SPEC 45351
CU 600/1000V XLPE Insulation ARMOR-X® PVC Jacket. XHHW-2 VFD Cable
Type MC-HL Power Cable 600Volt Three Conductor Copper, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Continuous Corrugated Welded Armor - ARMOR-X®, Polyvinyl Chloride (PVC) Jacket with 3 Bare CU Ground

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compressed stranded bare copper per ASTM B3 and B8
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polypropylene tape
- Armor:ARMOR-X® Continuous Corrugated Welded Armor
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 Volt Type MC-HL ARMOR-X® power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.
Specifications:
Sample Print Legend:
{SQFTG_DUAL} SOUTHWIRE MASTER-DESIGN ARMOR-X® {UL} TYPE MC-HL 3/C XXX KCMIL (XXX{mm2}) CU XHHW-2 GW 3 X X AWG 90{D}C JACKET -40{D}C SUN. RES. DIR. BUR. FOR CT USE 600V IEEE1202/FT4 -- {CSA} RA90-HL AG14 XLPE -40{D}C 600V FT4 SR 90{D}C -- {NOM}-ANCE Tipo MC XHHW-2 CT FT4 -- VFD USA
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Diameter Over Insulation | Ground | Diameter Over Armor | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | No. x AWG | inch | mil | inch | lb/1000ft | lb/1000ft | ||
550593◊ | 8 | 3 | 7 | 0.141 | 45 | 0.233 | 3 x 14 | 0.750 | 60 | 0.870 | 192 | 422 |
890513◊ | 6 | 3 | 7 | 0.177 | 45 | 0.268 | 3 x 12 | 0.840 | 60 | 0.960 | 306 | 564 |
890514◊ | 4 | 3 | 7 | 0.225 | 45 | 0.315 | 3 x 12 | 0.920 | 60 | 1.040 | 449 | 733 |
890515◊ | 2 | 3 | 7 | 0.282 | 45 | 0.371 | 3 x 10 | 1.020 | 60 | 1.140 | 717 | 1081 |
890516◊ | 1/0 | 3 | 19 | 0.361 | 55 | 0.476 | 3 x 10 | 1.350 | 60 | 1.470 | 1085 | 1765 |
890517◊ | 2/0 | 3 | 19 | 0.405 | 55 | 0.522 | 3 x 10 | 1.470 | 60 | 1.596 | 1342 | 1967 |
890518 | 3/0 | 3 | 19 | 0.456 | 55 | 0.570 | 3 x 8 | 1.540 | 60 | 1.666 | 1724 | 2426 |
890519◊ | 4/0 | 3 | 19 | 0.512 | 55 | 0.608 | 3 x 8 | 1.590 | 60 | 1.710 | 2134 | 2832 |
890520◊ | 250 | 3 | 37 | 0.558 | 65 | 0.672 | 3 x 8 | 1.845 | 60 | 1.965 | 2493 | 3346 |
890521◊ | 350 | 3 | 37 | 0.661 | 65 | 0.771 | 3 x 6 | 2.040 | 60 | 2.160 | 3520 | 4529 |
890522◊ | 500 | 3 | 37 | 0.789 | 65 | 0.902 | 3 x 6 | 2.290 | 75 | 2.448 | 4923 | 6002 |
641426 | 500 | 3 | 37 | 0.789 | 65 | 0.896 | 1 x 4/0 | 2.430 | 75 | 2.588 | 5337 | 6461 |
646751 | 600 | 3 | 61 | 0.865 | 80 | 1.026 | 3 x 6 | 2.670 | 75 | 2.820 | 5858 | 7215 |
890523◊ | 750 | 3 | 61 | 0.968 | 80 | 1.128 | 3 x 4 | 3.000 | 75 | 3.150 | 7406 | 9633 |
TBA | 1000 | 3 | 61 | 1.117 | 80 | 1.277 | 3 x 4 | 3.220 | 85 | 3.390 | 9737 | 12086 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | ||
550593◊ | 8 | 3 | 6.0 | 396 | 0.653 | 0.786 | 0.052 | 40 | 50 | 55 |
890513◊ | 6 | 3 | 6.7 | 629 | 0.411 | 0.495 | 0.051 | 55 | 65 | 75 |
890514◊ | 4 | 3 | 7.2 | 1001 | 0.258 | 0.310 | 0.048 | 70 | 85 | 95 |
890515◊ | 2 | 3 | 7.9 | 1592 | 0.162 | 0.195 | 0.045 | 95 | 115 | 130 |
890516◊ | 1/0 | 3 | 10.2 | 2534 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
890517◊ | 2/0 | 3 | 11.1 | 3194 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
890518 | 3/0 | 3 | 11.6 | 4027 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
890519◊ | 4/0 | 3 | 11.9 | 5078 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
890520◊ | 250 | 3 | 13.7 | 6000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
890521◊ | 350 | 3 | 15.1 | 8400 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
890522◊ | 500 | 3 | 17.1 | 10000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
641426 | 500 | 3 | 18.1 | 10000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
646751 | 600 | 3 | 19.7 | 10000 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
890523◊ | 750 | 3 | 22.0 | 10000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
TBA | 1000 | 3 | 23.7 | 10000 | 0.011 | 0.018 | 0.037 | 455 | 545 | 615 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Revision: 1.000.007
Updated On: Sept. 11, 2023, 8:18 p.m. UTC