SPEC 25077

CU 1000V LSZH Insulation. RW90

Single Copper Conductors, LSZH Insulation Solonon®, Sunlight Resistant, 1000V, 90ºC MAX, -40ºC MIN, Gasoline & Oil Resistant

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Low Smoke Zero Halogen Solonon® (XLPO)

Applications and Features:

Suitable for installation in Cable Trays, Underground Duct Banks - As per CE Code limitations (see Rule 12-2202) for grounding and bonding applications. Standard colour is black. Some sizes may be availabe in white, red, blue, yellow, brown, orange or grey. Green Duraground™ also available.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables
  • CSA C22.2 No.230 Tray Cables - Rated TC
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • Oil Res I & Sun Res - AWG 8 & Larger
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)
  • NFPA 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways
  • Sample Print Legend:

    SOUTHWIRE SOLONONplus{TM} LSZH XLPO 156205 {CSA} XXX KCMIL (XXX{mm2}) CU RW90 1000V VW-1 HAL-FREE TC PRI PRII GRI GRII -40°C SR FT4 ST-1
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.milinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA147450.160200.6322.6313.1700.05825
    TBA127450.178290.7521.6622.0020.05430
    TBA87450.231630.91320.6530.7860.05255
    TBA67600.2971041.12090.4110.4950.05175
    TBA47600.3451551.33330.2580.3100.04895
    TBA27600.4022371.65300.1620.1950.045130
    TBA1/019800.5213822.08440.1020.1220.044170
    TBA2/019800.5654732.210640.0810.0970.043195
    TBA3/019800.6165882.413420.0640.0780.042225
    TBA4/019800.6727302.616920.0510.0620.041260
    TBA25037900.7388662.920000.0430.0530.041290
    TBA35037900.84111913.328000.0310.0390.040350
    66447550037900.95617163.840000.0220.0290.039430
    TBA75061901.14824715.760000.0140.0220.038535
    664478100061901.30733476.580000.0110.0180.037615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandInsul. ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C
    AWG/KcmilNo.mmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA1471.144.063015.241428.6310.400.190325
    TBA1271.144.524317.782315.456.570.177230
    TBA871.145.879422.865872.142.580.170655
    TBA671.527.5415527.949301.351.620.167375
    TBA471.528.7623133.0214820.851.020.157595
    TBA271.5210.2135340.6423590.530.640.1476130
    TBA1/0192.0313.2356850.8037560.330.400.1444170
    TBA2/0192.0314.3570455.8847350.270.320.1411195
    TBA3/0192.0315.6587560.9659720.210.260.1378225
    TBA4/0192.0317.07108666.0475290.170.200.1345260
    TBA250372.2918.75128973.6689000.140.170.1345290
    TBA350372.2921.36177283.82124600.100.130.1312350
    664475500372.2924.28255496.52178000.070.100.1280430
    TBA750612.2929.163677144.78267000.050.070.1247535
    6644781000612.2933.204981165.10356000.040.060.1214615
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item

    Revision: 1.000.001

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC