SPEC 45264
AL 600/1000V XLPE Insulation PVC Jacket. XHHW-2
Type TC-ER Power Cable 600 or 1000 Volt Three Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket with 1 Bare AL Ground. Silicone Free

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type XHHW-2
- Grounding Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Filler:Paper filler (cable size 8 & 6 uses Polypropylene filler)
- Binder:Polyester flat thread binder tape for cable sizes larger than 2 AWG
- Overall Jacket:Sunlight resistant Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone free.
Specifications:
Sample Print Legend:
SOUTHWIRE{R} MASTER-DESIGN {UL} XXX AWG AL 3/C TYPE TC-ER XHHW-2 CDRS GW 1 X X AWG AL 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V or 1000V {YYYY} PC09-FLRBLGN {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Strand Count | Diameter Over Conductor | Insul. Thickness | Ground | Jacket Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | No. x AWG | mil | inch | lb/1000ft | lb/1000ft | ||
582238 | 8 | 3 | 7 | 0.134 | 45 | 1 x 8 | 60 | 0.666 | 62 | 189 |
TBA | 6 | 3 | 7 | 0.169 | 45 | 1 x 8 | 60 | 0.691 | 89 | 231 |
671633 | 4 | 3 | 7 | 0.212 | 45 | 1 x 6 GG | 80 | 0.886 | 142 | 394 |
TBA | 2 | 3 | 7 | 0.268 | 45 | 1 x 6 | 80 | 0.945 | 213 | 456 |
670971 | 2 | 3 | 6 | 0.268 | 45 | 1 x 6 GG | 80 | 0.983 | 214 | 523 |
675018 | 1 | 3 | 8 | 0.298 | 55 | 1 x 4 | 80 | 1.109 | 278 | 610 |
TBA | 1/0 | 3 | 19 | 0.336 | 55 | 1 x 4 | 80 | 1.135 | 338 | 668 |
670963 | 1/0 | 3 | 10 | 0.336 | 55 | 1 x 4 GG | 80 | 1.173 | 341 | 755 |
646672 | 2/0 | 3 | 12 | 0.376 | 55 | 1 x 4 | 80 | 1.209 | 419 | 782 |
599619 | 3/0 | 3 | 15 | 0.422 | 55 | 1 x 4 | 80 | 1.324 | 518 | 918 |
672057 | 4/0 | 3 | 19 | 0.474 | 55 | 1 x 2 | 80 | 1.423 | 667 | 1099 |
646667 | 250 | 3 | 22 | 0.520 | 65 | 1 x 1 | 80 | 1.564 | 793 | 1323 |
672257 | 300 | 3 | 35 | 0.569 | 65 | 1 x 2 | 110 | 1.732 | 919 | 1580 |
137880 | 350 | 3 | 35 | 0.615 | 65 | 1 x 1 | 110 | 1.844 | 1078 | 1788 |
582220 | 400 | 3 | 35 | 0.659 | 65 | 1 x 3/0 | 110 | 1.960 | 1301 | 2060 |
563211 | 500 | 3 | 35 | 0.735 | 65 | 1 x 1 | 110 | 2.090 | 1506 | 2298 |
582223 | 500 | 3 | 35 | 0.735 | 65 | 1 x 2/0 | 110 | 2.103 | 1553 | 2438 |
672259 | 500 | 3 | 35 | 0.735 | 65 | 1 x 4/0 | 110 | 2.200 | 1628 | 2540 |
671494 | 500 | 3 | 35 | 0.735 | 65 | 1 x 250 | 110 | 2.213 | 1665 | 2635 |
582129 | 600 | 3 | 58 | 0.812 | 80 | 1 x 1/0 | 110 | 2.304 | 1813 | 2881 |
679401 | 600 | 3 | 58 | 0.812 | 80 | 1 x 350 | 110 | 2.549 | 2045 | 3166 |
587573 | 750 | 3 | 58 | 0.908 | 80 | 1 x 1/0 | 110 | 2.526 | 2241 | 3430 |
580013 | 750 | 3 | 58 | 0.908 | 80 | 1 x 3/0 | 110 | 2.526 | 2300 | 3392 |
579924 | 750 | 3 | 58 | 0.908 | 80 | 3 x 2/0 | 110 | 2.526 | 2520 | 3963 |
671392 | 750 | 3 | 58 | 0.908 | 80 | 1 x 400 | 110 | 2.585 | 2521 | 3756 |
TBA | 1000 | 3 | 61 | 1.060 | 80 | 1 x 1/0 | 140 | 2.927 | 2945 | 4555 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Cond. Number | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 75°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C | Allowable Ampacity At 75°C | Allowable Ampacity At 90°C |
---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | ||
582238 | 8 | 3 | 2.6 | 297 | 1.072 | 1.290 | 0.052 | 35 | 40 | 45 |
TBA | 6 | 3 | 2.7 | 472 | 0.674 | 0.812 | 0.051 | 40 | 50 | 55 |
671633 | 4 | 3 | 3.5 | 751 | 0.424 | 0.510 | 0.048 | 55 | 65 | 75 |
TBA | 2 | 3 | 3.7 | 1194 | 0.267 | 0.321 | 0.045 | 75 | 90 | 100 |
670971 | 2 | 3 | 3.9 | 1194 | 0.267 | 0.321 | 0.045 | 75 | 90 | 100 |
675018 | 1 | 3 | 5.5 | 1506 | 0.211 | 0.254 | 0.046 | 85 | 100 | 115 |
TBA | 1/0 | 3 | 5.6 | 1900 | 0.168 | 0.201 | 0.044 | 100 | 120 | 135 |
670963 | 1/0 | 3 | 5.8 | 1900 | 0.168 | 0.201 | 0.044 | 100 | 120 | 135 |
646672 | 2/0 | 3 | 6.1 | 2396 | 0.133 | 0.160 | 0.043 | 115 | 135 | 150 |
599619 | 3/0 | 3 | 6.5 | 3020 | 0.105 | 0.126 | 0.042 | 130 | 155 | 175 |
672057 | 4/0 | 3 | 7.1 | 3808 | 0.084 | 0.100 | 0.041 | 150 | 180 | 205 |
646667 | 250 | 3 | 7.8 | 4500 | 0.071 | 0.086 | 0.041 | 170 | 205 | 230 |
672257 | 300 | 3 | 8.7 | 5400 | 0.059 | 0.071 | 0.041 | 195 | 230 | 260 |
137880 | 350 | 3 | 9.2 | 6300 | 0.050 | 0.062 | 0.040 | 210 | 250 | 280 |
582220 | 400 | 3 | 9.8 | 7200 | 0.044 | 0.054 | 0.040 | 225 | 270 | 305 |
563211 | 500 | 3 | 12.5 | 9000 | 0.035 | 0.044 | 0.039 | 260 | 310 | 350 |
582223 | 500 | 3 | 12.6 | 9000 | 0.035 | 0.044 | 0.039 | 260 | 310 | 350 |
672259 | 500 | 3 | 13.2 | 9000 | 0.035 | 0.044 | 0.039 | 260 | 310 | 350 |
671494 | 500 | 3 | 13.2 | 9000 | 0.035 | 0.044 | 0.039 | 260 | 310 | 350 |
582129 | 600 | 3 | 13.8 | 10000 | 0.029 | 0.037 | 0.039 | 285 | 340 | 385 |
679401 | 600 | 3 | 15.2 | 10000 | 0.029 | 0.037 | 0.039 | 285 | 340 | 385 |
587573 | 750 | 3 | 15.1 | 10000 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
580013 | 750 | 3 | 15.1 | 10000 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
579924 | 750 | 3 | 15.1 | 10000 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
671392 | 750 | 3 | 15.5 | 10000 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
TBA | 1000 | 3 | 17.5 | 10000 | 0.018 | 0.025 | 0.037 | 375 | 445 | 500 |
* Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
Method 4 Color Code. (1-ONE, 2-TWO, 3-THREE)
Stock Code | Size |
---|---|
671633 | 4 |
670971 | 2 |
670963 | 1/0 |
Revision: 1.000.002
Updated On: Aug. 18, 2023, 2:40 p.m. UTC