SPEC 45052
CU 600V XLPE Insulation PVC Jacket. XHHW-2
Type TC-ER Control Cable 600 or 1000 Volt Copper Conductors, Cross Linked Polyethylene (XLPE) Insulation XHHW-2 Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone free. VW-1 Rated

Construction:
- Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) XHHW-2, 30 Mils thick for all cable sizes. VW-1 Rated
- Filler:Polypropylene filler on cables with 5 or less conductors
- Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
- Overall Jacket:Polyvinyl Chloride (PVC) Jacket
Applications and Features:
Southwire’s 600 or 1000 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. The jacket acts as gas/vapor-tight polymeric sheath that is extruded over the core per Sections 501.15(D) and 501.15(E) of the NEC, however when these cables are used in a hazardous location, they may need to be sealed further as described in more detail in the NEC. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. VW-1 Rated.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} (UL) XX AWG (X.XXmm2) CU 3/C TYPE TC-ER XHHW-2 CDRS 90(D)C JACKET SUNLIGHT RESISTANT DIRECT BURIAL FT4/IEEE1202 600V or 1000V NOM-ANCE XHHW-2 CT SR 600V 90(D)C
Table 1 – Physical and Electrical Data
Stock Number | Cond. Size | Cond. Number | Cond. Strands | Diameter Over Cond. | Insul. Thickness | Jacket Thickness | Approx. OD | Copper Weight | Approx. Weight | DC Resistance @ 25°C | AC Resistance @ 90°C | Min Bending Radius | Allowable Ampacity At 60°C * | Allowable Ampacity 75°C * | Allowable Ampacity 90°C * | ||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
AWG | No. | strands | inch | mil | mil | inch | lb/1000ft | lb/1000ft | Ω/1000ft | Ω/1000ft | inch | Amp | Amp | Amp | |||||
14 AWG | |||||||||||||||||||
952459◊ | 14 | 2 | 7 | 0.070 | 30 | 45 | 0.355 | 25 | 66 | 2.631 | 3.170 | 1.4 | 15 | 20 | 25 | ||||
952465◊ | 14 | 3 | 7 | 0.070 | 30 | 45 | 0.376 | 38 | 90 | 2.631 | 3.170 | 1.5 | 15 | 20 | 25 | ||||
952473◊ | 14 | 4 | 7 | 0.070 | 30 | 45 | 0.409 | 51 | 109 | 2.631 | 3.170 | 1.6 | 12 | 16 | 20 | ||||
952481◊ | 14 | 5 | 7 | 0.070 | 30 | 45 | 0.447 | 64 | 129 | 2.631 | 3.170 | 1.7 | 12 | 16 | 20 | ||||
952440◊ | 14 | 7 | 7 | 0.070 | 30 | 45 | 0.482 | 89 | 168 | 2.631 | 3.170 | 1.9 | 10 | 14 | 17 | ||||
952499 | 14 | 6 | 7 | 0.070 | 30 | 45 | 0.486 | 76 | 151 | 2.631 | 3.170 | 1.9 | 12 | 16 | 20 | ||||
952507 | 14 | 8 | 7 | 0.070 | 30 | 60 | 0.559 | 102 | 208 | 2.631 | 3.170 | 2.2 | 10 | 14 | 17 | ||||
952572◊ | 14 | 9 | 7 | 0.070 | 30 | 60 | 0.598 | 114 | 231 | 2.631 | 3.170 | 2.3 | 10 | 14 | 17 | ||||
952598◊ | 14 | 12 | 7 | 0.070 | 30 | 60 | 0.670 | 153 | 295 | 2.631 | 3.170 | 2.6 | 7 | 10 | 12 | ||||
952606◊ | 14 | 15 | 7 | 0.070 | 30 | 60 | 0.742 | 191 | 358 | 2.631 | 3.170 | 2.9 | 7 | 10 | 12 | ||||
952614◊ | 14 | 19 | 7 | 0.070 | 30 | 60 | 0.780 | 242 | 439 | 2.631 | 3.170 | 3.1 | 7 | 10 | 12 | ||||
952622 | 14 | 20 | 7 | 0.070 | 30 | 60 | 0.820 | 255 | 462 | 2.631 | 3.170 | 3.2 | 7 | 10 | 12 | ||||
952630◊ | 14 | 25 | 7 | 0.070 | 30 | 80 | 0.952 | 319 | 602 | 2.631 | 3.170 | 3.8 | 6 | 9 | 11 | ||||
952648 | 14 | 30 | 7 | 0.070 | 30 | 80 | 1.006 | 386 | 707 | 2.631 | 3.170 | 5.0 | 6 | 9 | 11 | ||||
952655◊ | 14 | 37 | 7 | 0.070 | 30 | 80 | 1.083 | 474 | 849 | 2.631 | 3.170 | 5.4 | 6 | 8 | 10 | ||||
12 AWG | |||||||||||||||||||
953042◊ | 12 | 2 | 7 | 0.088 | 30 | 45 | 0.388 | 40 | 88 | 1.662 | 2.002 | 1.5 | 20 | 25 | 30 | ||||
953059◊ | 12 | 3 | 7 | 0.088 | 30 | 45 | 0.408 | 61 | 117 | 1.662 | 2.002 | 1.6 | 20 | 25 | 30 | ||||
953067◊ | 12 | 4 | 7 | 0.088 | 30 | 45 | 0.449 | 81 | 152 | 1.662 | 2.002 | 1.7 | 16 | 20 | 24 | ||||
953075◊ | 12 | 5 | 7 | 0.088 | 30 | 45 | 0.487 | 101 | 174 | 1.662 | 2.002 | 1.9 | 16 | 20 | 24 | ||||
953091◊ | 12 | 7 | 7 | 0.088 | 30 | 60 | 0.561 | 142 | 248 | 1.662 | 2.002 | 2.2 | 14 | 17 | 21 | ||||
953109 | 12 | 8 | 7 | 0.088 | 30 | 60 | 0.607 | 162 | 279 | 1.662 | 2.002 | 2.4 | 14 | 17 | 21 | ||||
953117◊ | 12 | 9 | 7 | 0.088 | 30 | 60 | 0.657 | 182 | 315 | 1.662 | 2.002 | 2.6 | 14 | 17 | 21 | ||||
953125 | 12 | 10 | 7 | 0.088 | 30 | 60 | 0.714 | 202 | 349 | 1.662 | 2.002 | 2.8 | 10 | 12 | 15 | ||||
953133◊ | 12 | 12 | 7 | 0.088 | 30 | 60 | 0.738 | 243 | 404 | 1.662 | 2.002 | 2.9 | 10 | 12 | 15 | ||||
953141 | 12 | 15 | 7 | 0.088 | 30 | 60 | 0.819 | 303 | 496 | 1.662 | 2.002 | 3.2 | 10 | 12 | 15 | ||||
953158◊ | 12 | 19 | 7 | 0.088 | 30 | 80 | 0.904 | 385 | 647 | 1.662 | 2.002 | 3.6 | 10 | 12 | 15 | ||||
953174◊ | 12 | 25 | 7 | 0.088 | 30 | 80 | 1.051 | 511 | 835 | 1.662 | 2.002 | 5.2 | 9 | 11 | 13 | ||||
TBA | 12 | 37 | 7 | 0.088 | 30 | 80 | 1.198 | 753 | 1181 | 1.662 | 2.002 | 5.9 | 8 | 10 | 12 | ||||
10 AWG | |||||||||||||||||||
952861◊ | 10 | 2 | 7 | 0.113 | 30 | 45 | 0.436 | 64 | 119 | 1.040 | 1.253 | 1.7 | 30 | 35 | 40 | ||||
952879◊ | 10 | 3 | 7 | 0.113 | 30 | 45 | 0.459 | 97 | 163 | 1.040 | 1.253 | 1.8 | 30 | 35 | 40 | ||||
952895◊ | 10 | 4 | 7 | 0.113 | 30 | 45 | 0.502 | 129 | 210 | 1.040 | 1.253 | 2.0 | 24 | 28 | 32 | ||||
952887◊ | 10 | 5 | 7 | 0.113 | 30 | 60 | 0.587 | 161 | 267 | 1.040 | 1.253 | 2.3 | 24 | 28 | 32 | ||||
952911◊ | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.639 | 226 | 354 | 1.040 | 1.253 | 2.5 | 21 | 24 | 28 | ||||
TBA | 10 | 7 | 7 | 0.113 | 30 | 60 | 0.651 | 258 | 377 | 1.040 | 1.253 | 2.6 | 21 | 24 | 28 | ||||
952929 | 10 | 8 | 7 | 0.113 | 30 | 60 | 0.692 | 257 | 399 | 1.040 | 1.253 | 2.7 | 21 | 24 | 28 | ||||
952937◊ | 10 | 9 | 7 | 0.113 | 30 | 60 | 0.743 | 289 | 446 | 1.040 | 1.253 | 2.9 | 21 | 24 | 28 | ||||
952952◊ | 10 | 12 | 7 | 0.113 | 30 | 80 | 0.879 | 386 | 613 | 1.040 | 1.253 | 3.5 | 15 | 17 | 20 | ||||
952960 | 10 | 15 | 7 | 0.113 | 30 | 80 | 0.973 | 483 | 748 | 1.040 | 1.253 | 3.8 | 15 | 17 | 20 | ||||
952978 | 10 | 19 | 7 | 0.113 | 30 | 80 | 1.015 | 612 | 909 | 1.040 | 1.253 | 5.0 | 15 | 17 | 20 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F). Ampacities have been adjusted to article 240.4 (D) and Table 310.15 (B)(3) for more than 3 current carrying conductors