SPEC 26502

HVTECK CU 1/C 345NLEPR TS PVC AIA PVC 28kV 133% CSA

Single Conductor, 345 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:345 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 28kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 345 NLEPR AIA 28kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    TBA1190.3221.0503451.110801.646601.7661443
    TBA1/0190.3611.0893451.149801.685601.8051557
    TBA2/0190.4051.1333451.193801.729601.8491693
    TBA3/0190.4561.1843451.244801.780601.9001861
    TBA4/0190.5121.2403451.300801.836601.9562062
    TBA250370.5581.2943451.354801.890602.0102340
    577263^350370.6611.3773451.437802.071602.1912837
    TBA500370.7891.5253451.5851102.181602.3013528
    TBA750610.9681.7143451.7741102.370752.5204630
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^Yellow outer jacket
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    112.36690.1280.1620.0610.0610.511 + j0.3250.163 + j0.0613439245244
    1/012.68440.1020.1280.0570.0590.474 + j0.3120.129 + j0.0593560278272
    2/012.910640.0810.1020.0530.0570.444 + j0.2980.103 + j0.0573696316303
    3/013.313420.0640.0810.0490.0550.419 + j0.2840.082 + j0.0553854356333
    4/013.616920.0510.0650.0460.0530.398 + j0.2690.066 + j0.0534027403367
    25014.020000.0430.0560.0430.0510.384 + j0.2560.057 + j0.0514195455411
    35015.328000.0310.0410.0390.0480.36 + j0.2330.042 + j0.0484514537459
    50016.140000.0220.0300.0340.0460.336 + j0.2090.031 + j0.0464910616499
    75017.660000.0140.0230.0290.0440.312 + j0.1790.024 + j0.0445496716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    TBA1198.1826.678.7628.192.0341.811.5244.862147
    TBA1/0199.1727.668.7629.182.0342.801.5245.852317
    TBA2/01910.2928.788.7630.302.0343.921.5246.962519
    TBA3/01911.5830.078.7631.602.0345.211.5248.262769
    TBA4/01913.0031.508.7633.022.0346.631.5249.683069
    TBA2503714.1732.878.7634.392.0348.011.5251.053482
    577263^3503716.7934.988.7636.502.0352.601.5255.654222
    TBA5003720.0438.738.7640.262.7955.401.5258.455250
    TBA7506124.5943.548.7645.062.7960.201.9164.016890
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    ^Yellow outer jacket
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1312.4229770.41990.530.01860.20010.511 + j0.3250.163 + j0.0613439245244
    1/0320.0437560.33460.420.01740.19360.474 + j0.3120.129 + j0.0593560278272
    2/0327.6647350.26570.330.01620.18700.444 + j0.2980.103 + j0.0573696316303
    3/0337.8259720.21000.270.01490.18040.419 + j0.2840.082 + j0.0553854356333
    4/0345.4475290.16730.210.01400.17390.398 + j0.2690.066 + j0.0534027403367
    250355.6089000.14110.180.01310.16730.384 + j0.2560.057 + j0.0514195455411
    350388.62124600.10170.130.01190.15750.36 + j0.2330.042 + j0.0484514537459
    500408.94178000.07220.100.01040.15090.336 + j0.2090.031 + j0.0464910616499
    750447.04267000.04590.080.00880.14440.312 + j0.1790.024 + j0.0445496716557
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC