SPEC 26626
HVTECK AL 1/C 420NLEPR CB PVC AIA PVC 35kV 133% CSA
Single Conductor, 420 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:420 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 420 NLEPR AIA 35kV 133% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft |
1/0 | 19 | 0.336 | 1.214 | 420 | 1.274 | 7 x 14 | 80 | 1.924 | 60 | 2.044 | 1668 |
2/0 | 19 | 0.376 | 1.254 | 420 | 1.314 | 11 x 14 | 80 | 1.964 | 60 | 2.084 | 1800 |
3/0 | 19 | 0.422 | 1.300 | 420 | 1.360 | 11 x 14 | 110 | 2.070 | 60 | 2.190 | 2010 |
4/0 | 19 | 0.474 | 1.352 | 420 | 1.412 | 11 x 14 | 110 | 2.122 | 60 | 2.242 | 2120 |
250 | 37 | 0.520 | 1.406 | 420 | 1.466 | 13 x 14 | 110 | 2.176 | 60 | 2.296 | 2260 |
350 | 37 | 0.615 | 1.501 | 420 | 1.561 | 17 x 14 | 110 | 2.271 | 75 | 2.421 | 2607 |
500 | 37 | 0.735 | 1.621 | 420 | 1.681 | 21 x 14 | 110 | 2.391 | 75 | 2.541 | 2969 |
750 | 61 | 0.908 | 1.804 | 420 | 1.864 | 17 x 12 | 110 | 2.608 | 75 | 2.758 | 3555 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ/1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1/0 | 14.3 | 633 | 0.168 | 0.211 | 0.067 | 0.063 | 0.193 + j0.038 | 0.199 + j0.046 | 5458 | 221 | 219 |
2/0 | 14.5 | 798 | 0.133 | 0.167 | 0.062 | 0.061 | 0.149 + j0.036 | 0.155 + j0.044 | 8577 | 253 | 246 |
3/0 | 15.3 | 1006 | 0.105 | 0.133 | 0.058 | 0.060 | 0.115 + j0.034 | 0.121 + j0.042 | 8577 | 288 | 275 |
4/0 | 15.6 | 1269 | 0.084 | 0.105 | 0.054 | 0.057 | 0.087 + j0.032 | 0.093 + j0.04 | 8577 | 327 | 305 |
250 | 16 | 1500 | 0.071 | 0.090 | 0.051 | 0.056 | 0.072 + j0.031 | 0.078 + j0.039 | 10137 | 367 | 343 |
350 | 16.9 | 2100 | 0.050 | 0.065 | 0.046 | 0.053 | 0.047 + j0.028 | 0.053 + j0.036 | 13256 | 443 | 399 |
500 | 17.7 | 3000 | 0.035 | 0.046 | 0.041 | 0.050 | 0.028 + j0.026 | 0.035 + j0.034 | 16376 | 529 | 451 |
750 | 19.3 | 4500 | 0.024 | 0.033 | 0.035 | 0.047 | 0.015 + j0.023 | 0.022 + j0.032 | 21062 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Table 3 – Weights and Measurements (Metric)
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km |
1/0 | 19 | 8.53 | 30.84 | 10.67 | 32.36 | 7 x 14 | 2.03 | 48.87 | 1.52 | 51.92 | 2482 |
2/0 | 19 | 9.55 | 31.85 | 10.67 | 33.38 | 11 x 14 | 2.03 | 49.89 | 1.52 | 52.93 | 2679 |
3/0 | 19 | 10.72 | 33.02 | 10.67 | 34.54 | 11 x 14 | 2.79 | 52.58 | 1.52 | 55.63 | 2991 |
4/0 | 19 | 12.04 | 34.34 | 10.67 | 35.86 | 11 x 14 | 2.79 | 53.90 | 1.52 | 56.95 | 3155 |
250 | 37 | 13.21 | 35.71 | 10.67 | 37.24 | 13 x 14 | 2.79 | 55.27 | 1.52 | 58.32 | 3363 |
350 | 37 | 15.62 | 38.13 | 10.67 | 39.65 | 17 x 14 | 2.79 | 57.68 | 1.91 | 61.49 | 3880 |
500 | 37 | 18.67 | 41.17 | 10.67 | 42.70 | 21 x 14 | 2.79 | 60.73 | 1.91 | 64.54 | 4418 |
750 | 61 | 23.06 | 45.82 | 10.67 | 47.35 | 17 x 12 | 2.79 | 66.24 | 1.91 | 70.05 | 5290 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ/km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
1/0 | 363.22 | 2817 | 0.5512 | 0.69 | 0.0204 | 0.2067 | 0.193 + j0.038 | 0.199 + j0.046 | 5458 | 221 | 219 |
2/0 | 368.30 | 3551 | 0.4364 | 0.55 | 0.0189 | 0.2001 | 0.149 + j0.036 | 0.155 + j0.044 | 8577 | 253 | 246 |
3/0 | 388.62 | 4477 | 0.3445 | 0.44 | 0.0177 | 0.1969 | 0.115 + j0.034 | 0.121 + j0.042 | 8577 | 288 | 275 |
4/0 | 396.24 | 5647 | 0.2756 | 0.34 | 0.0165 | 0.1870 | 0.087 + j0.032 | 0.093 + j0.04 | 8577 | 327 | 305 |
250 | 406.40 | 6675 | 0.2329 | 0.30 | 0.0155 | 0.1837 | 0.072 + j0.031 | 0.078 + j0.039 | 10137 | 367 | 343 |
350 | 429.26 | 9345 | 0.1640 | 0.21 | 0.0140 | 0.1739 | 0.047 + j0.028 | 0.053 + j0.036 | 13256 | 443 | 399 |
500 | 449.58 | 13350 | 0.1148 | 0.15 | 0.0125 | 0.1640 | 0.028 + j0.026 | 0.035 + j0.034 | 16376 | 529 | 451 |
750 | 490.22 | 20025 | 0.0787 | 0.11 | 0.0107 | 0.1542 | 0.015 + j0.023 | 0.022 + j0.032 | 21062 | 633 | 505 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Revision: 1.000.000
Updated On: Aug. 18, 2023, 2:39 p.m. UTC