SPEC 45006

1/C CU 600V EPR RHH/RHW-2 USE-2 LSZH-TS Silicone-Free Power Cable

Power Cable 600Volt Single Conductor Copper, Ethylene Propylene Rubber (EPR) insulation RHH/RHW-2 USE-2 Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Jacket

...

Construction:

  1. Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
  2. Binder Tape:Mylar Tape
  3. Insulation:Ethylene Propylene Rubber (EPR) Type RHH/RHW-2 USE-2
  4. Overall Jacket:Thermoset SOLONON® Low Smoke Zero Halogen (LSZH-TS) Silicone-Free Jacket

Applications and Features:

Southwire’s 600 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502.

Specifications:

  • ASTM B3 Standard Specification for Soft or Annealed Copper Wire
  • ASTM B8 Concentric-Lay-Stranded Copper Conductors
  • UL 44 Thermoset-Insulated Wires and Cables
  • UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
  • ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
  • CT USE Sizes 1/0 AWG and Larger
  • Sample Print Legend:

    SOUTHWIRE {UL} XXX AWG CU TYPE RHH OR RHW-2 OR USE-2 XX MILS EPR XX MILS SOLONON{R} ST1 FOR CT USE SUN RES 600 VOLTS {YYYY} {SEQUENTIAL FOOTAGE MARKS} SEQ FEET
    Table 1 – Weights and Measurements
    Stock NumberCond. SizeStrand CountDiameter Over ConductorInsul. ThicknessJacket ThicknessApprox. ODApprox. Weight
    AWG/KcmilNo. of Strandsinchmilmilinchlb/1000ft
    890660870.14140150.26874
    890659670.17745300.338119
    555214470.22545300.375164
    551088270.28245300.438258
    5660101190.32255450.522338
    5615611/0190.36155450.575418
    5615602/0190.40555450.617511
    5817993/0190.45655450.669628
    5615564/0190.51255450.711770
    561554250370.55865650.817944
    561553350370.66165650.9161280
    890658500370.78965651.0411775
    566011600610.86580651.1672133
    551091750610.96880651.2752633
    5510921000611.11780651.4073387
    All dimensions are nominal and subject to normal manufacturing tolerances
    ◊ Cable marked with this symbol is a standard stock item
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).
    Table 2 – Electrical and Engineering Data
    Stock NumberCond. SizeMin Bending RadiusMax Pull TensionDC Resistance @ 25°CAC Resistance @ 90°CInductive Reactance @ 60HzAllowable Ampacity At 60°C†Allowable Ampacity At 75°C†Allowable Ampacity At 90°C†
    AWG/KcmilinchlbΩ/1000ftΩ/1000ftΩ/1000ftAmpAmpAmp
    89066081.01320.6530.7860.052405055
    89065961.32090.4110.4950.051556575
    55521441.53330.2580.3100.048708595
    55108821.75300.1620.1950.04595115130
    56601012.06690.1280.1540.046110130145
    5615611/02.38440.1020.1220.044125150170
    5615602/02.410640.0810.0970.043145175195
    5817993/02.613420.0640.0780.042165200225
    5615564/02.816920.0510.0620.041195230260
    5615542503.220000.0430.0530.041215255290
    5615533503.628000.0310.0390.040260310350
    8906585005.240000.0220.0290.039320380430
    5660116005.848000.0180.0250.039350420475
    5510917506.360000.0140.0220.038400475535
    55109210007.080000.0110.0180.037455545615
    † Ampacities are based on Table 310.16 of the NEC 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts with not more than three current-carrying conductors in raceway, cable or direct buried based on ambient temperature of 30ºC (86ºF).

    Revision: 3.0.00C