SPEC 85015
Multi-Conductor CU 600 V FR-XLPE Thermoplastic LSZH-TP Jacket Control Cable Color Method 1 Table 1
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8 (tinned copper optional per ASTM B33)
- Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Rip Cord:Rip cord for ease of jacket removal
- Overall Jacket:Thermoplastic SOLONON® Low Smoke Zero Halogen (LSZH-TP) Jacket
Applications and Features:
Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Specifications:
Sample Print Legend:
UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C LSZH JKT 600V SUN. RES. SUITABLE FOR DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Non UL Listed
SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C LSZH JKT 600V SUN. RES. SUITABLE FOR DIRECT BURIAL YEAR {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
16 AWG | |||||||||||||||||||
6247970 | 16 | 12 | 7 | 0.056 | 25 | 60 | 0.573 | 96 | 205 | 4.181 | 5.037 | 2.2 | 0 | 0 | 9 | ||||
10 AWG | |||||||||||||||||||
624152 | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.44 | 64 | 118 | 1.04 | 1.253 | 1.7 | 30 | 35 | 40 | ||||
624150 | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.471 | 97 | 172 | 1.04 | 1.253 | 1.8 | 30 | 35 | 40 | ||||
6625480 | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.506 | 129 | 206 | 1.04 | 1.253 | 2 | 24 | 28 | 32 | ||||
6218970 | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.51 | 129 | 208 | 1.04 | 1.253 | 2 | 24 | 28 | 32 | ||||
624147 | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.641 | 226 | 357 | 1.04 | 1.253 | 2.5 | 21 | 24 | 28 | ||||
625524 | 10 | 9 | 7 | 0.113 | 30 | 60 | 0.741 | 291 | 450 | 1.04 | 1.253 | 2.9 | 21 | 24 | 28 | ||||
626225 | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.879 | 388 | 619 | 1.04 | 1.253 | 3.5 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
! Triple stripes on insulation
^ UL Listed part number
^^ Thermoset Low Smoke Zero Halogen (LSZH-TS) Jacket
! Triple stripes on insulation
^ UL Listed part number
^^ Thermoset Low Smoke Zero Halogen (LSZH-TS) Jacket
Revision: 3.0.00C