SPEC 10025
SIMpull CoilPAK™ Wire Payoff
Construction:
- Conductor:Solid soft drawn bare copper per ASTM B3 or combination-unilay stranded soft drawn bare copper per ASTM B787
- Insulation:Heat and moisture resistant PVC insulation in various colors
- Sheath:Nylon jacket utilizing SIMpull® Technology
Applications and Features:
The SIMpull® CoilPAK™ Wire Payoff provides greater versatility and efficiency to branch circuit installations, eliminating the need for handling bulky spools and all the setup and energy that go along with them. SIMpull® CoilPAK™ Wire Payoffs increase both safety and productivity by reducing the physical effort associated with material handling, pulling wire out of the package, and pulling wire through conduit.
Specifications:
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Conductor | Insul. Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | No. | inch | mil | inch | lb/1000ft | |
580285◊ | 14 | 1 | Solid | 0.064 | 20 | 0.106 | 16 |
580264◊ | 12 | 1 | Solid | 0.080 | 20 | 0.123 | 23 |
586144◊ | 12 | 2 | Solid | 0.080 | 20 | 0.245 | 47 |
583897◊ | 12 | 3 | Solid | 0.080 | 20 | 0.368 | 70 |
580202◊ | 10 | 1 | Solid | 0.101 | 25 | 0.154 | 37 |
580297◊ | 10 | 2 | Solid | 0.101 | 25 | 0.307 | 73 |
586095◊ | 12 | 2 | 7 | 0.088 | 20 | 0.260 | 48 |
584533◊ | 12 | 3 | 7 | 0.088 | 20 | 0.390 | 73 |
580170◊ | 14 | 1 | 19 | 0.070 | 20 | 0.113 | 17 |
580182◊ | 12 | 1 | 19 | 0.090 | 20 | 0.132 | 25 |
580207◊ | 10 | 1 | 19 | 0.113 | 25 | 0.165 | 39 |
587251◊ | 10 | 2 | 7 | 0.113 | 25 | 0.326 | 76 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
Table 2 – Electrical and Engineering Data
Cond. Size | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance | Min Bending Radius | Allowable Ampacity In Raceway At 60°C | Allowable Ampacity In Raceway At 75°C | Allowable Ampacity In Raceway At 90°C |
---|---|---|---|---|---|---|---|
AWG/Kcmil | Ω/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp |
14 | 2.580 | 3.170 | 0.058 | 0.4 | 15 | 20 | 25 |
12 | 1.662 | 2.002 | 0.054 | 0.5 | 20 | 25 | 30 |
12 | 1.662 | 2.002 | 0.054 | 0.9 | 20 | 25 | 30 |
12 | 1.662 | 2.002 | 0.054 | 1.4 | 20 | 25 | 30 |
10 | 1.040 | 1.253 | 0.050 | 0.6 | 30 | 35 | 40 |
10 | 1.040 | 1.253 | 0.050 | 1.2 | 30 | 35 | 40 |
12 | 1.662 | 2.002 | 0.054 | 1.0 | 20 | 25 | 30 |
12 | 1.662 | 2.002 | 0.054 | 1.5 | 20 | 25 | 30 |
14 | 2.580 | 3.170 | 0.058 | 0.6 | 15 | 20 | 25 |
12 | 1.662 | 2.002 | 0.054 | 0.5 | 20 | 25 | 30 |
10 | 1.040 | 1.253 | 0.050 | 0.7 | 30 | 35 | 40 |
10 | 1.040 | 1.253 | 0.050 | 1.3 | 30 | 35 | 40 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Revision: 1.000.000
Updated On: Dec. 11, 2023, 9:29 p.m. UTC