SPEC 26401

HVTECK CU 1/C 260NLEPR TS PVC AIA PVC 25kV 100% CSA

Single Conductor, 260 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 100% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Conductor Shield:Semi-conducting cross-linked copolymer
  3. Insulation:260 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Black Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 25kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CU 260 NLEPR AIA 25kV 100% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    1190.3220.8802600.940801.452501.5521147
    1/0190.3610.9192600.979801.491501.5911254
    2/0190.4050.9632601.023801.535601.6551416
    3/0190.4561.0142601.074801.586601.7061576
    4/0190.5121.0702601.130801.666601.7861801
    250370.5581.1242601.184801.720601.8401979
    350370.6611.2272601.287801.823601.9432398
    500370.7891.3552601.415801.951602.0713091
    750610.9681.5442601.6041102.200602.3204209
    1000611.1171.6932601.7531102.349752.4995229
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ/1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    110.86690.1280.1620.0520.0580.521 + j0.3760.163 + j0.0582912245244
    1/011.18440.1020.1280.0480.0560.485 + j0.360.129 + j0.0563033278272
    2/011.510640.0810.1020.0450.0540.457 + j0.3440.103 + j0.0543169316303
    3/011.913420.0640.0810.0410.0520.432 + j0.3270.082 + j0.0523327356333
    4/012.516920.0510.0650.0380.0500.412 + j0.3090.066 + j0.0513501403367
    25012.820000.0430.0560.0360.0490.399 + j0.2930.057 + j0.0493668455411
    35013.628000.0310.0410.0320.0460.375 + j0.2660.042 + j0.0473987537459
    50014.440000.0220.0300.0280.0440.352 + j0.2360.031 + j0.0444384616499
    75016.260000.0140.0230.0240.0420.327 + j0.2010.024 + j0.0424969716557
    100017.480000.0110.0190.0210.0400.31 + j0.1790.02 + j0.045431825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Cond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    1198.1822.356.6023.882.0336.881.2739.421707
    1/0199.1723.346.6024.872.0337.871.2740.411866
    2/01910.2924.466.6025.982.0338.991.5242.042107
    3/01911.5825.766.6027.282.0340.281.5243.332345
    4/01913.0027.186.6028.702.0342.321.5245.362680
    2503714.1728.556.6030.072.0343.691.5246.742945
    3503716.7931.176.6032.692.0346.301.5249.353569
    5003720.0434.426.6035.942.0349.561.5252.604600
    7506124.5939.226.6040.742.7955.881.5258.936264
    10006128.3743.006.6044.532.7959.661.9163.477782
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    1 Comply with ICEA S-93-639 Appendix C for jacket thickness determination
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ/kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    1274.3229770.41990.530.01580.19030.521 + j0.3760.163 + j0.0582912245244
    1/0281.9437560.33460.420.01460.18370.485 + j0.360.129 + j0.0563033278272
    2/0292.1047350.26570.330.01370.17720.457 + j0.3440.103 + j0.0543169316303
    3/0302.2659720.21000.270.01250.17060.432 + j0.3270.082 + j0.0523327356333
    4/0317.5075290.16730.210.01160.16400.412 + j0.3090.066 + j0.0513501403367
    250325.1289000.14110.180.01100.16080.399 + j0.2930.057 + j0.0493668455411
    350345.44124600.10170.130.00980.15090.375 + j0.2660.042 + j0.0473987537459
    500365.76178000.07220.100.00850.14440.352 + j0.2360.031 + j0.0444384616499
    750411.48267000.04590.080.00730.13780.327 + j0.2010.024 + j0.0424969716557
    1000441.96356000.03610.060.00640.13120.31 + j0.1790.02 + j0.045431825608
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.

    Revision: 1.000.000

    Updated On: Aug. 18, 2023, 2:39 p.m. UTC