SPEC 45502

CU 2000V XLPE Insulation. RHH/RHW-2

Power Cable 2000Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2

Applications and Features:

Southwire’s 2000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 4
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE E32071 MASTER-DESIGN {UL} XXX KCMIL (XXX{mm2}) CU TYPE RHH OR RHW-2 120 MILS XLP FOR CT USE SUN. RES. VW-1 2000 VOLTS {NOM}-ANCE
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODCopper WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    TBA870.141700.2815074
    TBA670.177700.31781109
    TBA470.225700.365128161
    TBA270.282700.422204244
    TBA1190.322900.502258318
    TBA1/0190.361900.541325391
    TBA2/0190.405900.585410482
    TBA3/0190.456900.636518598
    TBA4/0190.512900.692653741
    TBA250370.5581050.768771884
    TBA350370.6611050.87110811212
    568018500370.7891050.98615431748
    TBA600610.8651201.10518532046
    648750750610.9681201.22023152569
    TBA1000611.1171201.35730883330
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    TBA81.11320.6530.7860.052405055
    TBA61.22090.4110.4950.051556575
    TBA41.43330.2580.3100.048708595
    TBA21.65300.1620.1950.04595115130
    TBA12.06690.1280.1540.046110130145
    TBA1/02.18440.1020.1220.044125150170
    TBA2/02.310640.0810.0970.043145175195
    TBA3/02.513420.0640.0780.042165200225
    TBA4/02.716920.0510.0620.041195230260
    TBA2503.020000.0430.0530.041215255290
    TBA3503.428000.0310.0390.040260310350
    5680185003.940000.0220.0290.039320380430
    TBA6005.548000.0180.0250.039350420475
    6487507506.160000.0140.0220.038400475535
    TBA10006.780000.0110.0180.037455545615
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).

    Revision: 3.0.00C