SPEC 85013

Multi-Conductor CU 600 V PE/PVC Insulation PVC Jacket Control Cable Color Method 1 Table 1

Control Cable 600 Volt Copper Conductors, Polyethylene and Polyvinyl Chloride (PE/PVC) Insulation Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 1. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:20 mils Polyethylene (PE) and 10 mils Polyvinyl Chloride (PVC) for cable sizes 16 AWG and larger
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C for normal operation in wet and dry locations, 90°C for emergency overload, and 150°C for short circuit conditions.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA CSA marking is available upon request
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 1
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    Non UL Listed
    SOUTHWIRE XX AWG X/C PE/PVC CDRS 75C PVC JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600V {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.ColorInsul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    60678618770.045M1T125450.38535886.6698.0351.5--9
    606787181270.045M1T125450.495601376.6698.0351.9--7
    16 AWG
    61912816470.056M1T125450.38032814.1815.0371.5--14
    66906616570.056M1T125450.509791614.1815.0372.0--14
    14 AWG
    62064614470.070M1T230450.417511072.6313.1701.6121620
    60677614770.070M1T230450.494891662.6313.1701.9101417
    606777141270.070M1T230600.6741532902.6313.1702.671012
    12 AWG
    61685612470.088M1T230450.453811521.6622.0021.8162024
    61741612570.088M1T230600.5431011901.6622.0022.1162024
    61917312670.088M1T230600.5841222241.6622.0022.3162024
    61742112770.088M1T230600.5881422511.6622.0022.3141721
    577810$127190.088M1T230600.6741422761.6622.0022.6141721
    61938212970.088M1T230600.6751833121.6622.0022.7141721
    619993$1212190.088M1T230600.7542444001.6622.0023.0101215
    617420121270.088M1T230600.7642444001.6622.0023.0101215
    10 AWG
    61871910270.113M1T230450.444641201.0401.2531.7303540
    60677810270.113M1T230450.448641251.0401.2531.7303540
    61911710370.113M1T230450.471971661.0401.2531.8303540
    60677910370.113M1T130450.471971661.0401.2531.8303540
    61872010470.113M1T130600.5421292261.0401.2532.1242832
    61930110470.113M1T130600.5461292271.0401.2532.1242832
    61673310470.113M1T230450.5511292251.0401.2532.2242832
    60678110570.113M1T130600.5911612721.0401.2532.3242832
    61917810770.113M1T130600.6432263481.0401.2532.5212428
    61917910870.113M1T230600.7002583901.0401.2532.8212428
    60678210970.113M1T230600.7472914441.0401.2532.9212428
    619181101070.113M1T230600.8143234871.0401.2533.2151720
    606783101270.113M1T230800.8913886101.0401.2533.5151720
    618911$1012190.117M1T230800.8873885981.0401.2533.5151720
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    ^ UL listed part number
    $ 19 strand combination unilay conductor per ASTM B787
    * Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements. Ampacities have been adjusted for stock numbers containing more than Three Current-Carrying Conductors.