"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Ground","Inner Jacket Thickness","Diameter Over Armor","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius" "","AWG/Kcmil","","","inches","mils","inches","inches","No. x AWG","mils","inch","mils","inches","lbs./MFT","lbs.","inches" TBA,"1/0","3","19","0.361","220","0.839","0.899","3x8","60","2.307","75",2.457,"3041","2534","17.1" TBA,"2/0","3","19","0.405","220","0.883","0.943","3x8","60","2.402","75",2.552,"3417","3194","17.8" TBA,"3/0","3","19","0.456","220","0.934","0.994","3x7","60","2.512","75",2.662,"3913","4027","18.6" TBA,"4/0","3","19","0.512","220","0.990","1.050","3x7","75","2.633","75",2.783,"4474","5078","19.4" TBA,"250","3","37","0.558","220","1.044","1.104","3x7","75","2.749","75",2.899,"4994","6000","20.2" TBA,"350","3","37","0.661","220","1.147","1.207","3x6","75","2.972","75",3.122,"6261","8400","21.8" "552046","500","3","37","0.789","220","1.252","1.312","3x1","75","3.475","85",3.645,"9544","12000","25.5" TBA,"750","3","61","0.968","220","1.464","1.524","3x4","85","3.657","90",3.837,"11181","18000","26.8" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "1/0","0.102","0.128","0.043","0.043","0.500 + j0.385","0.128 + j0.043","2816","195/210","215/240" "2/0","0.081","0.102","0.040","0.042","0.471 + j0.367","0.102 + j0.042","2952","220/235","245/275" "3/0","0.064","0.081","0.037","0.040","0.447 + j0.347","0.081 + j0.040","3110","250/270","285/315" "4/0","0.051","0.065","0.034","0.039","0.426 + j0.328","0.065 + j0.039","3284","285/305","325/360" "250","0.043","0.056","0.032","0.038","0.413 + j0.310","0.056 + j0.038","3451","310/335","360/400" "350","0.031","0.041","0.028","0.036","0.388 + j0.280","0.041 + j0.036","3770","375/400","435/490" "500","0.022","0.030","0.025","0.034","0.365 + j0.248","0.030 + j0.034","4167","450/485","535/600" "750","0.014","0.023","0.021","0.032","0.339 + j0.210","0.024 + j0.032","4752","545/585","670/745"