SPEC 81252

35kV AL 133% TRXLPE One-Third Neutral LLDPE Primary UD

Single Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, One-third Concentric Neutral, Linear Low Density Polyethylene (LLDPE) Jacket. Silicone Free

...

Construction:

  1. Conductor:Class B compressed Aluminum ASTM 1350 ¾ hard H16/H26; Conductor moisture block (optional)
  2. Conductor Shield:Conventional Semi-conducting cross-linked copolymer; Supersmooth conductor shield optional; A conductor tape is used for cable size larger than or equal to 1500 Kcmil
  3. Insulation:420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Neutral:Helically applied soft drawn bare copper one-third concentric neutral
  6. Overall Jacket:Linear Low Density Polyethylene (LLDPE) Jacket, Black (red extruded stripes optional); PowerGlide® LLDPE jacket optional

Applications and Features:

Southwire's 35kV cables are suited for use in wet and dry areas, conduits, ducts, direct burial, sunlight, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation. 130°C for emergency overload, and 250°C for short circuit conditions. Jacket types available that can be installed in conduit without the aid of lubrication. Rated for 1000 lbs./FT maximum sidewall pressure.

Specifications:

  • ASTM B231 Standard Specification for Concentric-Lay-Stranded Aluminum 1350 Conductors
  • ASTM B609 Standard Specification for Aluminum 1350 Round Wire, Annealed and Intermediate Tempers, for Electrical Purposes
  • ICEA S-94-649 Standard for Concentric Neutral Cables Rated 5 - 46kV
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Rural Utility Standard RUS 1728F-U1 or 1728.204 (Electric standards and specifications for materials and construction)
  • UL 1072 Listed as MV 90 When Specified
  • Optional CSA 68.5: -40ºC and MV 90ºC optional marking available upon request
  • Sample Print Legend:

    SOUTHWIRE HI-DRI(R) [CONDUCTOR SIZE] [AWG or KCMIL] AL 35000 VOLTS TRXLPE INSULATION 420 MILS -- (NESC) -- SOUTHWIRE {MMM} {YYYY} NON-CONDUCTING JACKET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilinchinchmilinchNo. x AWGΩ/1000ftmilinchlb/1000ftinchlb
    6185894/0 (19)0.4981.3684201.47811x140.239751.760126914.11269
    TBA250 (37)0.5581.4444201.55413x140.202751.832152014.71500
    618590350 (37)0.6611.5414201.65118x140.146751.933164315.52100
    618591500 (37)0.7891.6694201.80916x120.103752.124207917.03000
    628573#750 (61)0.9681.8584201.99824x120.069752.313265918.54500
    616939750 (61)0.9681.8584201.99824x120.069752.313266018.54500
    618592750 (61)0.9681.8584201.99815x100.069752.355271818.84500
    6185931000 (61)1.1172.0074202.14720x100.052752.504325720.06000
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    # HiDri-Plus® - Water Blocking Powder
    § HiDri-Plus® - Water Blocking Powder. CSA Listed
    Table 2 – Electrical and Engineering Data
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftA/1000ftW/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    4/0 (19)0.0840.1050.0690.0510.1683.40.159 + j0.7300.105 + j0.0503836235285
    250 (37)0.0710.0900.0640.0490.1803.60.144 + j0.7260.090 + j0.0494533257
    350 (37)0.0500.0650.0570.0470.2014.10.119 + j0.7190.065 + j0.0476277315370
    500 (37)0.0350.0460.0510.0440.2274.60.100 + j0.7110.046 + j0.0458865380445
    750 (61)0.0240.0330.0440.0420.2615.30.087 + j0.7020.033 + j0.04213298470530
    750 (61)0.0240.0330.0440.0420.2615.30.087 + j0.7020.033 + j0.04213298470530
    750 (61)0.0240.0330.0440.0420.2615.30.087 + j0.7010.033 + j0.04213211470530
    1000 (61)0.0180.0260.0400.0400.2915.90.080 + j0.6950.026 + j0.04017615530585
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralNeutral DC Resistance 25°CJacket ThicknessApprox. ODApprox. WeightMin Bending RadiusMax Pull Tension*
    AWG/KcmilmmmmmmmmNo. x AWGΩ/kmmmmmkg/kmmmnewton
    6185894/0 (19)12.6534.7510.6737.5411x140.781.9144.701888358.145647
    TBA250 (37)14.1736.6810.6739.4713x140.661.9146.532262373.386675
    618590350 (37)16.7939.1410.6741.9418x140.481.9149.102445393.709345
    618591500 (37)20.0442.3910.6745.9516x120.341.9153.953094431.8013350
    628573#750 (61)24.5947.1910.6750.7524x120.231.9158.753957469.9020025
    616939750 (61)24.5947.1910.6750.7524x120.231.9158.753959469.9020025
    618592750 (61)24.5947.1910.6750.7515x100.231.9159.824045477.5220025
    6185931000 (61)28.3750.9810.6754.5320x100.171.9163.604847508.0026700
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Pulling tension based on pulling eye directly connected to conductor
    # HiDri-Plus® - Water Blocking Powder
    § HiDri-Plus® - Water Blocking Powder. CSA Listed
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzCharging CurrentDielectric LossZero Sequence Impedance*Positive Sequence Impedance*Short Circuit Current @ 30 CycleAllowable Ampacity in Duct 90°C†Allowable Ampacity Directly Buried 90°C‡
    AWG/KcmilΩ/kmΩ/kmMΩ*kmΩ/kmA/kmW/kmΩ/1000ftΩ/1000ftAmpAmpAmp
    4/0 (19)0.27560.340.02100.16730.55111.15490.159 + j0.7300.105 + j0.0503836235285
    250 (37)0.23290.300.01950.16080.59111.81100.144 + j0.7260.090 + j0.0494533257
    350 (37)0.16400.210.01740.15420.65913.45140.119 + j0.7190.065 + j0.0476277315370
    500 (37)0.11480.150.01550.14440.74515.09190.100 + j0.7110.046 + j0.0458865380445
    750 (61)0.07870.110.01340.13780.85617.38850.087 + j0.7020.033 + j0.04213298470530
    750 (61)0.07870.110.01340.13780.85617.38850.087 + j0.7020.033 + j0.04213298470530
    750 (61)0.07870.110.01340.13780.85617.38850.087 + j0.7010.033 + j0.04213211470530
    1000 (61)0.05910.090.01220.13120.95519.35700.080 + j0.6950.026 + j0.04017615530585
    *Ampacities for Direct Buried are based on ICEA P-117-734-2016 Single-Conductor Solid Dielectric 15-35kV. Single Circuit Flat Direct Buried Figure 3
    *Ampacities for Duct are based on ICEA P-117-734-2016 for Single-Conductor Solid Dielectric 15-35kV. Single Circuit Trefoil Conduit Figure 7.
    *Sequence Impedance values are based on Rho Earth Resistivity: 100 Ohm-Meter/1000ft.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:40 p.m. UTC