SPEC 60103

Armorlite® Type MC THHN/THWN Circuit Size Copper Conductor PVC Jacketed 120/208V Colors. Silicone Free

Copper THHN/THWN Insulated Singles. Green Insulated Copper Grounding Conductor. UL Listed. 600 Volts. Rated VW-1. Lightweight Aluminum Interlocked Armor. PVC Jacketed, Sunlight Resistant and Direct Burial.

...

Construction:

  1. Conductor:Solid or 19 strands class C compressed copper per ASTM B3 and ASTM B8
  2. Insulation:All phases are insulated with Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  3. Ground:Green insulated ground. Polyvinyl Chloride with Nylon Sheath Type THHN/THWN
  4. Binder:Mylar tape
  5. Armor:Aluminum Interlocked Armor
  6. Jacket:Polyvinyl Chloride (PVC) Jacket, sunlight resistant

Applications and Features:

Southwire Armorlite® Jacketed Type MC Cable is suitable for use as follows:
  • Branch and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
  • Direct burial applications, embedded in concrete, and where exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids.
  • Fished or embedded in plaster.
  • Concealed or exposed installations.
  • Suitable for Wet Location per NEC 330.10(11)
  • Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
  • Installation in cable tray and approved raceways, or as aerial cable on a messenger.
  • Under raised floors for information technology equipment conductors and cables per NEC Article 645
  • Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
  • Type THHN/THWN rated 90ºC Dry/ 75ºC Wet
  • Anti-Short bushing not required

  • Southwire Armorlite® Type MC Cable - meets or exceeds the following requirements:
  • UL Online Product Guide Info - Metal-Clad Cable (PJAZ) ( www.ul.com )
  • Federal Specification A-A59544 (formerly J-C-30B)
  • NFPA 70 (National Electrical Code), Article 330
  • Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems
  • Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1569 Metal-Clad Cables
  • UL 1479 Standard for Safety Fire Tests of Penetration Firestops
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • REACH/RoHS-2 (Chemical Limit) Compliant
  • Buy American: Compliant with Buy American Requirements, found in 49 U.S.C. § 5323(j); specify “Made in the USA Only!” when ordering to ensure your project receives American made products.
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE MASTER-DESIGN {UL} E96627 X/C XX AWG CU THHN OR THWN CDRS 600 VOLTS GG 1 X X AWG CU TYPE MC EZ-JKT FOR CT USE SUN. RES. DIRECT BURIAL 90{D}C
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeConductor NumberColorDiameter Over ConductorConductor StrandingInsulation ThicknessGround Size x NumDiameter Over ArmorJacket Thickness1Approx. ODOverall Weight
    AWG/KcmilinchmilsNo. x AWGinchmilinchlbs/1000ft
    610037142BK/WE0.064Solid201x140.451500.557143
    610041143BK/RD/WE0.064Solid201x140.478500.584165
    564289143BK/RD/WE0.064Solid201x140.497500.603172
    610045144BK/RD/BE/WE0.064Solid201x140.508500.614187
    561045122BE/WE0.08Solid201x120.487500.593175
    561041122RD/WE0.08Solid201x120.487500.593175
    610050122BK/WE0.08Solid201x120.487500.593162
    610054123BK/RD/WE0.08Solid201x120.518500.624207
    610059124BK/RD/BE/WE0.08Solid201x120.553500.659240
    561052102BE/WE0.101Solid251x100.554500.660232
    561048102RD/WE0.101Solid251x100.554500.660232
    610064102BK/WE0.101Solid251x100.554500.660232
    610068103BK/RD/WE0.101Solid251x100.593500.699277
    610074104BK/RD/BE/WE0.101Solid251x100.637500.743324
    561439122BK/WE0.0919201x120.508500.614183
    567274123BK/RD/WE0.0919201x120.542500.648215
    677379124BK/RD/BE/WE0.0919201x120.580500.686250
    585616102RD/WE0.11719251x100.587500.693248
    552808102BK/WE0.11719251x100.587500.693248
    553631103BK/RD/WE0.11719251x100.630500.736297
    556420104BK/RD/BE/WE0.11719251x100.678500.784349
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    Note: Conductor number = number of phase conductors plus neutral. Does not include green ground.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin. Bend Radius*DC Resistance at 25°CAC Resistance at 75°CAllowable Ampacity Raceway 60°CAllowable Ampacity Raceway 75°CAllowable Ampacity Raceway 90°C
    AWG/KcmilInchesΩ/1000ftΩ/1000ftAmpAmpAmp
    610037◊143.82.6313.170152025
    610041◊144.02.6313.170152025
    564289◊144.22.6313.170152025
    610045◊144.22.6313.170121620
    561045◊124.11.6622.002202530
    561041◊124.11.6622.002202530
    610050◊124.11.6622.002202530
    610054◊124.31.6622.002202530
    610059◊124.61.6622.002162024
    561052◊104.61.0401.253303540
    561048◊104.61.0401.253303540
    610064◊104.61.0401.253303540
    610068◊104.81.0401.253303540
    610074◊105.21.0401.253242832
    561439◊124.21.6622.002202530
    567274◊124.51.6622.002202530
    677379◊124.81.6622.002162024
    585616◊104.81.041.253303540
    552808◊104.81.0401.253303540
    553631◊105.11.0401.253303540
    556420◊105.41.0401.253242832
    Ampacities have been adjusted for more than Three Current-Carrying Conductors
    Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.