"Table 1 - Weights and Measurements" "" "Stock Number","Cond. Size","Conductor Number","Conductor Stranding","Diameter Over Conductor","Insul. Thickness","Diameter Over Insulation","Diameter Over Insulation Shield","Ground","Jacket Thickness","Approx. OD","Approx. Weight","Max Pull Tension","Min Bending Radius" "","AWG/Kcmil","","","inches","mils","inches","inches","No. x AWG","mils","inches","lbs./MFT","lbs.","inches" "599065","2","3","7","0.268","115","0.536","0.596","1x4","80",1.499,"1123","1194","10.4" TBA,"1","3","19","0.298","115","0.566","0.626","1x6","80",1.567,"1066","1506","10.9" TBA,"1/0","3","19","0.336","115","0.604","0.664","1x6","80",1.649,"1187","1900","11.5" TBA,"2/0","3","19","0.376","115","0.644","0.704","1x4","110",1.795,"1479","2395","12.5" "599070","3/0","3","18","0.422","115","0.691","0.751","1x4","110",1.894,"1783","3020","13.2" "581876","4/0","3","19","0.474","115","0.743","0.803","1x4","110",2.006,"2069","3808","14.0" TBA,"250","3","35","0.520","115","0.796","0.856","1x4","110",2.124,"2085","4500","14.8" "580932","350","3","35","0.615","115","0.892","0.952","1x3","110",2.334,"2808","6300","16.3" TBA,"500","3","35","0.735","115","1.011","1.071","1x2","110",2.588,"3267","9000","18.1" TBA,"750","3","58","0.908","115","1.194","1.254","1x1","135",3.033,"4558","13500","21.2" "All dimensions are nomial and subject to normal manufacturing tolerances" "Table 2 - Electrical and Engineering Data" "Cond. Size","DC Resistance @ 25C","AC Resistance @ 90C","Capacitive Reactance","Inductive Reactance","Zero Sequence Impedance","Positive Sequence Impedance","Shield Short Circuit Current 6 Cycles","Allowable Ampacity In Duct 90/105C","Allowable Ampacity In Air 90/105C" "AWG/Kcmil","ohm/MFT","ohm/MFT","Mohm*MFT","Mohm/MFT","ohm/MFT","ohm/MFT","Amps","Amps","Amps" "2","0.267","0.336","0.036","0.041","0.705 + j0.524","0.336 + j0.041","1877","105/110","110/120" "1","0.211","0.266","0.033","0.039","0.637 + j0.504","0.266 + j0.038","1970","120/130","125/140" "1/0","0.168","0.211","0.030","0.038","0.584 + j0.483","0.211 + j0.037","2088","140/150","145/160" "2/0","0.133","0.167","0.028","0.037","0.542 + j0.462","0.167 + j0.035","2212","160/170","170/185" "3/0","0.105","0.133","0.025","0.035","0.509 + j0.438","0.133 + j0.034","2354","180/195","195/215" "4/0","0.084","0.105","0.023","0.034","0.48 + j0.414","0.105 + j0.033","2515","205/220","225/250" "250","0.071","0.090","0.022","0.034","0.464 + j0.39","0.09 + j0.032","2683","230/245","250/280" "350","0.050","0.065","0.019","0.032","0.434 + j0.353","0.065 + j0.031","2977","280/310","310/345" "500","0.035","0.046","0.016","0.031","0.406 + j0.312","0.046 + j0.029","3349","340/365","385/430" "750","0.024","0.033","0.014","0.029","0.376 + j0.261","0.033 + j0.028","3916","425/460","495/550"