SPEC 83353

Covered Line Wire With Crosslinked Polyethylene (XLPE)

Aluminum Conductor Covered with Black Crosslinked Polyethylene

...

Construction:

  1. Conductor:Conductors are solid or stranded compressed aluminum
  2. Insulation:Black Crosslinked Polyethylene (XLPE)

Applications and Features:

Aluminum alloy 1350-H19 or 6201 concentrically stranded. Covered with crosslinked polyethylene (XLP). Used primarily for, but not limited to, overhead secondary distribution lines. Installed on insulators, otherwise treated as a bare conductor. Crosslinked covered line wires have the below temperature ratings:

  • Normal Service temperature of 90ºC
  • Emergency Overload of 130ºC
  • Short Circuit temperature of 250ºC
  • Specifications:

  • ASTM B230 Aluminum, 1350-H19 Wire for Electrical Purposes
  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B400 Standard Specification for Compact Round Concentric-Lay-Stranded, Aluminum 1350 Conductors
  • ICEA S-70-547 Weather Resistant Polyethylene Covers Conductors
  • Table 1 Weights and Measurements H19
    Stock CodeCode WordSizeStrandingCover ThicknessTotal DiameterRated StrengthWeight Per 1000 ft. (lbs.)Allowable Ampacity+
    AWG/KcmilNo.milsinchlbslb/1000ftamps
    Apple61300.22244531105
    Plum67300.23851056105
    Pear41300.26471047135
    663570Apricot47300.28579051140
    Cherry21450.348110078180
    104240Peach27450.373122084180
    Nectarine17450.4081470104210
    104257Quince1/07600.4771790136240
    Orange2/07600.5222260167280
    104273Fig3/07600.572740205320
    104281Olive4/07600.6263450253370
    104299Pomegranate4/019600.6323620247370
    Mulberry266.819600.6944470305430
    104315Annona336.419600.7655540377495
    148130Chinquapin35019600.7785751390506
    Molles397.519800.8616400462545
    104331Huckleberry47737800.9317820538610
    104349Paw Paw556.537800.9928950619670
    202127Breadfruit63661951.08110500715720
    148460Persimmon79561951.18612900877825
    202135Grapefruit1033.561951.326165001128970
    +Ampacity ratings based on 75ºC conductor temperature 25ºC ambient temperature elevation - sea level. Emissivity 0.91 coefficient of absorption 0.95. Thermal resistivity of covering - 375 C M /Watt-CM. Wind speed 2 ft./sec. in sun.
    Table 2 Weights and Measurements 6201
    Stock CodeCode WordEquiv Dia (AWG)*SizeStrandingCover ThicknessTotal DiameterRated StrengthWeightAllowable Ampacity+
    AWGKcmilmilsmilsLbsLbs/1000 ft.amps
    Hornbeam448.69730310136060145
    104547Linden277.47745406216099190
    104554Oilnut1/0123.37605183440159250
    Waterash2/0155.47605674160195290
    104570Shellbark3/0195.77606225240240335
    Planetree4/0246.97606836610297385
    +Ampacity ratings based on 75ºC conductor temperature 25ºC ambient temperature elevation - sea level. Emissivity 0.91 coefficient of absorption 0.95. Thermal resistivity of covering - 375 C M /Watt-CM. Wind speed 2 ft./sec. in sun.
    *Diameter equivalent to ACSR construction or 1350 aluminum equivalent.

    Revision: 1.000.000