"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius","Conduit Size" "","AWG/Kcmil","","","inches","mils","inches","inches","mils","inches","lbs./MFT","lbs.","inches","inches" "673433","2","1","7","0.282","220","0.755","0.815","80",0.995,"604","530","11.9","3.0" "673432","1","1","19","0.322","220","0.800","0.860","80",1.040,"683","669","12.4","3.0" "673431","1/0","1","19","0.361","220","0.840","0.900","80",1.080,"774","844","12.9","3.0" "673430","2/0","1","19","0.405","220","0.884","0.944","80",1.124,"885","1064","13.4","3.5" "641179","2/0","1","19","0.405","220","0.884","0.944","80",1.124,"888","1064","13.4","3.5" "673429","3/0","1","19","0.456","220","0.934","0.994","80",1.174,"1021","1342","14.0","3.5" "673428","4/0","1","19","0.512","220","0.990","1.050","80",1.230,"1189","1692","14.7","3.5" "673427","250","1","37","0.558","220","1.044","1.104","80",1.284,"1342","2000","15.4","4.0" "673425","350","1","37","0.661","220","1.147","1.207","80",1.387,"1711","2800","16.6","4.0" "673415","500","1","37","0.789","220","1.252","1.312","80",1.492,"2237","4000","17.9","4.5" "669891","750","1","61","0.968","220","1.464","1.524","110",1.764,"3239","6000","21.1","5.0" TBA,"1000","1","61","1.117","220","1.613","1.673","110",1.913,"4143","8000","22.9","5.5" TBA,"1250","1","91","1.250","220","1.750","1.810","110",2.050,"5011","10000","24.6","6.0" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.162","0.204","0.067","0.051","0.575 + j0.42","0.204 + j0.052","2571","155/165","195/215" "1","0.128","0.162","0.061","0.049","0.532 + j0.401","0.162 + j0.049","2695","175/185","225/250" "1/0","0.102","0.128","0.057","0.047","0.496 + j0.384","0.128 + j0.047","2816","200/215","260/290" "2/0","0.081","0.102","0.053","0.045","0.468 + j0.367","0.103 + j0.045","2952","230/245","300/335" "2/0","0.081","0.102","0.053","0.045","0.468 + j0.367","0.103 + j0.045","2952","230/245","300/335" "3/0","0.064","0.081","0.048","0.043","0.444 + j0.347","0.082 + j0.044","3110","260/275","345/385" "4/0","0.051","0.065","0.044","0.042","0.424 + j0.328","0.066 + j0.042","3284","295/315","400/445" "250","0.043","0.056","0.042","0.041","0.41 + j0.31","0.057 + j0.041","3451","325/345","445/495" "350","0.031","0.041","0.037","0.039","0.386 + j0.281","0.042 + j0.039","3770","390/415","550/610" "500","0.022","0.030","0.032","0.037","0.363 + j0.249","0.031 + j0.037","4167","465/500","685/765" "750","0.014","0.023","0.028","0.035","0.337 + j0.211","0.024 + j0.035","4752","565/610","885/990" "1000","0.011","0.019","0.025","0.034","0.319 + j0.186","0.02 + j0.034","5214","640/690","1060/1185" "1250","0.009","0.018","0.022","0.033","0.305 - j0.089","0.019 - j0.223","5638","715/770","1210/1350"