SPEC 45005

ROYAL GUARD™ CU 600V EPR Insulation Thermoset CPE-TS Jacket RHH/RHW-2. CT Rated - Sunlight Resistant - For Direct Burial - Silicone Free

Power Cable 600Volt Single Conductor Copper, Lead Free Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Cross-Linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket. CT Rated 1/0 and Larger - For Direct Burial - Sunlight Resistant - Oil Resistant - Silicone Free

...

Construction:

  1. Conductor:Class B compressed stranded tinned copper per ASTM B33 and ASTM B8
  2. Binder Tape:Mylar Tape
  3. Insulation:Lead Free Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
  4. Overall Jacket:Lead Free & Silicone-Free Cross-Linked/Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. CT Rated 1/0 and Larger - Sunlight Resistant - Oil Resistant - Silicone Free.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE® ROYAL GUARD® XX AWG ({mm2}) E32071 {UL} RHH/RHW-2 OR USE-2 90°C 600V SUN RES VW-1 PRI PRII -40°C FT4 -- IEEE 1202 {MM/DD/YY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorMin. Avg. Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ftlb/1000ft
    592004870.14145150.2785077
    589493670.17745300.34281121
    589492470.22545300.390128176
    652233470.22545300.390128176
    589491270.28245300.455204262
    594504270.28245300.455204262
    5894901190.32255450.536258346
    5894951/0190.36155450.576326421
    5894962/0190.40555450.622410516
    5945062/0190.40555450.622410516
    5920113/0190.45655450.663518631
    5895004/0190.51255450.728653780
    5945074/0190.51255450.728653780
    589497250370.55865650.836771955
    589499350370.66165650.93910801291
    589501500370.78965651.06215431786
    595421600610.86580651.20318522159
    592017750610.96880651.27823152644
    5894881000911.11780651.44330873464
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    59200481.11320.6530.7860.052405055
    58949361.32090.4110.4950.051556575
    58949241.53330.2580.3100.048708595
    65223341.53330.2580.3100.048708595
    58949121.85300.1620.1950.04595115130
    59450421.85300.1620.1950.04595115130
    58949012.16690.1280.1540.046110130145
    5894951/02.38440.1020.1220.044125150170
    5894962/02.410640.0810.0970.043145175195
    5945062/02.410640.0810.0970.043145175195
    5920113/02.613420.0640.0780.042165200225
    5895004/02.916920.0510.0620.041195230260
    5945074/02.916920.0510.0620.041195230260
    5894972503.320000.0430.0530.041215255290
    5894993503.728000.0310.0390.040260310350
    5895015005.340000.0220.0290.039320380430
    5954216006.048000.0180.0250.039350420475
    5920177506.360000.0140.0220.038400475535
    58948810007.280000.0110.0180.037455545615
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Inductive Reactance is based on non-ferrous conduit with one diameter spacing.

    Size and Color

    SizeGRN
    4652233
    2594504
    2/0594506
    4/0594507

    Revision: 1.000.008

    Updated On: Jan. 24, 2024, 6 p.m. UTC