SPEC 45041

Southwire® MACHINE FLEX™ CU 600/1000V PVC-Nylon Insulation TPE Gray Jacket. THHN

Type TC-ER Machine Tray Control Cable 600/1000 Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation Thermoplastic Elastomer Jacket, 90°C Dry 75°C Wet -40°C Cold Impact Identification Method 4

...

Construction:

  1. Conductor:Class K, Flexible stranded bare annealed copper per ASTM B3, B172, and B174
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer THHN
  3. Ground:One Green Ground with Yellow Stripe THHN
  4. Jacket:Sunlight Resistant Gray Thermoplastic Elastomer TPE: Other jacket colors available upon request

Applications and Features:

Southwire’s MachineFLEX™ control tray cables 600/1000 Volt conform to NFPA 79 and are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 130°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, Division 2 hazardous locations per NEC® Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC® 336.10. Southwire’s machine tray cable is ideal for use in CNC machines, grinding, cutting, metal forming, buffing, bottling equipment, conveyors, processing & packaging equipment, assembly lines, control panels, food and beverage, oil sands, plant expansion, wind ener- gy and data centers. Multiple approvals for multiple applications. Cable is rated for -40°C cold impact. Two conductor cables contain no green/yellow ground.

Specifications:

  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors
  • ASTM B174 Standard Specification for Bunch-Stranded Copper
  • UL 66 Fixture Wire Type TFFN (for sizes 18 and 16 AWG)
  • UL 83 Thermoplastic Insulated Wire and Cables (sizes 14 AWG to 1000 kcmil)
  • UL 758 AWM Style 2587
  • UL 1063 Machine Tool Wiring (MTW)
  • UL 1277 TC-ER
  • UL 1690 Data Processing Cable (DP-1)
  • UL 2277 Type WTTC
  • UL 13 Type PLTC-ER sizes 18-12AWG
  • UL 2250 Type ITC-ER on sizes 18-12 AWG
  • CSA C22.2 No. 210 Appliance wiring material products I/II A/B (Sizes 16 - 8AWG)
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 239 Control and instrumentation cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • CE/RoHS-2 – The CE Marking has been applied solely to express the conformance to the material restrictions identified in the RoHS-2 (2011/65/EU) Directive
  • NFPA 79 Electrical Standard for Industrial Machinery
  • Sample Print Legend:

    Print Legend 1:
    Southwire XXAWG (XXmm2) XX/C PVC/Nylon Type TC-ER EXXXXX (UL) 600V 90°C Dry 75C Wet Sun Res Oil Res I/II DIR BUR - 40°C OR MTW Flexing OR DP-1 OR WTTC 1000V OR AWM 2587 -- LLXXXXXX CSA AWM I/II A/B 105°C 1000V -40°C FT4 -- CSA FT4 CE RoHS -2 Made in USA

    Print Legend 2:
    SOUTHWIRE{R} XX AWG (X.XXmm2) X/C PVC/NYLON TYPE TC-ER E75755 MASTER-DESIGN (UL) 600V 90{D}C DRY 75{D}C WET SUN RES OIL RES I/II DIR BUR -40{D}C OR MTW FLEXING OR DP-1 OR WTTC 1000V OR PLTC-ER OR ITC-ER OR AWM 2587 -- LL90458 CSA CIC/TC FT4 OR AWM I/II A/B 105{D}C 1000V -40{D}C FT4 -- NOM-ANCE 90{D}C PVC/NYLON PVC-TPE THHN/THWN FT4 600V -- {CE} RoHS-2 MADE IN USA
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    677071182160.04420450.26610357.1488.6131.0--14
    581511183160.04420450.28115427.1488.6131.1--14
    582642184160.04420450.30620547.1488.6131.2--11
    582644185160.04420450.33225637.1488.6131.3--11
    581513187160.04420450.35835797.1488.6131.4--9
    582645189160.04420450.411451017.1488.6131.6--9
    5826461812160.04420450.456601287.1488.6131.8--7
    5826471818160.04420450.554902257.1488.6132.2--7
    6462621819160.04420450.560952007.1488.6132.2--7
    5815141825160.04420600.6351252537.1488.6132.5--6
    16 AWG
    677072162260.05920500.29416454.4875.4061.1--18
    581515163260.05920500.31124584.4875.4061.2--18
    582648164260.05920500.33932714.4875.4061.3--14
    582649165260.05920500.37040864.4875.4061.4--14
    581516167260.05920500.400561074.4875.4061.6--12
    TBA168260.05920500.429721264.4875.4061.7--12
    582651169260.05920500.462721374.4875.4061.8--12
    5826521612260.05920500.509971744.4875.4062.0--9
    5826531618260.05920650.6231452624.4875.4062.4--9
    6462631619260.05920650.6301542724.4875.4062.5--9
    5815171625260.05920650.7172023454.4875.4062.8--8
    5815181641260.05920900.9483325904.4875.4063.8--6
    14 AWG
    677073142410.07320500.32425582.8143.3911.2152025
    581519143410.07320500.34238772.8143.3911.3152025
    582654144410.07320500.37551962.8143.3911.5121620
    582655145410.07320500.411631142.8143.3911.6121620
    581521147410.07320500.445891492.8143.3911.7101417
    673795148410.07320500.4951021752.8143.3911.9101417
    582656149410.07320500.5161151882.8143.3912.0101417
    5826571412410.07320650.6081532572.8143.3912.471012
    5826581418410.07320650.6972303632.8143.3912.771012
    5815221425410.07320650.8063184862.8143.3913.26911
    12 AWG
    677074122650.09420500.36240801.7742.1371.4202530
    677188123650.09420500.389601081.7742.1371.5202530
    582659124650.09420500.420811361.7742.1371.6162024
    582660125650.09420500.5021011701.7742.1372.0162024
    582661127650.09420500.5021412191.7742.1372.0141721
    10 AWG
    6770751021050.11725500.430641191.1111.3391.7303540
    6771891031050.11725500.462971591.1111.3391.8303540
    5815231041050.11725500.5021292011.1111.3392.0242832
    5826621051050.11725500.5791612911.1111.3392.3242832
    5826631071050.11725650.6282263361.1111.3392.5212428
    8 AWG
    677190831680.15335650.6261573140.7150.8612.5405055
    643367841680.15335650.6802103610.7150.8612.7324044
    673797851680.15335700.7662634500.7150.8613.0324044
    6 AWG
    677191632590.19835700.7252684400.4500.5412.9556575
    643369642590.19835700.8173585620.4500.5413.2445260
    4 AWG
    677192434200.23550800.8893996490.2820.3403.5708595
    643371444200.23550800.9695328290.2820.3403.8566876
    2 AWG
    677193236510.302501001.0706379880.1790.2165.395115130
    643373246510.302501001.19684912620.1790.2165.97692104
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.