"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" "566994","1/0","1","10","0.336","420","1.214","1.274","80",1.454,"998","633","17.4","4.0" "590621","2/0","1","12","0.376","420","1.254","1.314","80",1.494,"1063","798","17.9","4.5" "566995","3/0","1","15","0.422","420","1.301","1.361","80",1.541,"1141","1006","18.4","4.5" "591197","4/0","1","19","0.474","420","1.353","1.413","80",1.593,"1233","1269","19.1","4.5" "591198","250","1","22","0.520","420","1.406","1.466","80",1.646,"1323","1500","19.7","5.0" "591199","350","1","35","0.615","420","1.502","1.562","110",1.802,"1611","2100","21.6","5.0" "578178","500","1","35","0.735","420","1.644","1.704","110",1.944,"1899","3000","23.3","5.5" TBA,"600","1","58","0.812","420","1.708","1.768","110",2.008,"2016","3600","24.0","6.0" "566996","750","1","58","0.908","420","1.816","1.876","110",2.126,"2339","4500","25.5","6.0" "597787","1000","1","58","1.060","420","1.968","2.028","110",2.278,"2722","6000","27.3" "677472","1250","1","91","1.250","420","2.171","2.231","110",2.471,"3174","7500","29.6" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "1/0","0.168","0.211","0.067","0.055","0.55 + j0.279","0.212 + j0.054","3978","155/165","200/225" "2/0","0.133","0.167","0.062","0.053","0.502 + j0.268","0.168 + j0.052","4102","175/190","230/260" "3/0","0.105","0.133","0.058","0.051","0.464 + j0.257","0.134 + j0.05","4244","200/215","270/300" "4/0","0.084","0.105","0.054","0.050","0.431 + j0.244","0.106 + j0.048","4405","230/245","310/345" "250","0.071","0.090","0.051","0.048","0.41 + j0.233","0.091 + j0.047","4573","250/270","345/380" "350","0.050","0.065","0.046","0.046","0.375 + j0.214","0.066 + j0.045","4867","305/330","430/475" "500","0.035","0.046","0.041","0.044","0.345 + j0.193","0.047 + j0.042","5239","370/400","530/590" "600","0.029","0.039","0.038","0.042","0.33 + j0.18","0.04 + j0.04","5508","404/436","592/660" "750","0.024","0.033","0.035","0.041","0.315 + j0.167","0.034 + j0.039","5806","455/490","685/765" "1000","0.018","0.026","0.031","0.039","0.295 + j0.15","0.027 + j0.038","6277","525/565","825/920" "1250","0.014","0.023","0.028","0.037","0.276 - j0.124","0.024 - j0.219","6878","595/640","950/1055"