SPEC 45301

CU 600/1000V XLPE Insulation AIA PVC Jacket XHHW-2. CT Rated -Sunlight Resistant - For Direct Burial - Silicone Free

Type MC Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket with 1 Bare CU Ground. Silicone Free.

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
  3. Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  4. Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
  5. Binder:Polypropylene tape
  6. Armor:Aluminum Interlocked Armor (AIA)
  7. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type MC power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 3 (1-BLACK, 2-RED, 3-BLUE)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • Sample Print Legend:

    {SQFTG_DUAL} SOUTHWIRE {UL} 3/C (1 AWG) XX.Xmm2 CU XX MILS XLP 600 VOLTS GW 1 X X AWG CU TYPE MC FOR CT USE SUN. RES. DIRECT BURIAL 90°C USA -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeCond. NumberStrand CountDiameter Over ConductorInsul. ThicknessGroundDiameter Over ArmorJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of StrandsinchmilNo. x AWGinchmilinchlb/1000ftlb/1000ft
    6069398370.141451 x 100.721500.821186404
    6069476370.177451 x 80.788500.888297545
    6069544370.225451 x 80.898500.998441713
    6718923370.252451 x 60.945501.045574891
    5604662370.282451 x 61.019501.1197021046
    55080113190.322551 x 61.151501.2518641264
    5604741/03190.361551 x 61.233501.33310691499
    5604822/03190.405551 x 61.328501.42813261816
    8903393/03190.456551 x 41.436501.53616992256
    3836794/03190.512551 x 41.631601.75121092786
    6013772503370.558651 x 41.769601.88924693379
    3836463503370.661651 x 31.983602.10334384551
    3806185003370.789651 x 22.253752.40348846180
    5822745003370.789651 x 4/02.341752.49153376691
    8903916003610.865801 x 4/02.507752.65762727604
    8904057503610.968801 x 12.758752.90872779227
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeCond. NumberMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftAmpAmp
    606939835.73960.6530.7860.0330.0525055
    606947636.26290.4110.4950.0270.0516575
    606954437.010010.2580.3100.0220.0488595
    671892337.312620.2050.2460.0200.047100115
    560466237.815920.1620.1950.0180.045115130
    550801138.820080.1280.1540.0190.046130145
    5604741/039.325340.1020.1220.0170.044150170
    5604822/0310.031940.0810.0970.0160.043175195
    8903393/0310.840270.0640.0780.0140.042200225
    3836794/0312.350780.0510.0620.0130.041230260
    601377250313.260000.0430.0530.0140.041255290
    383646350314.784000.0310.0390.0120.040310350
    380618500316.8120000.0220.0290.0100.039380430
    582274500317.4120000.0220.0290.0100.039380430
    890391600318.6144000.0180.0250.0110.039420475
    890405750320.4180000.0140.0220.0100.038475535
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 1.000.005

    Updated On: Jan. 24, 2024, 6:14 p.m. UTC