SPEC 60001

SIMpull MC™ THHN/THWN Circuit Size Copper Conductor 120/208V Colors

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts Rated VW-1. Lightweight Low Profile Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape with print legend wrapped around assembly.
  5. Armor:Low Profile Aluminum Interlocked Armor

Applications and Features:

  • Southwire SIMpull MC Cable is suitable for use as follows:
  • Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC Article 645
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.
  • Anti-Short bushing not required

  • Southwire SIMpull MC Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • RoHS-2 (European Directive 2011/65/EU)
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround SizeDiameter Over ArmorCopper WeightOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ftlbs/1000ft
    137914142BK/WE0.064Solid201x140.4153776
    TBA143BK/WE/BE0.064Solid201x140.4645098
    665383143BK/WE/RD0.064Solid201x140.4425093
    TBA144BK/RD/BE/WE0.064Solid201x140.49362116
    665378122BE/WE0.080Solid201x120.45159104
    137912122BK/WE0.080Solid201x120.45159103
    665377122RD/WE0.080Solid201x120.45159103
    137918122BN/GY0.080Solid201x120.45159103
    665381122OE/GY0.080Solid201x120.45159103
    665382122YW/GY0.080Solid201x120.45159103
    665387123BN/OE/GY0.080Solid201x120.48279128
    665436123BK/RD/BE0.080Solid201x120.48279128
    137913123BK/RD/WE0.080Solid201x120.48279128
    665384124BK/RD/BE/WE0.080Solid201x120.51799155
    TBA124BK/RD/BE/WE0.080Solid201x120.53699162
    665379102RD/WE0.101Solid251x100.51892147
    TBA102BE/WE0.101Solid251x100.53892154
    665380102BN/GY0.101Solid251x100.51892147
    137917102BK/WE0.101Solid251x100.51892147
    137916103BK/RD/WE0.101Solid251x100.557123187
    TBA104BK/RD/BE/WE0.101Solid251x100.620154235
    TBA142BK/WE0.07319201x140.4563883
    TBA143BK/WE/RD0.07319201x140.48551103
    137915122BK/WE0.09019201x120.47260107
    665385123BK/RD/WE0.09019201x120.50680134
    TBA124BK/RD/BE/WE0.09019201x120.563100169
    665386102BK/WE0.11719251x100.55197159
    TBA103BK/RD/BE0.11719251x100.616129209
    TBA104BK/RD/BE/WE0.11719251x100.663161254
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Cond. SizeConductor NumberMin. Bend RadiusDC Resistance at 25°CAC Resistance at 75°CInductive Reactance @ 60HzAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    1422.92.6313.1700.058152025
    1433.92.6313.1700.058152025
    1433.12.6313.1700.058152025
    1444.22.6313.1700.058121620
    1224.01.6622.0020.054202530
    1223.21.6622.0020.054202530
    1223.21.6622.0020.054202530
    1223.21.6622.0020.054202530
    1223.21.6622.0020.054202530
    1223.21.6622.0020.054202530
    1233.41.6622.0020.054202530
    1233.41.6622.0020.054202530
    1233.41.6622.0020.054202530
    1243.61.6622.0020.054162024
    1244.51.6622.0020.054162024
    1023.61.0401.2530.050303540
    1024.51.0401.2530.050303540
    1023.61.0401.2530.050303540
    1023.61.0401.2530.050303540
    1033.91.0401.2530.050303540
    1045.01.0401.2530.050242832
    1423.92.6313.1700.058152025
    1434.12.6313.1700.058152025
    1223.31.6622.0020.054202530
    1233.51.6622.0020.054202530
    1244.61.6622.0020.054162024
    1023.91.0401.2530.050303540
    1035.01.0401.2530.050303540
    1045.31.0401.2530.050242832
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.

    Revision: 1.000.013

    Updated On: March 21, 2024, 12:42 p.m. UTC