SPEC 45051

Multi-Conductor CU 600V PVC THHN or TFFN/TFN PVC Control Cable. Silicone Free

Type TC-ER Control Cable 600Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation THHN or TFFN/TFN Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free. VW-1 Rated.

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8 for 14, 12, and 10 AWG cables. Class K bare copper per ASTM B3 and B174 for 16 AWG (26 strands) and 18 AWG (16 strands) cables
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer 19 Mils thick for 18, 16, 14, 12 AWG cables and 24 Mils for 10 AWG cables, Type TFFN/TFN for 16 AWG cable and Type THHN or THWN for 14, 12 , 10 AWG cables. Types THHN or THWN are VW-1 Rated
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Silicone Free. Types THHN or THWN are VW-1 Rated.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XX AWG (X.XX{mm2}) CU XX CDRS TYPE TC-ER THHN OR THWN CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE

    Stock No: 408633
    SOUTHWIRE{R} MASTER-DESIGN E75755 {UL} 14 AWG (2.08{mm2}) CU 7 CDRS TYPE TC-ER-JP THHN OR THWN CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberCond. StrandsDiameter Over Cond.Insul. ThicknessJacket ThicknessApprox. ODCopper WeightApprox. WeightDC Resistance @ 25°CAC Resistance @ 90°CMin Bending RadiusAllowable Ampacity At 60°C *Allowable Ampacity 75°C *Allowable Ampacity 90°C *
    AWGNo.strandsinchmilmilinchlb/1000ftlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    57787918270.04520450.26810356.6698.0351.00018
    65218818370.04520450.28015456.6698.0351.10018
    65219118570.04520450.33625666.6698.0351.30014
    65219418670.04520450.35830746.6698.0351.40014
    65219718870.04520450.38540936.6698.0351.50012
    652200181070.04520450.438501406.6698.0351.7009
    652203181270.04520450.454601556.6698.0351.8009
    652215181670.04520450.508801656.6698.0352.0009
    652209181970.04520600.560952056.6698.0352.2009
    652212182470.04520600.6541212566.6698.0352.6008
    5778781840.04621450.30420546.6698.6761.2555
    16 AWG
    60484316270.05620450.29216444.1815.0371.10018
    60485016370.05620450.30824584.1815.0371.20018
    60486816470.05620450.33332704.1815.0371.30014
    60487616570.05620450.36240824.1815.0371.40014
    TBA16670.05620450.39048924.1815.0371.50014
    60489216770.05620450.393561084.1815.0371.50012
    TBA16870.05620450.419641164.1815.0371.60012
    60491816970.05620450.454721354.1815.0371.80012
    TBA161070.05620450.486801434.1815.0371.9009
    604942161270.05620450.510961754.1815.0372.0009
    604975161570.05620600.5951212274.1815.0372.3009
    605014161970.05620600.6251532734.1815.0372.5009
    TBA162070.05620600.6411602774.1815.0372.5009
    605071162570.05620600.7002013504.1815.0372.8008
    605121163070.05620600.7672444154.1815.0373.0008
    605196163770.05620600.8673005294.1815.0373.4007
    14 AWG
    40848414270.0720450.30525562.6313.1701.2152025
    40851814370.0720450.32238742.6313.1701.2152025
    40854214470.0720450.35151942.6313.1701.4121620
    40857514570.0720450.380641092.6313.1701.5121620
    40863314770.0720450.412891462.6313.1701.6101417
    60883614670.0720450.416761302.6313.1701.6121620
    TBA14870.0720450.4661021622.6313.1701.8101417
    40874014970.0720450.4901151892.6313.1701.9101417
    605477141070.0720600.5561282222.6313.1702.271012
    408807141270.0720600.5731532562.6313.1702.271012
    412874141570.0720600.6321923122.6313.1702.571012
    412908141970.0720600.6642433812.6313.1702.671012
    608729142070.0720600.6972564012.6313.1702.771012
    552133142570.0720600.8023205072.6313.1703.26911
    557553143070.0720800.8173845972.6313.1703.26911
    552190143770.0720800.9494757592.6313.1703.76810
    12 AWG
    40846812270.08820450.34440771.6622.0021.3202530
    40852612370.08820450.364611071.6622.0021.4202530
    40855912470.08820450.406811521.6622.0021.6162024
    40858312570.08820450.4331011781.6622.0021.7162024
    40864112770.08820450.4711422321.6622.0021.8141721
    60873712670.08820450.4751221871.6622.0021.9162024
    TBA12870.08820450.5251622321.6622.0022.1141721
    40875712970.08820600.5801833281.6622.0022.3141721
    TBA121070.08820600.6442033071.6622.0022.5101215
    408815121270.08820600.6492444141.6622.0022.5101215
    622420121670.08820600.7233254691.6622.0022.8101215
    412882121570.08820600.7253054541.6622.0022.9101215
    412916121970.08820600.7623865521.6622.0023.0101215
    TBA122070.08820600.8114065651.6622.0023.2101215
    552166122570.08820800.9435097571.6622.0023.791113
    609180123070.08820800.9926108601.6622.0023.991113
    552224123770.08820801.06475510841.6622.0025.381012
    10 AWG
    40849210270.11325450.408641131.0401.2531.6303540
    40853410370.11325450.433971561.0401.2531.7303540
    40856710470.11325450.5051292041.0401.2532.0242832
    40859110570.11325600.5481612511.0401.2532.1242832
    40865810770.11325600.5972263681.0401.2532.3212428
    TBA10670.11325600.6211942931.0401.2532.4242832
    TBA10870.11325600.6712583751.0401.2532.6212428
    40876510970.11325600.6942914841.0401.2532.7212428
    408823101270.11325600.7813886291.0401.2533.1151720
    TBA101070.11325600.7843234641.0401.2533.1151720
    601658101570.11325800.9394857041.0401.2533.7151720
    601666101970.11325800.9636128811.0401.2533.8151720
    608802102070.11325801.0376469091.0401.2535.1151720
    608810102570.11325801.15080811181.0401.2535.7131518
    608828103070.11325801.21697013181.0401.2536.0131518
    TBA103770.11325801.313119615991.0401.2536.5121416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF). Ampacities have been adjusted for more than three current-carrying conductors based on Table 310.15(C) 1.
    2/C cables are not listed as TC-ER
    ^ Stock No: 408633 TYPE TC-ER-JP
    ! Ripcord under jacket

    Revision: 3.0.00C