SPEC 26115

HVTECK CU 1/C 90TRXLPE CB PVC AIA PVC 5kV 100% CSA

Single Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 90 TRXLPE AIA 5kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ftlb/1000ft
    270.2820.500900.5607x14651.040501.140299735
    1190.3220.540900.60011x14801.110501.210407901
    1/0190.3610.579900.63911x14801.149501.249474992
    2/0190.4050.623900.68311x14801.193501.2935591107
    3/0190.4560.674900.73413x14801.354501.4546941285
    4/0190.5120.730900.79013x14801.410501.5108291455
    250370.5580.784900.84417x14801.464501.56410011666
    350370.6610.887900.94721x14801.601601.72113652145
    500370.7891.015901.07526x14801.753601.87318962796
    750610.9681.204901.26421x12801.942602.06227533890
    1000611.1171.353901.41321x121102.151602.27135254898
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    213.75300.1620.2040.0340.0540.548 + j0.5350.205 + j0.0555458215221
    114.56690.1280.1620.0310.0520.511 + j0.5110.163 + j0.0528577245247
    1/015.08440.1020.1280.0280.0500.481 + j0.4910.129 + j0.0508577278275
    2/015.510640.0810.1020.0260.0480.459 + j0.4680.103 + j0.0498577317306
    3/017.413420.0640.0810.0230.0480.438 + j0.4430.082 + j0.04910137357335
    4/018.116920.0510.0650.0210.0470.424 + j0.4180.066 + j0.04710137404369
    25018.820000.0430.0560.0200.0450.415 + j0.3950.057 + j0.04513256456412
    35020.728000.0310.0410.0170.0440.396 + j0.3560.042 + j0.04416376537456
    50022.540000.0220.0300.0150.0420.378 + j0.3140.031 + j0.04220275616497
    75024.760000.0140.0230.0120.0390.356 + j0.2620.024 + j0.03926018706551
    100027.380000.0110.0190.0110.0380.339 + j0.2290.020 + j0.03826018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/kmkg/km
    277.1612.702.2914.227x141.6526.421.2728.964451094
    1198.1813.722.2915.2411x142.0328.191.2730.736061341
    1/0199.1714.712.2916.2311x142.0329.181.2731.727051476
    2/01910.2915.822.2917.3511x142.0330.301.2732.848321647
    3/01911.5817.122.2918.6413x142.0334.391.2736.9310331912
    4/01913.0018.542.2920.0713x142.0335.811.2738.3512342165
    2503714.1719.912.2921.4417x142.0337.191.2739.7314902479
    3503716.7922.532.2924.0521x142.0340.671.5243.7120313192
    5003720.0425.782.2927.3026x142.0344.531.5247.5728224161
    7506124.5930.582.2932.1121x122.0349.331.5252.3740975789
    10006128.3734.372.2935.8921x122.7954.641.5257.6852467289
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence ImpedancePositive Sequence ImpedancePhase Short Circuit Current @ 6 CyclesAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    2347.9823590.53150.670.01040.17720.548 + j0.5350.205 + j0.0555458215221
    1368.3029770.41990.530.00940.17060.511 + j0.5110.163 + j0.0528577245247
    1/0381.0037560.33460.420.00850.16400.481 + j0.4910.129 + j0.0508577278275
    2/0393.7047350.26570.330.00790.15750.459 + j0.4680.103 + j0.0498577317306
    3/0441.9659720.21000.270.00700.15750.438 + j0.4430.082 + j0.04910137357335
    4/0459.7475290.16730.210.00640.15420.424 + j0.4180.066 + j0.04710137404369
    250477.5289000.14110.180.00610.14760.415 + j0.3950.057 + j0.04513256456412
    350525.78124600.10170.130.00520.14440.396 + j0.3560.042 + j0.04416376537456
    500571.50178000.07220.100.00460.13780.378 + j0.3140.031 + j0.04220275616497
    750627.38267000.04590.080.00370.12800.356 + j0.2620.024 + j0.03926018706551
    1000693.42356000.03610.060.00340.12470.339 + j0.2290.020 + j0.03826018813596
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC