SPEC 25084

CU 2000V EPR/LSZH RW90 Traction Cable

2000 Volt Single Conductor Copper, No Lead Ethylene Propylene Rubber (NLEPR) insulation RW90 SOLONON® Low Smoke Zero Halogen (LSZH) Jacket

...

Construction:

  1. Conductor:Stranded bare or tinned copper per ASTM B3 or B33. Center strand embossed with “Southwire, Year, Plant” when required
  2. Binder Tape:Mylar Tape
  3. Insulation:No Lead Ethylene Propylene Rubber (EPR) Type RW90
  4. Overall Jacket:SOLONON® Low Smoke Zero Halogen (LSZH) Jacket

Applications and Features:

Southwire 2000V EPR/SOLONON Power Cable is suited for use in mass transit and general industry applications where flexibility, fire resistance, and low smoke generation are a concern. May be installed in wet or dry locations in cable trays or raceways. These cables are capable of operating continuously at a conductor temperature not in excess of 90°C for normal operation, 130°C for emergency overload conditions, and 250°C for short circuit conditions. Resistance to moisture and most oils, acids, and alkalis with an overall durable LSZH XLPO jacket. Meets Flame Spread and Smoke Release requirements of NFPA 130. Alternate constructions available upon request.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
  • ASTM B172 Standard Specification for Rope-Lay-Stranded Copper Conductors Having Bunch-Stranded Copper Conductors (As Applicable)
  • CSA C22.2 No. 38 Thermoset-insulated wires and cables Type RW90
  • CSA C22.2 No.230 Tray Cables - Rated TC-ER
  • CSA C22.2 No. 2556 / UL 2556 Cable Test Methods
  • CSA SUN RES - for Sunlight Resistant rating
  • CSA ST1 Smoke Test - marked FT4-ST1 (1/0 and Larger)
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Oil Res I & Sun Res - AWG 8 & Larger
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • NFPA 130 Standard for Fixed Guideway Transit and Passenger Rail Systems (500kcmil & Larger)
  • Sample Print Legend:

    {SQMTR} SOUTHWIRE{R} LL90458 {CSA} XXX KCMIL CU TYPE RW90 -40{D}C XX MILS EPR XX MILS SOLONON{R} ST1 FT4 PR I PR II SUN RES OIL RES TC-ER 2000V YEAR OF MANUFACTURE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessJacket Thickness1Approx. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.inchmilmilinchlb/1000ftinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmp
    TBA1/0190.36165450.5413912.18440.1020.1220.044170
    TBA2/0190.40565450.5854822.310640.0810.0970.043195
    TBA3/0190.45665450.6365982.513420.0640.0780.042225
    TBA4/0190.51265450.6927412.716920.0510.0620.041260
    TBA250370.55875650.7688843.020000.0430.0530.041290
    TBA350370.66175650.87112123.428000.0310.0390.040350
    TBA500370.78975650.99916973.940000.0220.0290.039430
    668908*500910.78975651.09318035.440000.0220.0290.039430
    TBA535.513490.83090651.15718035.842820.0210.0320.028446
    589215535.313490.830120951.28820106.442820.0210.0320.028446
    669880750610.96890651.30226566.560000.0140.0220.038535
    TBA1000611.11790651.35733306.780000.0110.0180.037615
    665061!10004271.11790651.49335437.480000.0110.0180.037615
    5975901000611.117120651.51335367.580000.0110.0180.037615
    6691541500911.37115951.81852779.0120000.0070.0160.035705
    5925211500911.371401251.93454819.6120000.0070.0160.035705
    TBA20001271.583115951.86365699.3160000.0050.0160.034750
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ¹Thicknesses reported as minimum average
    * Bare copper
    ! Class G stranding per ASTM B173: Standard Specification for Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members, for Electrical Conductors
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorInsul. ThicknessJacket Thickness1Approx. ODApprox. WeightMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity In Raceway 90°C†
    AWG/KcmilNo.mmmmmmmmkg/kmmmnewtonΩ/kmΩ/kmΩ/kmAmp
    TBA1/0199.171.651.1413.7458253.3437560.33460.400.1444170
    TBA2/01910.291.651.1414.8671758.4247350.26570.320.1411195
    TBA3/01911.581.651.1416.1589063.5059720.21000.260.1378225
    TBA4/01913.001.651.1417.58110368.5875290.16730.200.1345260
    TBA2503714.171.911.6519.51131676.2089000.14110.170.1345290
    TBA3503716.791.911.6522.12180486.36124600.10170.130.1312350
    TBA5003720.041.911.6525.37252599.06178000.07220.100.1280430
    668908*5009120.041.911.6527.762683137.16178000.07220.100.1280430
    TBA535.5134921.082.291.6529.392683147.32190550.06890.100.0919446
    589215535.3134921.083.052.4132.722991162.56190550.06890.100.0919446
    6698807506124.592.291.6533.073953165.10267000.04590.070.1247535
    TBA10006128.372.291.6534.474956170.18356000.03610.060.1214615
    665061!100042728.372.291.6537.925273187.96356000.03610.060.1214615
    59759010006128.373.051.6538.435262190.50356000.03610.060.1214615
    66915415009134.802.922.4146.187853228.60534000.02300.050.1148705
    59252115009134.803.563.1849.128157243.84534000.02300.050.1148705
    TBA200012740.212.922.4147.329776236.22712000.01640.050.1115750
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ¹Thicknesses reported as minimum average
    * Bare copper
    ! Class G stranding per ASTM B173: Standard Specification for Rope-Lay-Stranded Copper Conductors Having Concentric-Stranded Members, for Electrical Conductors

    Revision: