SPEC 45410

AL 2000V XLPE Insulation. RHH/RHW-2 PV

Single Conductor Photovoltaic (Type PV) Power Cable 2000 Volt Aluminum Conductor XLPE Insulation. Sizes 6AWG through 1000 kcmil. Heat, Moisture, and Sunlight Resistant RoHS. 90°C

...

Construction:

  1. Conductor:AlumaFlex® Compact Stranded Aluminum Alloy (AA-8176)
  2. Insulation: Cross-linked Polyethylene (XLPE)

Applications and Features:

The cable is available in sizes 6 AWG through 1000 kcmil. The product is approved for use in solar power applications per the NEC article 690 and is rated 90°C for exposed or concealed wiring in wet or dry locations. Individual conductors are stranded aluminum alloy covered with a cross-linked polyethylene (XLPE) insulation and is rated for direct burial. The cable is sunlight resistant, oil resistant PRI and PRII, RoHS compliant, passes -40°C cold bend.

Specifications:

  • ASTM B836 Compact Rounded Stranded Aluminum Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 854 Service Entrance Cable
  • UL 4703 Standard for Photovoltaic Wire
  • Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
  • VW-1 Vertical-Wire Flame Test (Optional)
  • AA 8176 Stranded Aluminum Alloy Conductors
  • Sample Print Legend:

    SOUTHWIRE E316464 {UL} PV WIRE XXX KCMIL (XXX.XXX{mm2}) COMPACT AL. --- AlumaFlex® AA8176 2000V 90°C WET OR DRY -40°C SUN RES DIRECT BURIAL OR RHH-RHW-2 2000V --- RoHS {MMM/DD/YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessApprox. ODAluminum WeightApprox. Weight
    AWG/KcmilNo. of Strandsinchmilinchlb/1000ftlb/1000ft
    585843670.169850.3492459
    586673470.212850.3833977
    586672260.268850.43862104
    589171260.268850.43862104
    619879180.2981050.51978146
    589051180.2981050.51978146
    5912561/0100.3361050.54699164
    5912411/0100.3361050.54699164
    5836732/0120.3761050.586125195
    5771003/0160.4221050.633158235
    6695153/0160.4221050.633158235
    6695183/0160.4221050.633158235
    6695163/0160.4221050.633158235
    5778433/0160.4221050.633158235
    6695173/0160.4221050.633158235
    5836784/0190.4741050.685199284
    5912424/0190.4741050.685199284
    6074004/0190.4741050.685199284
    5976984/0190.4741050.685199284
    577101250220.5201200.760235350
    668535250220.5201200.760235350
    577844250220.5201200.760235350
    584290300210.5691200.810282397
    675225300210.5691200.810282397
    589170300210.5691200.810282397
    582174350350.6151200.856329462
    592618350350.6151200.856329462
    597996350350.6151200.856329462
    584291400350.6591200.899376518
    652801400350.6591200.899376518
    596689400350.6591200.899376518
    582267500340.7351200.978471615
    591243500340.7351200.978471615
    591246500340.7351200.978471615
    591244500340.7351200.978471615
    588797500340.7351200.978471615
    586671500340.7351200.978471615
    591245500340.7351200.978471615
    585499600370.8121351.083565745
    588799600370.8121351.083565745
    591247600370.8121351.083565745
    586013750610.9081351.178706904
    592619750610.9081351.178706904
    589375750610.9081351.178706904
    6413871000581.0601351.3309421168
    6413861000581.0601351.3309421168
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    * Strand count meets minimum number per ASTM
    TBA stock codes are estimations only and actual product may vary. Please wait until a stock code is assigned to purchase connectors and/or fittings.
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 75°CInductive Reactance @ 60HzAllowable Ampacity At 75°CAllowable Ampacity At 90°C
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmp
    58584361.41570.6740.8120.0515055
    58667341.52500.4240.5100.0486575
    58667221.83980.2670.3210.04590100
    58917121.83980.2670.3210.04590100
    61987912.15020.2110.2540.046100115
    58905112.15020.2110.2540.046100115
    5912561/02.26330.1680.2010.044120135
    5912411/02.26330.1680.2010.044120135
    5836732/02.37980.1330.1600.043135150
    5771003/02.510060.1050.1260.042155175
    6695153/02.510060.1050.1260.042155175
    6695183/02.510060.1050.1260.042155175
    6695163/02.510060.1050.1260.042155175
    5778433/02.510060.1050.1260.042155175
    6695173/02.510060.1050.1260.042155175
    5836784/02.712690.0840.1000.041180205
    5912424/02.712690.0840.1000.041180205
    6074004/02.712690.0840.1000.041180205
    5976984/02.712690.0840.1000.041180205
    5771012503.015000.0710.0860.041205230
    6685352503.015000.0710.0860.041205230
    5778442503.015000.0710.0860.041205230
    5842903003.218000.0590.0710.041230260
    6752253003.218000.0590.0710.041230260
    5891703003.218000.0590.0710.041230260
    5821743503.421000.0500.0620.040250280
    5926183503.421000.0500.0620.040250280
    5979963503.421000.0500.0620.040250280
    5842914003.624000.0440.0540.040270305
    6528014003.624000.0440.0540.040270305
    5966894003.624000.0440.0540.040270305
    5822675003.930000.0350.0440.039310350
    5912435003.930000.0350.0440.039310350
    5912465003.930000.0350.0440.039310350
    5912445003.930000.0350.0440.039310350
    5887975003.930000.0350.0440.039310350
    5866715003.930000.0350.0440.039310350
    5912455003.930000.0350.0440.039310350
    5854996005.436000.0290.0370.039340385
    5887996005.436000.0290.0370.039340385
    5912476005.436000.0290.0370.039340385
    5860137505.945000.0240.0310.038385435
    5926197505.945000.0240.0310.038385435
    5893757505.945000.0240.0310.038385435
    64138710006.760000.0180.0250.037445500
    64138610006.760000.0180.0250.037445500
    * Ampacities based upon 2023 NEC Table 310.16. See NEC sections 310.15 and 110.14(C) for additional requirements.
    * Inductive Reactance is based on non-ferrous conduit with one diameter spacing center-to-center.

    Stock Codes and Colors

    SizeBlackBrownOrangeYellowWhiteRedGreen
    AWG/KcmilBlackBrownOrangeYellowWhiteRedGreen
    6585843
    4586673
    2586672589171
    1619879589051
    1/0591256591241
    2/0583673
    3/0577100669515669516669517577843669518
    4/0583678597698607400591242
    250577101577844668535
    300584290589170675225
    350582174597996592618
    400584291596689652801
    500582267591243591244591245586671588797591246
    600585499591247588799
    750586013589375592619
    1000641387641386