Interlocked Armor

Contact Southwire SPEED™ Services to request a quote.

Applications and Features:

Southwire Armorlite® Type MC Cable is suitable for use as follows:
  • Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC Article 645
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.
  • Anti-Short bushing not required

  • Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    685792142BK/WE0.064Solid201x140.4513779
    685826143BK/RD/WE0.064Solid201x140.4785097
    687186144BK/RD/BE/WE0.064Solid201x140.50862116
    689489122BE/WE0.080Solid201x120.48359105
    689521122RD/WE0.080Solid201x120.48359105
    685800122BK/WE0.080Solid201x120.48359107
    610971123RD/BE/WE0.080Solid201x120.51479132
    610973123BK/BE/WE0.080Solid201x120.51479132
    685834123BK/RD/WE0.080Solid201x120.51479132
    687194124BK/RD/BE/WE0.080Solid201x120.54999159
    550172124BK/RD/BE/WE0.080Solid201x120.54999159
    610520102PE/GY0.101Solid251x100.55092151
    685818102BK/WE0.101Solid251x100.55092151
    610521102RD/WE0.101Solid251x100.55092151
    610518102BE/WE0.101Solid251x100.55092151
    685842103BK/RD/WE0.101Solid251x100.589123192
    687202104BK/RD/BE/WE0.101Solid251x100.633154232
    550177142BK/WE0.07319201x140.4683883
    550180143BK/RD/WE0.07319201x140.49751102
    691147122BK/WE0.09019201x120.50460110
    691154123BK/RD/WE0.09019201x120.53880138
    691162124BK/RD/BE/WE0.09019201x120.576100167
    691170102BK/WE0.11719251x100.58397163
    691188103BK/RD/BE0.11719251x100.626129206
    691196104BK/RD/BE/WE0.11719251x100.674161251
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1423.22.6313.1700.058152025
    1433.32.6313.1700.058152025
    1443.62.6313.1700.058121620
    1223.41.6622.0020.054202530
    1223.41.6622.0020.054202530
    1223.41.6622.0020.054202530
    1233.61.6622.0020.054202530
    1233.61.6622.0020.054202530
    1233.61.6622.0020.054202530
    1243.81.6622.0020.054162024
    1243.81.6622.0020.054162024
    1023.91.0401.2530.050303540
    1023.91.0401.2530.050303540
    1023.91.0401.2530.050303540
    1023.91.0401.2530.050303540
    1034.11.0401.2530.050303540
    1044.41.0401.2530.050242832
    1423.32.6313.1700.058152025
    1433.52.6313.1700.058152025
    1223.51.6622.0020.054202530
    1233.81.6622.0020.054202530
    1244.01.6622.0020.054162024
    1024.11.0401.2530.050303540
    1034.41.0401.2530.050303540
    1044.71.0401.2530.050242832
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    * Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.003

    Updated On: March 21, 2024, 3:20 p.m. UTC