SPEC 60127

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor 277/480V Colors

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts Rated VW-1. Lightweight Aluminum Interlocked Armor.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor

Applications and Features:

Southwire Armorlite® Type MC Cable is suitable for use as follows:
  • Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Environmental air-handling spaces per NEC 300.22 (C).
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways.
  • Under raised floors for information technology equipment conductors and cables per NEC Article 645
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Binder tape with print legend wrapped around assembly.
  • Type THHN/THWN rated 90ºC Dry.
  • Anti-Short bushing not required

  • Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • REACH/RoHS-2 (Chemical Limit) Compliant
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    SOUTHWIRE E96627 {UL} TYPE MC XX AWG THHN OR THWN CDRS FOR USE IN CABLE TRAYS 600 VOLTS
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround Size x NumDiameter Over ArmorOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchlbs/1000ft
    589090144BN/OE/YW/GY0.064Solid201x140.508116
    689448122PE/GY0.080Solid201x120.487107
    689406122OE/GY0.080Solid201x120.487107
    689364122BN/GY0.080Solid201x120.487107
    689323122YW/GY0.080Solid201x120.487107
    611270123OE/YW/GY0.080Solid201x120.518134
    689562123BN/OE/GY0.080Solid201x120.518134
    610523123BN/YW/GY0.080Solid201x120.518134
    689570124BN/OE/YW/GY0.080Solid201x120.553162
    689604102BN/GY0.101Solid251x100.554154
    610522102YW/GY0.101Solid251x100.554154
    551167102BN/GY0.101Solid251x100.554154
    553193103BN/OE/YW0.101Solid251x100.593194
    689539103BN/OE/GY0.101Solid251x100.593194
    689414104BN/OE/YW/GY0.101Solid251x100.637235
    587745122OE/GY0.09019201x120.508112
    551110122BN/GY0.09019201x120.508112
    551108122YW/GY0.09019201x120.508112
    551114123BN/OE/GY0.09019201x120.542140
    551276102BN/GY0.11719251x100.587166
    551121103BN/OE/GY0.11719251x100.630209
    551278104BN/OE/YW/GY0.11719251x100.678254
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin. Bend Radius*DC Resistance at 25°CAC Resistance at 75°CAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftAmpAmpAmp
    589090◊143.52.6313.170121620
    689448◊123.41.6622.002202530
    689406◊123.41.6622.002202530
    689364◊123.41.6622.002202530
    689323◊123.41.6622.002202530
    611270◊123.61.6622.002202530
    689562◊123.61.6622.002202530
    610523◊123.61.6622.002202530
    689570◊123.81.6622.002162024
    689604◊103.81.041.253303540
    610522◊103.81.041.253303540
    551167◊103.81.041.253303540
    553193◊104.11.041.253303540
    689539◊104.11.041.253303540
    689414◊104.41.041.253242832
    587745◊123.51.6622.002202530
    551110◊123.51.6622.002202530
    551108◊123.51.6622.002202530
    551114◊123.71.6622.002202530
    551276◊104.11.041.253303540
    551121◊104.41.041.253303540
    551278◊104.71.041.253242832
    Ampacities have been adjusted for more than Three Current-Carrying Conductors
    Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.

    Revision: 3.0.00C