SPEC 80120

AAC

All Aluminum Conductor. Bare.

...

Construction:

  1. Conductor:Aluminum 1350-H19 wires, concentrically stranded.

Applications and Features:

Classes1 AA and A are used primarily for overhead transmission and primary and secondary distribution, where ampacity must be maintained and a lighter conductor (compared to ACSR) is desired, and when conductor strength is not a critical factor. Classes B and C are used primarily as bus, apparatus connectors and jumpers, where additional flexibility is required.

1Classes refer to stranding and are an indication of relative conductor flexibility, AA being the least flexible, C the most flexible.

Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • Table 1 – Weights and Measurements
    Stock NumberCode WordSizeNo. of WiresStranding ClassInd. Wire DiaComp CableCross-Sectional AreaOverall Weight
    (AWG or kcmil)inchinchSq. inchlbs/1,000'
    Peachbell67A0.06120.1840.020625
    Rose47A0.07720.2320.032839
    100834Iris27AA, A0.09740.2920.052262
    Pansy17AA0.10930.3280.065778
    100859Poppy1/07AA, A0.12280.3680.082999
    100867Aster2/07AA, A0.13790.4140.1045125
    100875Phlox3/07AA, A0.15480.4640.1317157
    100883Oxlip4/07AA, A0.17390.5220.1663198
    Sneezewort2507AA0.1890.5670.1964234
    Valerian25019A0.11470.5740.1963234
    Daisy266.87AA0.19520.5860.2095250
    100909Laurel266.819A0.11850.5920.2095250
    Peony30019A0.12570.6280.2358281
    100917Tulip336.419A0.13310.6650.2644315
    148122Daffodil35019A0.13570.6790.2748328
    100925Canna397.519AA, A0.14460.7230.312373
    Goldentuft45019AA0.15390.7690.3534422
    100933Cosmos47719AA0.15840.7920.3744447
    Syringa47737A0.11350.7950.3744447
    Zinnia50019AA0.16220.8110.3926469
    Hyacinth50037AA0.11620.8140.3924469
    100941Dahlia556.519AA0.17110.8560.4369522
    100966Mistletoe556.537AA0.12260.8580.4368522
    157743Meadowsweet60037AA0.12730.8910.4709562
    100974Orchid63637AA, A0.13110.9180.4995596
    Heuchera65037AA0.13250.9280.5102609
    Verbena70037AA0.13750.9630.5494656
    Flag70061A0.10710.9640.5495656
    Violet715.537AA0.13910.9730.5623671
    Nasturtium715.561AA0.10830.9750.5619671
    182618Petunia75037AA0.14240.9970.5893703
    Cattail75061AA0.11090.9980.5892703
    100990Arbutus79537AA0.14661.0260.6245745
    Lilac79561A0.11421.0270.6248745
    Cockscomb90037AA0.1561.0920.7072844
    Snapdragon90061AA0.12151.0930.7072844
    101014Magnolia95437AA0.16061.1240.7495894
    Goldenrod95461A0.12511.1250.7498894
    Hawkweed100037AA0.16441.1510.7854937
    Camellia100061AA0.1281.1520.7849937
    101022Bluebell1033.537AA0.16711.170.8114969
    Larkspur1033.561AA0.13021.1710.8122969
    Marigold111361AA, A0.13511.2160.87441043
    Hawthorn1192.561AA, A0.13981.2580.93631118
    101105Narcissus127261AA, A0.14441.30.9991192
    Columbine1351.561AA, A0.14881.341.06081267
    Carnation143161AA, A0.15321.3781.12441341
    Gladiolus1510.561A0.15741.4161.18691416
    101147Coreopsis159061AA0.16141.4531.2481490
    Jessamine175061AA0.16941.5241.37481640
    Cowslip200091A0.14821.6311.56971875
    Sagebrush225091A0.15721.731.76622130
    182675Lupine250091A0.16571.8231.96232366
    Bitterroot275091A0.17381.9122.15892603
    Trillium3000127A0.15371.9982.35642839
    Bluebonnet3500127A0.1662.1582.74863345
    Table 2 - Electrical and Engineering Data
    Stock NumberCode WordSizeRated StrengthDC Resistance @ 20CAC Resistance @ 75CAllowable Ampacity+
    (AWG or kcmil)lbsOhms/1,000'Ohms/1,000'Amps
    Peachbell65630.6580.805103
    Rose48810.4140.506138
    100834Iris213500.260.318185
    Pansy116400.2070.252214
    100859Poppy1/019900.1640.2247
    100867Aster2/025100.130.159286
    100875Phlox3/030400.1030.126331
    100883Oxlip4/038300.08170.0999383
    Sneezewort25045200.06910.0846425
    Valerian25046600.06910.0846426
    Daisy266.848300.06480.0793443
    100909Laurel266.849700.06480.0793444
    Peony30054800.05760.0706478
    100917Tulip336.461500.05140.063513
    148122Daffodil35063900.04940.0605526
    100925Canna397.571100.04350.0534570
    Goldentuft45078900.03840.0472616
    100933Cosmos47783600.03620.0445639
    Syringa47786900.03620.0445639
    Zinnia50087600.03460.0425658
    Hyacinth50091100.03460.0425658
    100941Dahlia556.597500.03110.0382703
    100966Mistletoe556.599400.03110.0382704
    157743Meadowsweet600107000.02880.0355738
    100974Orchid636114000.02720.0335765
    Heuchera650116000.02660.0328775
    Verbena700125000.02470.0305812
    Flag700129000.02470.0305812
    Violet715.5128000.02420.0299823
    Nasturtium715.5131000.02420.0299823
    182618Petunia750131000.0230.0286847
    Cattail750135000.0230.0286847
    100990Arbutus795139000.02170.027878
    Lilac795143000.02170.027879
    Cockscomb900154000.01920.0239948
    Snapdragon900159000.01920.0239948
    101014Magnolia954164000.01810.0226982
    Goldenrod954169000.01810.0226983
    Hawkweed1000172000.01730.02161010
    Camellia1000177000.07130.02161011
    101022Bluebell1033.5177000.01670.0211031
    Larkspur1033.5183000.01670.0211032
    Marigold1113197000.01550.01951079
    Hawthorn1192.5211000.01450.01831124
    101105Narcissus1272220000.01360.01731169
    Columbine1351.5234000.01280.01631212
    Carnation1431243000.01210.01551253
    Gladiolus1510.5256000.01140.01471294
    101147Coreopsis1590270000.01090.01411333
    Jessamine1750297000.009880.01291408
    Cowslip2000342000.008640.01151518
    Sagebrush2250375000.007760.01051612
    182675Lupine2500419000.006980.009691706
    Bitterroot2750461000.006350.0091793
    Trillium3000503000.005820.008341874
    Bluebonnet3500587000.0050.007562024

    Revision: 1.000.000

    Updated On: Dec. 11, 2023, 9:29 p.m. UTC