SPEC 85009

Multi-Conductor CU 600 V FR-XLPE Thermoset CPE-TS Jacket Control Cable Color Method 1 Table 2

Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation Thermoset Chlorinated Polyethylene (CPE-TS) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
  2. Insulation:Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Rip Cord:Rip cord for ease of jacket removal
  6. Overall Jacket:Thermoset Chlorinated Polyethylene (CPE-TS) Jacket

Applications and Features:

Southwire’s 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
  • VW-1 (Vertical-Wire) Flame Test
  • Sample Print Legend:

    UL Listed
    SOUTHWIRE E75755 {UL} XX AWG X/C TYPE TC XHHW-2 CDRS 90C CPE JKT FT4 VW-1 600V SUN RES {MM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FTG

    Non UL Listed
    SOUTHWIRE XX AWG X/C FR-XLPE CDRS 90C CPE JKT 600V SUN. RES. DIRECT BURIAL YEAR{SEQUENTIAL FOOTAGE MARKS} SEQ FEET

    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    62213518770.04525450.38135876.6698.0351.5009
    6206200182070.04525600.631002326.6698.0352.5007
    14 AWG
    625934014270.0730450.35725692.6313.171.4152025
    625838014370.0730450.37738872.6313.171.5152025
    625833014470.0730450.41511092.6313.171.6121620
    60752714470.0730450.418511122.6313.171.6121620
    625828014570.0730450.447641282.6313.171.7121620
    625824014770.0730450.486891672.6313.171.9101417
    603776148190.0730600.5611022082.6313.172.2101417
    625819014970.0730600.5951152272.6313.172.3101417
    60752814970.0730600.6031152312.6313.172.4101417
    6258150141270.0730600.6671532902.6313.172.671012
    6257810141570.0730600.7381923542.6313.172.971012
    607529141570.0730600.7461923582.6313.172.971012
    6258070141970.0730600.7762434322.6313.173.171012
    607526142770.0730800.9683456342.6313.173.86911
    12 AWG
    607514012270.08830450.38640871.6622.0021.5202530
    60748412270.08830450.440901.6622.0021.6202530
    61993312370.08830450.412611151.6622.0021.6202530
    60751312470.08830450.461811471.6622.0021.8162024
    60752112970.08830600.6671833151.6622.0022.6141721
    622186121270.08830600.742444011.6622.0022.9101215
    6075140121570.08830800.8693055281.6622.0023.4101215
    10 AWG
    60751810270.11330450.448641201.041.2531.7303540
    60751210470.11330450.511292051.041.2532242832
    662067101270.11330800.8793886071.041.2533.5151720
    6222188270.14145600.5921022100.6530.7862.3405055
    6075198470.14145600.6962053490.6530.7862.7324044
    6075166270.17745600.6721632830.4110.4952.6556575
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on Table 310.15 (B)(16) of the NEC, 2017 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
    ^ UL Listed part number