SPEC 26505

HVTECK CU 1/C 280NLEPR CB PVC AIA PVC 28kV 100% CSA

Single Conductor, 280 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:280 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
  6. Neutral Separator:Mylar tape
  7. Inner Jacket:PVC inner jacket
  8. Armour:Aluminum Interlocked Armour (AIA)
  9. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 280 NLEPR AIA 28kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchNo. x AWGmilinchmilinchlb/1000ft
    1190.3220.9202800.98011 x 14801.606601.7261350
    1/0190.3610.9592801.01911 x 14801.669601.7891489
    2/0190.4051.0032801.06311 x 14801.713601.8331618
    3/0190.4561.0542801.11413 x 14801.764601.8841804
    4/0190.5121.1102801.17013 x 14801.820601.9401996
    250370.5581.1642801.22417 x 14801.874601.9942316
    350370.6611.2672801.32721 x 14801.977602.0972790
    500370.7891.3952801.45526 x 141102.165602.2853582
    750610.9681.5842801.64421 x 121102.388752.5384752
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    112.06690.1280.1620.0540.0600.144 + j0.0350.15 + j0.0438577245244
    1/012.58440.1020.1280.0500.0580.11 + j0.0330.116 + j0.0418577278272
    2/012.810640.0810.1020.0470.0560.084 + j0.0310.09 + j0.0398577316303
    3/013.113420.0640.0810.0430.0540.063 + j0.030.069 + j0.03810137356333
    4/013.516920.0510.0650.0400.0520.047 + j0.0280.053 + j0.03610137403367
    25013.920000.0430.0560.0380.0510.038 + j0.0270.044 + j0.03513256455411
    35014.628000.0310.0410.0330.0480.023 + j0.0250.029 + j0.03316376537459
    50015.940000.0220.0300.0290.0460.012 + j0.0220.018 + j0.03120275616499
    75017.760000.0140.0230.0250.0440.005 + j0.0210.012 + j0.02926018716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldConcentric NeutralInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmNo. x AWGmmmmmmmmkg/km
    1198.1823.377.1124.8911 x 142.0340.791.5243.842009
    1/0199.1724.367.1125.8811 x 142.0342.391.5245.442216
    2/01910.2925.487.1127.0011 x 142.0343.511.5246.562408
    3/01911.5826.777.1128.3013 x 142.0344.811.5247.852685
    4/01913.0028.197.1129.7213 x 142.0346.231.5249.282970
    2503714.1729.577.1131.0917 x 142.0347.601.5250.653447
    3503716.7932.187.1133.7121 x 142.0350.221.5253.264152
    5003720.0435.437.1136.9626 x 142.7954.991.5258.045331
    7506124.5940.237.1141.7621 x 122.7960.661.9164.477072
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1304.8029770.41990.530.01650.19690.144 + j0.0350.15 + j0.0438577245244
    1/0317.5037560.33460.420.01520.19030.11 + j0.0330.116 + j0.0418577278272
    2/0325.1247350.26570.330.01430.18370.084 + j0.0310.09 + j0.0398577316303
    3/0332.7459720.21000.270.01310.17720.063 + j0.030.069 + j0.03810137356333
    4/0342.9075290.16730.210.01220.17060.047 + j0.0280.053 + j0.03610137403367
    250353.0689000.14110.180.01160.16730.038 + j0.0270.044 + j0.03513256455411
    350370.84124600.10170.130.01010.15750.023 + j0.0250.029 + j0.03316376537459
    500403.86178000.07220.100.00880.15090.012 + j0.0220.018 + j0.03120275616499
    750449.58267000.04590.080.00760.14440.005 + j0.0210.012 + j0.02926018716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC