SPEC 10020

Aluminum AlumaFlex® Silicone-Free RHH/RHW/USE-2

600 Volts. Underground Service Entrance Cable. AlumaFlex® Brand Aluminum Alloy (AA-8176) Conductor. Cross-linked Polyethylene (XLP) Insulation. High Heat, Moisture, and Sunlight Resistant. Rated SIS in sizes 6 – 4/0 AWG.

...

Construction:

  1. Conductor:Class B compact stranded bare aluminum per ASTM B800 and ASTM B801
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2 Silicone-Free

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B800 8000 Series Aluminum Alloy Wire
  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • RoHS-2 (European Directive 2011/65/EU)
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 {UL} XXX AWG COMPACT AL. --- {ALUMAFLEX}® AA8176 TYPE USE-2 OR RHH OR RHW-2 OR SIS XXX MILS XLP 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    272799670.169600.2952446
    272807470.213600.3393965
    272823260.268600.3946293
    272831180.299800.46778126
    2728491/0100.336800.50499151
    2728562/0120.376800.544125182
    2728643/0150.423800.591158221
    2728724/0190.475800.643199269
    272880250220.520950.720235321
    272898300350.570950.770282381
    272906350350.616950.816329435
    272914400350.659950.859376490
    272922500340.736950.938471601
    272930600580.8131101.037565724
    596530700580.8771101.157659925
    272955750610.9081101.140706884
    TBA900610.9991101.3518471376
    TBA1000611.0601101.4129411489
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 60°CAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    27279961.11570.6610.8120.051405055
    27280741.32500.4160.5100.048556575
    27282321.53980.2610.3210.0457590100
    27283111.85020.2070.2540.04685100115
    2728491/02.06330.1640.2010.044100120135
    2728562/02.17980.1300.1600.043115135150
    2728643/02.310060.1030.1260.042130155175
    2728724/02.512690.0820.1000.041150180205
    2728802502.815000.0690.0860.041170205230
    2728983003.018000.0580.0710.041195230260
    2729063503.221000.0490.0620.040210250280
    2729144003.324000.0430.0540.040225270305
    2729225003.730000.0350.0440.039260310350
    2729306005.136000.0290.0370.039285340385
    5965307005.742000.0250.0330.038315375425
    2729557505.645000.0230.0310.038320385435
    TBA9006.854000.0190.0270.037355425480
    TBA10007.160000.0170.0250.037375445500
    † Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    † Ampacities have been adjusted for more than Three Current-Carrying Conductors.
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Stock Code Colors

    SizeBlackBrownWhiteGreen
    BlackBrownWhiteGreen
    6272799301572
    4272807334680
    2272823575240
    1272831
    1/0272849
    2/0272856
    3/0272864
    4/0272872
    250272880
    300272898
    350272906576086
    400272914
    500272922560674
    600272930
    700596530
    750272955