SPEC 70126

300V ROYAL® SJOOW Cord with Black Jacket 90°C. Silicone Free

300 Volt, 90°C Flexible Cord. Heat, Moisture and Oil Resistant EPDM Rubber Insulation and Sunlight, Heat, Moisture and Oil Resistant Flexible CPE Jacket

...

Construction:

  1. Conductor:Class K stranded bare copper per ASTM B-174
  2. Insulation:Heat, moisture and oil resistant EPDM
  3. Filler:Waxed paper fillers, with a tissue-paper separator wrapped around the assembly
  4. Jacket:Black Sunlight, Heat, Moisture and Oil Resistant Flexible CPE (Other colors available upon request)

Applications and Features:

Southwire Type SJOOW Flexible Cords UL/ CSA listed are permitted for use as specified by Article 400 and related articles of the 2014 National Electrical Code. The cable is rated -40°C to 90°C, water, oil, and weather resistant, designed for hard usage on industrial equipment, heavy tools, battery chargers, portable lights welding leads, marine dockside power, power extensions and mining applications.

Specifications:

  • UL 62 Flexible Cords and Cables
  • CSA C22.2 No. 49 Flexible Cords and Cables
  • Passes CSA FT2 Flame Test
  • RoHS-2 (European Directive 2011/65/EU)
  • NEC Article 400 Flexible Cords, Cables and Fixture Wire
  • NEC Article 501.140 Class I Division 2
  • Federal Specification J-C-580B
  • Sample Print Legend:

    SOUTHWIRE® ROYAL® CORD XX/C XX AWG (XXmm2) SJOOW E46194 (UL) 300V -40C TO 90C -- CSA LL90458 SJOOW 300V -40C TO 90C FT2 WATER RESISTANT

    Packaging:

    Standard lengths: 250', 500' and 1,000' reels. Other lengths available upon request.
    Table 1 – Weights and Measurements
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmilmilinchlb/1000ftAmp
    5579618232251824130400.2904410
    5581168232251821630400.2885110
    5581178233251831630400.3105910
    5581208234251841630400.333737
    5581188232261622630400.3135713
    5602548232261626530400.3256613
    5580858233261632630400.3327113
    5581198234261642630350.3608710
    5581218232271424130350.3366718
    5580868233271434130400.3619318
    5581238234271444130400.40012315
    5600158232281226530600.41510925
    5580878233281236530600.43414525
    5581248234281246530500.46717520
    55837882322910210445700.55517430
    55812582332910310445750.56923430
    55812682342910410445700.64029525
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Ampacities are based on TABLE 400.5(A)of the 2014 National Electrical Code and CEC Table 12.
    ** Not a Federal and Military Specification JC-580B
    ***No Fillers or Separator
    Table 2 – Weights and Measurements (Metric)
    Stock NumberCCI Part #Cond. SizeCond. NumberCond. StrandsInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightAmpacity *
    AWG/KcmilCount# x AWGmmmmmmkg/kmAmp
    557961823225182410.761.027.376510
    558116823225182160.761.027.327610
    558117823325183160.761.027.878810
    558120823425184160.761.028.461097
    558118823226162260.761.027.958513
    560254823226162650.761.028.259813
    558085823326163260.761.028.4310613
    558119823426164260.760.899.1412910
    558121823227142410.760.898.5310018
    558086823327143410.761.029.1713818
    558123823427144410.761.0210.1618315
    560015823228122650.761.5210.5416225
    558087823328123650.761.5211.0221625
    558124823428124650.761.2711.8626020
    5583788232291021041.141.7814.1025930
    5581258233291031041.141.9114.4534830
    5581268234291041041.141.7816.2643925

    Color Code

    # of ConductorColor Sequence
    2Black, White
    3Black, White, Green
    4Black, White, Red, Green

    Revision: 3.0.00M