SPEC 26135
HVTECK AL 1/C 90TRXLPE CB PVC AIA PVC 5kV 100% CSA
Single Conductor, 90 Mils Tree Retardant Cross Linked Polyethylene, 100% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Conductor Shield:Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
- Insulation:90 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
- Insulation Shield:Strippable semi-conducting cross-linked copolymer
- Concentric Shield:Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
- Neutral Separator:Mylar tape
- Inner Jacket:PVC inner jacket
- Armour:Aluminum Interlocked Armour (AIA)
- Overall Jacket:Orange Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire's 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Specifications:
Sample Print Legend:
(CSA) SOUTHWIRE (NESC) #P# 1/C [#AWG or #kcmil] CPT AL 90 TRXLPE AIA 5kV 100% INS LEVEL CB [No. x SIZE] AWG SUN RES 105°C FT4 HL (-40°C) LTGG RoHS YEAR [SEQUENTIAL METER MARKS]
Table 1 – Weights and Measurements
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | inch | inch | mil | inch | No. x AWG | mil | inch | mil | inch | lb/1000ft |
2 | 7 | 0.268 | 0.486 | 90 | 0.546 | 7 x 14 | 65 | 1.032 | 50 | 1.132 | 583 |
1 | 19 | 0.298 | 0.516 | 90 | 0.576 | 7 x 14 | 80 | 1.092 | 50 | 1.192 | 650 |
1/0 | 19 | 0.336 | 0.554 | 90 | 0.614 | 7 x 14 | 80 | 1.130 | 50 | 1.230 | 697 |
2/0 | 19 | 0.376 | 0.594 | 90 | 0.654 | 11 x 14 | 80 | 1.170 | 50 | 1.270 | 803 |
3/0 | 19 | 0.422 | 0.640 | 90 | 0.700 | 11 x 14 | 80 | 1.326 | 50 | 1.426 | 877 |
4/0 | 19 | 0.474 | 0.692 | 90 | 0.752 | 11 x 14 | 80 | 1.378 | 50 | 1.478 | 950 |
250 | 37 | 0.520 | 0.746 | 90 | 0.806 | 13 x 14 | 80 | 1.432 | 50 | 1.532 | 1052 |
350 | 37 | 0.615 | 0.841 | 90 | 0.901 | 17 x 14 | 80 | 1.527 | 60 | 1.647 | 1294 |
500 | 37 | 0.735 | 0.961 | 90 | 1.021 | 21 x 14 | 80 | 1.671 | 60 | 1.791 | 1604 |
750 | 61 | 0.908 | 1.144 | 90 | 1.204 | 17 x 12 | 80 | 1.888 | 60 | 2.008 | 2152 |
1000 | 61 | 1.060 | 1.296 | 90 | 1.356 | 17 x 12 | 110 | 2.100 | 60 | 2.220 | 2623 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 2 – Electrical and Engineering Data
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | MΩ*1000ft | Ω/1000ft | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 7.9 | 398 | 0.267 | 0.336 | 0.040 | 0.055 | 0.318 + j0.027 | 0.323 + j0.035 | 5458 | 169 | 176 |
1 | 8.3 | 502 | 0.211 | 0.266 | 0.037 | 0.053 | 0.248 + j0.025 | 0.253 + j0.032 | 5458 | 194 | 198 |
1/0 | 8.6 | 633 | 0.168 | 0.211 | 0.034 | 0.052 | 0.193 + j0.023 | 0.198 + j0.031 | 5458 | 222 | 223 |
2/0 | 8.8 | 798 | 0.133 | 0.167 | 0.031 | 0.050 | 0.149 + j0.022 | 0.155 + j0.03 | 8577 | 255 | 250 |
3/0 | 9.9 | 1006 | 0.105 | 0.133 | 0.028 | 0.050 | 0.115 + j0.02 | 0.12 + j0.028 | 8577 | 290 | 278 |
4/0 | 10.3 | 1269 | 0.084 | 0.105 | 0.025 | 0.048 | 0.087 + j0.019 | 0.092 + j0.027 | 8577 | 329 | 309 |
250 | 10.7 | 1500 | 0.071 | 0.090 | 0.024 | 0.047 | 0.072 + j0.018 | 0.077 + j0.026 | 10137 | 370 | 347 |
350 | 11.5 | 2100 | 0.050 | 0.065 | 0.021 | 0.044 | 0.047 + j0.017 | 0.053 + j0.025 | 13256 | 446 | 402 |
500 | 12.5 | 3000 | 0.035 | 0.046 | 0.018 | 0.042 | 0.028 + j0.015 | 0.034 + j0.023 | 16376 | 533 | 451 |
750 | 14.0 | 4500 | 0.024 | 0.033 | 0.015 | 0.040 | 0.015 + j0.014 | 0.021 + j0.022 | 21062 | 631 | 500 |
1000 | 15.5 | 6000 | 0.018 | 0.026 | 0.013 | 0.039 | 0.008 + j0.013 | 0.014 + j0.022 | 21062 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Table 3 – Weights and Measurements (Metric)
Cond. Size | Strand | Diameter Over Conductor | Diameter Over Insulation | Insul. Thickness | Diameter Over Insulation Shield | Concentric Neutral | Inner Jacket Thickness | Dia. Over Armour | Overall Jacket Thickness | Approx. OD | Approx. Weight |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | No. | mm | mm | mm | mm | No. x AWG | mm | mm | mm | mm | kg/km |
2 | 7 | 6.81 | 12.34 | 2.29 | 13.87 | 7 x 14 | 1.65 | 26.21 | 1.27 | 28.75 | 868 |
1 | 19 | 7.57 | 13.11 | 2.29 | 14.63 | 7 x 14 | 2.03 | 27.74 | 1.27 | 30.28 | 967 |
1/0 | 19 | 8.53 | 14.07 | 2.29 | 15.60 | 7 x 14 | 2.03 | 28.70 | 1.27 | 31.24 | 1037 |
2/0 | 19 | 9.55 | 15.09 | 2.29 | 16.61 | 11 x 14 | 2.03 | 29.72 | 1.27 | 32.26 | 1195 |
3/0 | 19 | 10.72 | 16.26 | 2.29 | 17.78 | 11 x 14 | 2.03 | 33.68 | 1.27 | 36.22 | 1305 |
4/0 | 19 | 12.04 | 17.58 | 2.29 | 19.10 | 11 x 14 | 2.03 | 35.00 | 1.27 | 37.54 | 1414 |
250 | 37 | 13.21 | 18.95 | 2.29 | 20.47 | 13 x 14 | 2.03 | 36.37 | 1.27 | 38.91 | 1566 |
350 | 37 | 15.62 | 21.36 | 2.29 | 22.89 | 17 x 14 | 2.03 | 38.79 | 1.52 | 41.83 | 1926 |
500 | 37 | 18.67 | 24.41 | 2.29 | 25.93 | 21 x 14 | 2.03 | 42.44 | 1.52 | 45.49 | 2387 |
750 | 61 | 23.06 | 29.06 | 2.29 | 30.58 | 17 x 12 | 2.03 | 47.96 | 1.52 | 51.00 | 3203 |
1000 | 61 | 26.92 | 32.92 | 2.29 | 34.44 | 17 x 12 | 2.79 | 53.34 | 1.52 | 56.39 | 3903 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
* Strand count meets minimum number per ASTM
Table 4 – Electrical and Engineering Data (Metric)
Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Capacitive Reactance @ 60Hz | Inductive Reactance @ 60Hz | Zero Sequence Impedance* | Positive Sequence Impedance* | Phase Short Circuit Current @ 60Hz | Allowable Ampacity In Air 90°C | Allowable Ampacity Directly Buried 90°C |
---|---|---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | mm | newton | Ω/km | Ω/km | MΩ*km | Ω/km | Ω/1000ft | Ω/1000ft | kAmp | Amp | Amp |
2 | 200.66 | 1771 | 0.8760 | 1.10 | 0.0122 | 0.1804 | 0.318 + j0.027 | 0.323 + j0.035 | 5458 | 169 | 176 |
1 | 210.82 | 2234 | 0.6923 | 0.87 | 0.0113 | 0.1739 | 0.248 + j0.025 | 0.253 + j0.032 | 5458 | 194 | 198 |
1/0 | 218.44 | 2817 | 0.5512 | 0.69 | 0.0104 | 0.1706 | 0.193 + j0.023 | 0.198 + j0.031 | 5458 | 222 | 223 |
2/0 | 223.52 | 3551 | 0.4364 | 0.55 | 0.0094 | 0.1640 | 0.149 + j0.022 | 0.155 + j0.03 | 8577 | 255 | 250 |
3/0 | 251.46 | 4477 | 0.3445 | 0.44 | 0.0085 | 0.1640 | 0.115 + j0.02 | 0.12 + j0.028 | 8577 | 290 | 278 |
4/0 | 261.62 | 5647 | 0.2756 | 0.34 | 0.0076 | 0.1575 | 0.087 + j0.019 | 0.092 + j0.027 | 8577 | 329 | 309 |
250 | 271.78 | 6675 | 0.2329 | 0.30 | 0.0073 | 0.1542 | 0.072 + j0.018 | 0.077 + j0.026 | 10137 | 370 | 347 |
350 | 292.10 | 9345 | 0.1640 | 0.21 | 0.0064 | 0.1444 | 0.047 + j0.017 | 0.053 + j0.025 | 13256 | 446 | 402 |
500 | 317.50 | 13350 | 0.1148 | 0.15 | 0.0055 | 0.1378 | 0.028 + j0.015 | 0.034 + j0.023 | 16376 | 533 | 451 |
750 | 355.60 | 20025 | 0.0787 | 0.11 | 0.0046 | 0.1312 | 0.015 + j0.014 | 0.021 + j0.022 | 21062 | 631 | 500 |
1000 | 393.70 | 26700 | 0.0591 | 0.09 | 0.0040 | 0.1280 | 0.008 + j0.013 | 0.014 + j0.022 | 21062 | 707 | 539 |
* Inductive impedance is based on non-ferrous conduit with one diameter spacing.
Revision: 1.000.000
Updated On: Aug. 18, 2023, 2:39 p.m. UTC