SPEC 45001
1/C CU 600 or 1000V XLPE-SIM XHHW-2 Power Cable. CT Rated 1/0 and Larger.
Power Cable 600 or 1000 Volt Single Conductor Copper, Cross Linked Polyethylene (XLPE) with Simpull technology insulation XHHW-2. FT4/IEEE 1202 350kcmil and larger.

Construction:
- Conductor:Class B compressed stranded bare copper per ASTM B3 and ASTM B8
- Insulation:Cross Linked Polyethylene (XLPE) with Simpull technology Type XHHW-2
Applications and Features:
Southwire’s 600 or 1000 Volt power cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. For uses in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. FT4/IEEE 1202 on 350kcmil and larger. Rated for 1000 lbs./FT maximum sidewall pressure.
Specifications:
Sample Print Legend:
{SQFTG} SOUTHWIRE{R} SIMpull XHHW-2{R} E30117 MASTER-DESIGN {UL} XXX AWG(XXX{mm2}) CU TYPE XHHW-2 SUN. RES. FOR CT USE GASOLINE AND OIL RESISTANT II 600V/1000V {NOM}-ANCE LS
Table 1 – Weights and Measurements
Stock Number | Cond. Size | Strand Count | Diameter Over Conductor | Insul. Thickness | Approx. OD | Copper Weight | Approx. Weight |
---|---|---|---|---|---|---|---|
AWG/Kcmil | No. of Strands | inch | mil | inch | lb/1000ft | lb/1000ft | |
553446◊ | 1/0 | 19 | 0.361 | 55 | 0.476 | 326 | 362 |
600510◊ | 2/0 | 19 | 0.405 | 55 | 0.520 | 410 | 451 |
557058◊ | 3/0 | 19 | 0.456 | 55 | 0.570 | 518 | 562 |
429712◊ | 4/0 | 19 | 0.512 | 55 | 0.614 | 653 | 702 |
557025◊ | 250 | 37 | 0.558 | 65 | 0.680 | 771 | 834 |
550871◊ | 350 | 37 | 0.661 | 65 | 0.779 | 1080 | 1153 |
557017◊ | 500 | 37 | 0.789 | 65 | 0.904 | 1543 | 1630 |
604579◊ | 600 | 61 | 0.865 | 80 | 1.034 | 1852 | 1969 |
551028◊ | 750 | 61 | 0.968 | 80 | 1.136 | 2315 | 2446 |
557488◊ | 1000 | 61 | 1.117 | 80 | 1.285 | 3087 | 3236 |
All dimensions are nominal and subject to normal manufacturing tolerances
◊ Cable marked with this symbol is a standard stock item
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Table 2 – Electrical and Engineering Data
Stock Number | Cond. Size | Min Bending Radius | Max Pull Tension | DC Resistance @ 25°C | AC Resistance @ 90°C | Inductive Reactance @ 60Hz | Allowable Ampacity At 60°C† | Allowable Ampacity At 75°C† | Allowable Ampacity At 90°C† |
---|---|---|---|---|---|---|---|---|---|
AWG/Kcmil | inch | lb | Ω/1000ft | Ω/1000ft | Ω/1000ft | Amp | Amp | Amp | |
553446◊ | 1/0 | 1.9 | 844 | 0.102 | 0.122 | 0.044 | 125 | 150 | 170 |
600510◊ | 2/0 | 2.0 | 1064 | 0.081 | 0.097 | 0.043 | 145 | 175 | 195 |
557058◊ | 3/0 | 2.2 | 1342 | 0.064 | 0.078 | 0.042 | 165 | 200 | 225 |
429712◊ | 4/0 | 2.4 | 1692 | 0.051 | 0.062 | 0.041 | 195 | 230 | 260 |
557025◊ | 250 | 2.7 | 2000 | 0.043 | 0.053 | 0.041 | 215 | 255 | 290 |
550871◊ | 350 | 3.1 | 2800 | 0.031 | 0.039 | 0.040 | 260 | 310 | 350 |
557017◊ | 500 | 3.6 | 4000 | 0.022 | 0.029 | 0.039 | 320 | 380 | 430 |
604579◊ | 600 | 5.1 | 4800 | 0.018 | 0.025 | 0.039 | 350 | 420 | 475 |
551028◊ | 750 | 5.6 | 6000 | 0.014 | 0.022 | 0.038 | 400 | 475 | 535 |
557488◊ | 1000 | 6.4 | 8000 | 0.011 | 0.018 | 0.037 | 455 | 545 | 615 |
† Ampacities are based on Table 310.16 of the NEC, 2020 Edition. Ampacities of insulated conductors rated up to and including 2000 Volts, based on ambient temperature of 30°C (86°F)
Revision: 3.0.00C