SPEC 26232

HVTECK AL 1/C 140TRXLPE TS PVC AIA PVC 8kV 133% CSA

Single Conductor, 140 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

...

Construction:

  1. Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
  2. Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
  3. Insulation:140 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
  4. Insulation Shield:Strippable semi-conducting cross-linked copolymer
  5. Copper Tape Shield:Helically wrapped 5 mil copper tape with 25% overlap
  6. Inner Jacket:PVC inner jacket
  7. Armour:Aluminum Interlocked Armour (AIA)
  8. Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire's 8kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.

Specifications:

  • ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • CSA C22.2 No. 174 Cables in Hazardous Locations
  • CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
  • CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
  • CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
  • CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
  • CSA HL - for Hazardous Locations rating
  • CSA SUN RES - for Sunlight Resistant rating
  • ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
  • ICEA T-29-520 Flame Test (210,000 BTU/Hr)
  • IEEE 383 Flame Test (70,000 btu)
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
  • FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
  • AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
  • Sample Print Legend:

    (CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 140 TRXLPE AIA 8kV 133% INS LEVEL 25% TS SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.inchinchmilinchmilinchmilinchlb/1000ft
    TBA270.2680.5861400.646651.018501.118585
    TBA1190.2980.6161400.676801.078501.178657
    TBA1/0190.3360.6541400.714801.116501.216709
    TBA2/0190.3760.6941400.754801.156501.256766
    TBA3/0190.4220.7401400.800801.202501.302837
    TBA4/0190.4740.7921400.852801.364501.464930
    TBA250370.5200.8461400.906801.418501.5181014
    TBA350370.6150.9411401.001801.513601.6331216
    672085500340.7351.0841401.144801.656601.7761479
    TBA750610.9081.2441401.304801.840601.9601890
    TBA1000611.0601.3961401.456801.992602.1122355
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 2 – Electrical and Engineering Data
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftMΩ*1000ftΩ/1000ftΩ/1000ftΩ/1000ftkAmpAmpAmp
    27.83980.2670.3360.0530.0550.693 + j0.4970.337 + j0.0542001169176
    18.25020.2110.2660.0490.0530.625 + j0.4790.267 + j0.0522094194198
    1/08.56330.1680.2110.0450.0510.572 + j0.460.212 + j0.052212222223
    2/08.77980.1330.1670.0410.0490.53 + j0.440.168 + j0.0482336255250
    3/09.110060.1050.1330.0380.0480.497 + j0.4190.134 + j0.0462478290278
    4/010.212690.0840.1050.0340.0480.467 + j0.3960.106 + j0.0462639329309
    25010.615000.0710.0900.0330.0460.45 + j0.3750.091 + j0.0452806370347
    35011.421000.0500.0650.0280.0440.421 + j0.3390.066 + j0.0433101446402
    50012.430000.0350.0460.0240.0420.394 + j0.3010.047 + j0.043473533451
    75013.745000.0240.0330.0210.0390.366 + j0.2530.034 + j0.0384040631500
    100014.760000.0180.0260.0180.0380.345 + j0.2210.027 + j0.0364511707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.
    Table 3 – Weights and Measurements (Metric)
    Stock NumberCond. SizeStrandDiameter Over ConductorDiameter Over InsulationInsul. ThicknessDiameter Over Insulation ShieldInner Jacket ThicknessDia. Over ArmourOverall Jacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo.mmmmmmmmmmmmmmmmkg/km
    TBA276.8114.883.5616.411.6525.861.2728.40871
    TBA1197.5715.653.5617.172.0327.381.2729.92978
    TBA1/0198.5316.613.5618.142.0328.351.2730.891055
    TBA2/0199.5517.633.5619.152.0329.361.2731.901140
    TBA3/01910.7218.803.5620.322.0330.531.2733.071246
    TBA4/01912.0420.123.5621.642.0334.651.2737.191384
    TBA2503713.2121.493.5623.012.0336.021.2738.561509
    TBA3503715.6223.903.5625.432.0338.431.5241.481810
    6720855003418.6727.533.5629.062.0342.061.5245.112201
    TBA7506123.0631.603.5633.122.0346.741.5249.782813
    TBA10006126.9235.463.5636.982.0350.601.5253.643505
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    Table 4 – Electrical and Engineering Data (Metric)
    Cond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CCapacitive Reactance @ 60HzInductive Reactance @ 60HzZero Sequence Impedance*Positive Sequence Impedance*Phase Short Circuit Current @ 60HzAllowable Ampacity In Air 90°CAllowable Ampacity Directly Buried 90°C
    AWG/KcmilmmnewtonΩ/kmΩ/kmMΩ*kmΩ/kmΩ/1000ftΩ/1000ftkAmpAmpAmp
    2198.1217710.87601.100.01620.18040.693 + j0.4970.337 + j0.0542001169176
    1208.2822340.69230.870.01490.17390.625 + j0.4790.267 + j0.0522094194198
    1/0215.9028170.55120.690.01370.16730.572 + j0.460.212 + j0.052212222223
    2/0220.9835510.43640.550.01250.16080.53 + j0.440.168 + j0.0482336255250
    3/0231.1444770.34450.440.01160.15750.497 + j0.4190.134 + j0.0462478290278
    4/0259.0856470.27560.340.01040.15750.467 + j0.3960.106 + j0.0462639329309
    250269.2466750.23290.300.01010.15090.45 + j0.3750.091 + j0.0452806370347
    350289.5693450.16400.210.00850.14440.421 + j0.3390.066 + j0.0433101446402
    500314.96133500.11480.150.00730.13780.394 + j0.3010.047 + j0.043473533451
    750347.98200250.07870.110.00640.12800.366 + j0.2530.034 + j0.0384040631500
    1000373.38267000.05910.090.00550.12470.345 + j0.2210.027 + j0.0364511707539
    * Inductive impedance is based on non-ferrous conduit with one diameter spacing.