"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Ground","Diameter Over Armor","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius" "","AWG/Kcmil","","","inches","mils","inches","inches","No. x AWG","inch","mils","inches","lbs./MFT","lbs.","inches" "890663","2","3","7","0.282","220","0.755","0.815","1x6","2.290","85",2.460,"2674","1592","17.2" "890664","1/0","3","19","0.361","220","0.840","0.900","1x4","2.550","75",2.700,"3357","2534","18.9" "890665","2/0","3","19","0.405","220","0.884","0.944","1x4","2.550","75",2.700,"3639","3194","18.9" "890666","4/0","3","19","0.512","220","0.976","1.036","1x3","2.750","75",2.900,"4769","5078","20.3" "890667","250","3","37","0.558","220","1.028","1.088","1x2","2.880","75",3.030,"5332","6000","21.2" "890668","350","3","37","0.661","220","1.127","1.187","1x2","3.220","85",3.390,"7406","8400","23.7" "890669","500","3","37","0.789","220","1.252","1.312","1x1","3.540","85",3.710,"8900","12000","25.9" "591219","500","3","37","0.789","220","1.275","1.335","1x4/0","3.540","85",3.710,"9177","12000","25.9" "550439","750","3","58","0.968","220","1.404","1.464","1x1/0","3.850","85",4.020,"12407","18000","28.1" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.051","0.047","0.579 + j0.421","0.204 + j0.048","2571","150/160","165/185" "1/0","0.102","0.128","0.043","0.043","0.5 + j0.385","0.128 + j0.043","2816","195/210","215/240" "2/0","0.081","0.102","0.040","0.042","0.471 + j0.367","0.102 + j0.042","2952","220/235","245/275" "4/0","0.051","0.065","0.034","0.039","0.426 + j0.328","0.065 + j0.039","3284","285/305","325/360" "250","0.043","0.056","0.032","0.038","0.413 + j0.31","0.056 + j0.038","3451","310/335","360/400" "350","0.031","0.041","0.028","0.036","0.388 + j0.28","0.041 + j0.036","3770","375/400","435/490" "500","0.022","0.030","0.025","0.034","0.365 + j0.248","0.03 + j0.034","4167","450/485","535/600" "500","0.022","0.030","0.025","0.034","0.365 + j0.248","0.03 + j0.034","4167","450/485","535/600" "750","0.014","0.023","0.021","0.032","0.339 + j0.21","0.024 + j0.032","4752","545/585","670/745"