SPEC 26335
HVTECK AL 1/C 175TRXLPE CB PVC AIA PVC 15kV 100% CSA
Single Conductor, 175 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Red Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 175 TRXLPE AIA 15kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft |
2 | 7 | 0.268 | 0.656 | 175 | 0.716 | 7 x 14 | 80 | 1.342 | 50 | 1.442 | 786 |
1 | 19 | 0.298 | 0.686 | 175 | 0.746 | 7 x 14 | 80 | 1.372 | 50 | 1.472 | 825 |
1/0 | 19 | 0.336 | 0.724 | 175 | 0.784 | 7 x 14 | 80 | 1.410 | 50 | 1.510 | 877 |
2/0 | 19 | 0.376 | 0.764 | 175 | 0.824 | 11 x 14 | 80 | 1.450 | 50 | 1.550 | 988 |
3/0 | 19 | 0.422 | 0.810 | 175 | 0.870 | 11 x 14 | 80 | 1.496 | 50 | 1.596 | 1056 |
4/0 | 19 | 0.474 | 0.862 | 175 | 0.922 | 11 x 14 | 80 | 1.548 | 60 | 1.668 | 1171 |
250 | 37 | 0.520 | 0.916 | 175 | 0.976 | 13 x 14 | 80 | 1.602 | 60 | 1.722 | 1281 |
350 | 37 | 0.615 | 1.011 | 175 | 1.071 | 17 x 14 | 80 | 1.721 | 60 | 1.841 | 1541 |
500 | 37 | 0.735 | 1.131 | 175 | 1.191 | 21 x 14 | 80 | 1.841 | 60 | 1.961 | 1836 |
750 | 61 | 0.908 | 1.314 | 175 | 1.374 | 17 x 12 | 110 | 2.118 | 60 | 2.238 | 2541 |
1000 | 61 | 1.060 | 1.466 | 175 | 1.526 | 17 x 12 | 110 | 2.270 | 75 | 2.420 | 2993 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ/1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 10.0 | 398 | 0.267 | 0.336 | 0.060 | 0.060 | 0.318 + j0.033 | 0.323 + j0.04 | 5458 | 169 | 176 |
1 | 10.3 | 502 | 0.211 | 0.266 | 0.056 | 0.058 | 0.248 + j0.03 | 0.253 + j0.037 | 5458 | 194 | 198 |
1/0 | 10.5 | 633 | 0.168 | 0.211 | 0.052 | 0.056 | 0.193 + j0.028 | 0.198 + j0.036 | 5458 | 222 | 223 |
2/0 | 10.8 | 798 | 0.133 | 0.167 | 0.048 | 0.054 | 0.149 + j0.026 | 0.155 + j0.034 | 8577 | 255 | 250 |
3/0 | 11.1 | 1006 | 0.105 | 0.133 | 0.044 | 0.052 | 0.115 + j0.025 | 0.121 + j0.033 | 8577 | 290 | 278 |
4/0 | 11.6 | 1269 | 0.084 | 0.105 | 0.040 | 0.051 | 0.087 + j0.023 | 0.093 + j0.031 | 8577 | 329 | 309 |
250 | 12.0 | 1500 | 0.071 | 0.090 | 0.038 | 0.049 | 0.072 + j0.022 | 0.078 + j0.03 | 10137 | 370 | 347 |
350 | 12.8 | 2100 | 0.050 | 0.065 | 0.033 | 0.047 | 0.047 + j0.02 | 0.053 + j0.028 | 13256 | 446 | 402 |
500 | 13.7 | 3000 | 0.035 | 0.046 | 0.029 | 0.044 | 0.028 + j0.018 | 0.034 + j0.026 | 16376 | 533 | 451 |
750 | 15.6 | 4500 | 0.024 | 0.033 | 0.025 | 0.042 | 0.015 + j0.017 | 0.021 + j0.025 | 21062 | 631 | 500 |
1000 | 16.9 | 6000 | 0.018 | 0.026 | 0.022 | 0.041 | 0.008 + j0.016 | 0.014 + j0.024 | 21062 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Table 3 – Weights and Measurements (Metric)
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km |
2 | 7 | 6.81 | 16.66 | 4.44 | 18.19 | 7 x 14 | 2.03 | 34.09 | 1.27 | 36.63 | 1170 |
1 | 19 | 7.57 | 17.42 | 4.44 | 18.95 | 7 x 14 | 2.03 | 34.85 | 1.27 | 37.39 | 1228 |
1/0 | 19 | 8.53 | 18.39 | 4.44 | 19.91 | 7 x 14 | 2.03 | 35.81 | 1.27 | 38.35 | 1305 |
2/0 | 19 | 9.55 | 19.41 | 4.44 | 20.93 | 11 x 14 | 2.03 | 36.83 | 1.27 | 39.37 | 1470 |
3/0 | 19 | 10.72 | 20.57 | 4.44 | 22.10 | 11 x 14 | 2.03 | 38.00 | 1.27 | 40.54 | 1572 |
4/0 | 19 | 12.04 | 21.89 | 4.44 | 23.42 | 11 x 14 | 2.03 | 39.32 | 1.52 | 42.37 | 1743 |
250 | 37 | 13.21 | 23.27 | 4.44 | 24.79 | 13 x 14 | 2.03 | 40.69 | 1.52 | 43.74 | 1906 |
350 | 37 | 15.62 | 25.68 | 4.44 | 27.20 | 17 x 14 | 2.03 | 43.71 | 1.52 | 46.76 | 2293 |
500 | 37 | 18.67 | 28.73 | 4.44 | 30.25 | 21 x 14 | 2.03 | 46.76 | 1.52 | 49.81 | 2732 |
750 | 61 | 23.06 | 33.38 | 4.44 | 34.90 | 17 x 12 | 2.79 | 53.80 | 1.52 | 56.85 | 3781 |
1000 | 61 | 26.92 | 37.24 | 4.44 | 38.76 | 17 x 12 | 2.79 | 57.66 | 1.91 | 61.47 | 4454 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ/km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 254.00 | 1771 | 0.8760 | 1.10 | 0.0183 | 0.1969 | 0.318 + j0.033 | 0.323 + j0.04 | 5458 | 169 | 176 |
1 | 261.62 | 2234 | 0.6923 | 0.87 | 0.0171 | 0.1903 | 0.248 + j0.03 | 0.253 + j0.037 | 5458 | 194 | 198 |
1/0 | 266.70 | 2817 | 0.5512 | 0.69 | 0.0158 | 0.1837 | 0.193 + j0.028 | 0.198 + j0.036 | 5458 | 222 | 223 |
2/0 | 274.32 | 3551 | 0.4364 | 0.55 | 0.0146 | 0.1772 | 0.149 + j0.026 | 0.155 + j0.034 | 8577 | 255 | 250 |
3/0 | 281.94 | 4477 | 0.3445 | 0.44 | 0.0134 | 0.1706 | 0.115 + j0.025 | 0.121 + j0.033 | 8577 | 290 | 278 |
4/0 | 294.64 | 5647 | 0.2756 | 0.34 | 0.0122 | 0.1673 | 0.087 + j0.023 | 0.093 + j0.031 | 8577 | 329 | 309 |
250 | 304.80 | 6675 | 0.2329 | 0.30 | 0.0116 | 0.1608 | 0.072 + j0.022 | 0.078 + j0.03 | 10137 | 370 | 347 |
350 | 325.12 | 9345 | 0.1640 | 0.21 | 0.0101 | 0.1542 | 0.047 + j0.02 | 0.053 + j0.028 | 13256 | 446 | 402 |
500 | 347.98 | 13350 | 0.1148 | 0.15 | 0.0088 | 0.1444 | 0.028 + j0.018 | 0.034 + j0.026 | 16376 | 533 | 451 |
750 | 396.24 | 20025 | 0.0787 | 0.11 | 0.0076 | 0.1378 | 0.015 + j0.017 | 0.021 + j0.025 | 21062 | 631 | 500 |
1000 | 429.26 | 26700 | 0.0591 | 0.09 | 0.0067 | 0.1345 | 0.008 + j0.016 | 0.014 + j0.024 | 21062 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.