SPEC 85029
Multi-Conductor CU 600 V FR-XLPE LCT Shielded Thermoplastic CPE-TP Jacket Power Cable Color Method 1 Table 1
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Shielded Thermoplastic Chlorinated Polyethylene Chloride (CPE-TP) Jacket, Power Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE)
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Shield:5 mils copper Longitudinally-Applied Corrugated Tape (LCT) shield
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoplastic Chlorinated Polyethylene Chloride (CPE-TP)
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated construction can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE E75755 {UL} XX AWG X/C FR-XLPE XHHW-2 TYPE TC-ER CDRS 90C CPE JKT SHIELDED 600V SUN RES YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT SHIELDED 600V SUN. RES. DIRECT BURIAL YEAR SEQUENTIAL FOOTAGE MARKS SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |
625635 | 8 | 12 | 7 | 0.141 | 45 | 80 | 1.229 | 701 | 1113 | 0.653 | 0.786 | 14.7 | 20 | 25 | 27 |
604320 | 8 | 4 | 7 | 0.142 | 45 | 60 | 0.78 | 255 | 434 | 0.653 | 0.786 | 9.3 | 32 | 40 | 44 |
625639 | 6 | 2 | 7 | 0.177 | 45 | 60 | 0.756 | 210 | 363 | 0.411 | 0.495 | 9 | 55 | 65 | 75 |
604319 | 6 | 3 | 7 | 0.177 | 45 | 60 | 0.802 | 278 | 452 | 0.411 | 0.495 | 9.6 | 55 | 65 | 75 |
TBA | 6 | 4 | 7 | 0.177 | 45 | 80 | 0.914 | 383 | 579 | 0.411 | 0.495 | 11.0 | 44 | 52 | 60 |
604318 | 4 | 3 | 7 | 0.225 | 45 | 80 | 0.94 | 457 | 713 | 0.258 | 0.31 | 11.2 | 70 | 85 | 95 |
TBA | 4 | 4 | 7 | 0.225 | 45 | 80 | 1.03 | 586 | 815 | 0.258 | 0.31 | 12.4 | 56 | 68 | 76 |
604316 | 2 | 2 | 7 | 0.282 | 45 | 80 | 1.014 | 447 | 698 | 0.162 | 0.195 | 12.1 | 95 | 115 | 130 |
622692 | 2 | 4 | 7 | 0.282 | 45 | 80 | 1.16 | 903 | 1216 | 0.162 | 0.195 | 13.9 | 76 | 92 | 104 |
604315 | 1 | 2 | 19 | 0.322 | 55 | 80 | 1.122 | 596 | 903 | 0.128 | 0.154 | 13.4 | 110 | 130 | 145 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
^ UL Listed part number
! Tinned copper 19 strand combination unilay conductor per ASTM B787
^ UL Listed part number
! Tinned copper 19 strand combination unilay conductor per ASTM B787