SPEC 45051

CU 600V PVC-Nylon Insulation PVC Jacket THHN/THWN-2. Sunlight Resistant - For Direct Burial - Silicone Free

Type TC-ER Control Cable 600Volt Copper Conductors, Polyvinyl Chloride (PVC) with nylon layer Insulation THHN or TFFN/TFN Polyvinyl Chloride (PVC) Jacket, Control Cable Conductor Identification Method 1 Table 2. Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.

...

Construction:

  1. Conductor:7 strands class B compressed bare copper per ASTM B3 and ASTM B8 for 14, 12, and 10 AWG cables. Class K bare copper per ASTM B3 and B174 for 16 AWG (26 strands) and 18 AWG (16 strands) cables
  2. Insulation:Polyvinyl Chloride (PVC) with nylon layer. Type TFFN/TFN for 18 and 16 AWG cable. Type THHN or THWN-2 for 14, 12 , 10 AWG cables. Types THHN or THWN-2 are VW-1 Rated
  3. Filler:Polypropylene filler on cables with 5 or less conductors
  4. Binder:Polyester flat thread binder tape applied for cables with more than 5 conductors
  5. Overall Jacket:Polyvinyl Chloride (PVC) Jacket

Applications and Features:

Southwire’s 600 Volt Type TC-ER control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 75°C in wet locations and 90°C in dry locations, 105°C for emergency overload, and 150°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. Constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10. Sunlight Resistant - For Direct Burial - Silicone Free - VW-1 Rated.

Specifications:

  • ASTM B3 Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 66 Fixture Wire
  • UL 83 Thermoplastic Insulated Wires and Cables
  • UL 1277 Electrical Power and Control Tray Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
  • ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
  • Sample Print Legend:

    {SQFTG} SOUTHWIRE{R} MASTER-DESIGN {UL} XX AWG (X.XX{mm2}) CU XX CDRS TYPE TC-ER THHN OR THWN CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE

    Stock No: 408633
    SOUTHWIRE{R} MASTER-DESIGN E75755 {UL} 14 AWG (2.08{mm2}) CU 7 CDRS TYPE TC-ER-JP THHN OR THWN CDRS 90{D}C JACKET SUNLIGHT RESISTANT DIRECT BURIAL 600 VOLTS {NOM}-ANCE
    Table 1 – Physical and Electrical Data
    Stock NumberCond. SizeCond. NumberInsul. ThicknessJacket ThicknessApprox. ODApprox. WeightDC Resistance @ 25°CAC Resistance @ 75°CMin Bending RadiusAllowable Ampacity At 60°CAllowable Ampacity 75°CAllowable Ampacity 90°C
    AWGNo.milmilinchlb/1000ftΩ/1000ftΩ/1000ftinchAmpAmpAmp
    18 AWG
    57787918220450.268356.6698.0351.0--18
    65218818320450.280456.6698.0351.1--18
    57787818420450.304546.6698.6761.2--5
    65219118520450.336666.6698.0351.3--14
    65219418620450.358746.6698.0351.4--14
    65219718820450.385936.6698.0351.5--12
    652200181020450.4381406.6698.0351.7--9
    652203181220450.4541556.6698.0351.8--9
    652215181620450.5081656.6698.0352.0--9
    652209181920600.5602056.6698.0352.2--9
    652212182420600.6542566.6698.0352.6--8
    16 AWG
    60484316220450.292444.1815.0371.1--18
    60485016320450.308584.1815.0371.2--18
    60486816420450.333704.1815.0371.3--14
    60487616520450.362824.1815.0371.4--14
    TBA16620450.390924.1815.0371.5--14
    60489216720450.3931084.1815.0371.5--12
    TBA16820450.4191164.1815.0371.6--12
    60491816920450.4541354.1815.0371.8--12
    TBA161020450.4861434.1815.0371.9--9
    604942161220450.5101754.1815.0372.0--9
    604975161520600.5952274.1815.0372.3--9
    605014161920600.6252734.1815.0372.5--9
    TBA162020600.6412774.1815.0372.5--9
    605071162520600.7003504.1815.0372.8--8
    605121163020600.7674154.1815.0373.0--8
    605196163720600.8675294.1815.0373.4--7
    14 AWG
    40848414220450.305562.6313.1701.2152025
    40851814320450.322742.6313.1701.2152025
    40854214420450.351942.6313.1701.4121620
    40857514520450.3801092.6313.1701.5121620
    40863314720450.4121462.6313.1701.6101417
    60883614620450.4161302.6313.1701.6121620
    TBA14820450.4661622.6313.1701.8101417
    40874014920450.4901892.6313.1701.9101417
    605477141020600.5562222.6313.1702.271012
    408807141220600.5732562.6313.1702.271012
    412874141520600.6323122.6313.1702.571012
    412908141920600.6643812.6313.1702.671012
    608729142020600.6974012.6313.1702.771012
    552133142520600.8025072.6313.1703.26911
    557553143020800.8175972.6313.1703.26911
    552190143720800.9497592.6313.1703.76810
    12 AWG
    40846812220450.344771.6622.0021.3202530
    40852612320450.3641071.6622.0021.4202530
    40855912420450.4061521.6622.0021.6162024
    40858312520450.4331781.6622.0021.7162024
    40864112720450.4712321.6622.0021.8141721
    60873712620450.4751871.6622.0021.9162024
    TBA12820450.5252321.6622.0022.1141721
    40875712920600.5803281.6622.0022.3141721
    TBA121020600.6443071.6622.0022.5101215
    408815121220600.6494141.6622.0022.5101215
    622420121620600.7234691.6622.0022.8101215
    412882121520600.7254541.6622.0022.9101215
    412916121920600.7625521.6622.0023.0101215
    TBA122020600.8115651.6622.0023.2101215
    552166122520800.9437571.6622.0023.791113
    TBA123020800.9928601.6622.0023.991113
    552224123720801.06410841.6622.0025.381012
    10 AWG
    40849210225450.4081131.0401.2531.6303540
    40853410325450.4331561.0401.2531.7303540
    40856710425450.5052041.0401.2532.0242832
    40859110525600.5482511.0401.2532.1242832
    40865810725600.5973681.0401.2532.3212428
    TBA10625600.6212931.0401.2532.4242832
    TBA10825600.6713751.0401.2532.6212428
    40876510925600.6944841.0401.2532.7212428
    408823101225600.7816291.0401.2533.1151720
    TBA101025600.7844641.0401.2533.1151720
    601658101525800.9397041.0401.2533.7151720
    601666101925800.9638811.0401.2533.8151720
    TBA102025801.0379091.0401.2535.1151720
    TBA102525801.15011181.0401.2535.7131518
    TBA103025801.21613181.0401.2536.0131518
    TBA103725801.31315991.0401.2536.5121416
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    *Ampacities based upon 2023 NEC Table 310.16 and do not take into account the overcurrent protection limitations in NEC 240.4(D) of 15 Amps for 14 AWG CU, 20 Amps for 12 AWG CU, and 30 Amps for 10 AWG CU (independent of the conductor temperature rating and stranding if size is present in table). Also, see NEC sections 310.15 and 110.14(C) for additional requirements.
    *Ampacities have been adjusted for more than Three Current-Carrying Conductors.