SPEC 45008
1/C AL 600V XLPE RHH/RHW-2 USE-2 Power Cable
Power Cable 600Volt Single Conductor Aluminum, Cross Linked Polyethylene (XLPE) insulation RHH/RHW-2 USE-2

Construction:
- Conductor:Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
- Insulation:Cross Linked Polyethylene (XLPE) Type RHH/RHW-2 USE-2
Applications and Features:
Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.
Specifications:
Sample Print Legend:
SOUTHWIRE EXXXXX #P# (UL) [#AWG Or #kcmil] AL RHH/RHW-2 USE-2 XLPE 600V For CT USE SUN. RES. For DIRECT BURIAL FT4 VW-1YEAR (NESC) [SEQUENTIAL FEET MARKS]
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Aluminum Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
272799 | 6 | 7 | 0.169 | 60 | 0.295 | 24 | 46 |
272807 | 4 | 7 | 0.212 | 60 | 0.339 | 39 | 66 |
272823 | 2 | 7 | 0.268 | 60 | 0.394 | 62 | 93 |
272831 | 1 | 19 | 0.298 | 80 | 0.467 | 78 | 126 |
576142 | 1/0 | 19 | 0.336 | 80 | 0.504 | 99 | 165 |
272856 | 2/0 | 19 | 0.376 | 80 | 0.544 | 125 | 182 |
272864 | 3/0 | 19 | 0.422 | 80 | 0.591 | 158 | 221 |
575991 | 4/0 | 19 | 0.474 | 80 | 0.643 | 199 | 293 |
576787 | 250 | 35 | 0.520 | 95 | 0.720 | 235 | 357 |
575992 | 300 | 35 | 0.569 | 95 | 0.770 | 282 | 402 |
576137 | 350 | 35 | 0.615 | 95 | 0.816 | 329 | 471 |
272914 | 400 | 35 | 0.659 | 95 | 0.859 | 376 | 489 |
567324 | 500 | 35 | 0.735 | 95 | 0.936 | 471 | 630 |
576141 | 600 | 58 | 0.812 | 110 | 1.037 | 565 | 756 |
596530 | 700 | 58 | 0.877 | 110 | 1.157 | 659 | 924 |
576219 | 750 | 58 | 0.908 | 110 | 1.140 | 706 | 920 |
TBA | 900 | 58 | 0.999 | 110 | 1.219 | 847 | 1046 |
TBA | 1000 | 58 | 1.060 | 110 | 1.280 | 941 | 1151 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
272799 | 6 | 1.1 | 157 | 0.674 | 0.812 | 0.051 | 40 | 50 | 55 |
272807 | 4 | 1.3 | 250 | 0.424 | 0.510 | 0.048 | 55 | 65 | 75 |
272823 | 2 | 1.5 | 398 | 0.267 | 0.321 | 0.045 | 75 | 90 | 100 |
272831 | 1 | 1.8 | 502 | 0.211 | 0.254 | 0.046 | 85 | 100 | 115 |
576142 | 1/0 | 2.0 | 633 | 0.168 | 0.201 | 0.044 | 100 | 120 | 135 |
272856 | 2/0 | 2.1 | 798 | 0.133 | 0.160 | 0.043 | 115 | 135 | 150 |
272864 | 3/0 | 2.3 | 1006 | 0.105 | 0.126 | 0.042 | 130 | 155 | 175 |
575991 | 4/0 | 2.5 | 1269 | 0.084 | 0.100 | 0.041 | 150 | 180 | 205 |
576787 | 250 | 2.8 | 1500 | 0.071 | 0.086 | 0.041 | 170 | 205 | 230 |
575992 | 300 | 3.0 | 1800 | 0.059 | 0.071 | 0.041 | 195 | 230 | 260 |
576137 | 350 | 3.2 | 2100 | 0.050 | 0.062 | 0.040 | 210 | 250 | 280 |
272914 | 400 | 3.4 | 2400 | 0.044 | 0.054 | 0.040 | 225 | 270 | 305 |
567324 | 500 | 3.7 | 3000 | 0.035 | 0.044 | 0.039 | 260 | 310 | 350 |
576141 | 600 | 5.1 | 3600 | 0.029 | 0.037 | 0.039 | 285 | 340 | 385 |
596530 | 700 | 5.7 | 4200 | 0.025 | 0.033 | 0.038 | 315 | 375 | 425 |
576219 | 750 | 5.7 | 4500 | 0.024 | 0.031 | 0.038 | 320 | 385 | 435 |
TBA | 900 | 6.0 | 5400 | 0.020 | 0.027 | 0.037 | 355 | 425 | 480 |
TBA | 1000 | 6.4 | 6000 | 0.018 | 0.025 | 0.037 | 375 | 445 | 500 |
† Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
Revision: 3.0.00C